Plan Review Details - Permit 22040625
Plan Review Stops For Permit 22040625
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2022-09-01 Cont ID  
Sent By rmcdouga Date 2022-09-01 Time 17:08 Rev Time 0.00
Received By rmcdouga Date 2022-09-01 Time 17:08 Sent To  
Notes
2022-09-01 17:09:56THE WALL SECTION SHOWS THE FOUNDATION IS 1 INCH INSIDE
 OF THE PROPERTY LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 09:51 Rev Time 0.00
Received By shill Date 2022-08-29 Time 09:51 Sent To  
Notes
2022-08-29 10:15:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST, NOT ADDRESSED.
  
 3. PROVIDE A SITE PLAN THAT SHOWS THE FOOTING RELATIVE
 TO THE PROPERTY LINE, FBC 107.
  
 NOT ADDRESSED. THE SITE PLAN GRAPHICALLY SHOWS THE WALL
 OVER THE PROPERTY LINE. FOOTER IS NOT ECCENTRIC SO THE
 WAY IT IS DESIGNED, THE FOOTER WILL BE INSTALLED ON
 CITY AND NEIGHBORING PROPERTY.
  
 SK-1 INCLUDES A "TYPICAL PRIVACY WALL SECTION" AND
 "SITE / SURVEY". THE SITE WALL DETAIL ON THE SITE PLAN
 IS NOT ECCENTRIC, GRAPHICALLY THE SITE PLAN SHOWS THE
 WALL SLIGHTLY OVER THE PROPERTY LINE. IF INSTALLED AS
 DRAWN THE FOOTER WILL ENCROACH THE PROPERTY LINE BY
 ABOUT A FOOT. THE PROPOSED IMPROVEMENT MUST BE
 INSTALLED ON THE SUBJECT PROPERTY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-07-27 Cont ID  
Sent By shill Date 2022-07-27 Time 06:33 Rev Time 0.00
Received By shill Date 2022-07-27 Time 06:33 Sent To  
Notes
2022-07-27 06:34:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST, NOT ADDRESSED.
  
 3. PROVIDE A SITE PLAN THAT SHOWS THE FOOTING RELATIVE
 TO THE PROPERTY LINE, FBC 107.
  
 NOT ADDRESSED. THE SITE PLAN GRAPHICALLY SHOWS THE WALL
 OVER THE PROPERTY LINE. FOOTER IS NOT ECCENTRIC SO THE
 WAY IT IS DESIGNED, THE FOOTER WILL BE INSTALLED ON
 CITY AND NEIGHBORING PROPERTY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-07-22 Cont ID  
Sent By shill Date 2022-07-22 Time 09:52 Rev Time 0.00
Received By shill Date 2022-07-22 Time 09:52 Sent To  
Notes
2022-07-22 09:56:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 DETAIL NAMED "REID - WALL DETAIL" HAS BEEN LOCKED (WILL
 NOT ISSUE, WILL BE DELETED). THIS REVIEW IS FOR THE
 WALL DETAIL "SITE WALL-SK-1". NUMBERING REMAINS THE
 SAME AS PREVIOUS TWO COMMENT LISTS, COMMENTS ADDRESSED
 HAVE BEEN REMOVED.
  
 1. THE STRUCTURAL DETAIL IS TO INCLUDE WIND DESIGN
 CRITERIA. FBC R 301.
  
 3. PROVIDE A SITE PLAN THAT SHOWS THE FOOTING RELATIVE
 TO THE PROPERTY LINE, FBC 107.
  
 NOT ADDRESSED. THE SITE PLAN GRAPHICALLY SHOWS THE WALL
 OVER THE PROPERTY LINE. FOOTER IS NOT ECCENTRIC SO THE
 WAY IT IS DESIGNED, THE FOOTER WILL BE INSTALLED ON
 CITY AND NEIGHBORING PROPERTY.
  
 5. THE WALL IS SHOWN AS CONTINUOUS. HOW WILL OCCUPANTS
 EXIT THE PROPERTY IN THE EVENT OF AN EMERGENCY? HOW
 WILL OCCUPANTS ACCESS THE PROPERTY? FBC 107. SCOPE OF
 WORK IS NOT CLEAR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-28 Cont ID  
Sent By shill Date 2022-05-28 Time 08:45 Rev Time 0.00
Received By shill Date 2022-05-28 Time 08:44 Sent To  
Notes
2022-05-28 08:50:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED WALL.
 THE STRUCTURAL DETAIL IS TO INCLUDE WIND DESIGN
 CRITERIA. DETAIL IS TO SHOW ALL STUCCO (OR OTHER
 MATERIAL) AND PAINT PROPOSED.
  
 2ND REVIEW, NOT ADDRESSED. THE PLAN SHOWS A PROPOSED
 WALL BEING INSTALLED ON WHAT APPEARS TO BE A MONOLITHIC
 SLAB, CALLS THAT "EXISTING". PROVIE THE PERMIT NUMBER.
 WIND DESIGN CRITERIA NOT PROVIDED. PROVIDE CALCULATIONS
 TO SHOW THAT THE "EXISTING" SLAB IS ADEQUATE TO SUPPORT
 THE PROPOSED BLOCK WALL. WATERPROOFING/PAINT/STUCCO NOT
 SHOWN. IS NONE PROPOSED?
  
 2. FBC 107, THE PLAN IS TO INCLUDE THE PRINTED NAME AND
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE DESIGN. CALCULATIONS MAY BE REQUIRED.
  
 NOT ADDRESSED.
  
 3. PROVIDE A SITE PLAN THAT SHOWS THE FOOTING RELATIVE
 TO THE PROPERTY LINE, FBC 107.
  
 NOT ADDRESSED. THE SITE PLAN GRAPHICALLY SHOWS THE WALL
 OVER THE PROPERTY LINE.
  
 4. DUE TO THE PROPOSED CONSTRUCTION AT THE CITY
 SIDEWALK, AN ENGINEERING REVIEW STOP HAS BEEN ADDED.
  
 5. THE WALL IS SHOWN AS CONTINUOUS. HOW WILL OCCUPANTS
 EXIT THE PROPERTY IN THE EVENT OF AN EMERGENCY? HOW
 WILL OCCUPANTS ACCESS THE PROPERTY? FBC 107. SCOPE OF
 WORK IS NOT CLEAR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-16 Cont ID  
Sent By shill Date 2022-05-16 Time 10:24 Rev Time 0.00
Received By shill Date 2022-05-16 Time 10:24 Sent To  
Notes
2022-05-16 10:27:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107, A PLAN WAS NOT SUBMITTED. PROVIDE A PLAN THAT
 SHOWS THE FOLLOWING:
  
 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED WALL.
 THE STRUCTURAL DETAIL IS TO INCLUDE WIND DESIGN
 CRITERIA. DETAIL IS TO SHOW ALL STUCCO (OR OTHER
 MATERIAL) AND PAINT PROPOSED.
  
 2. FBC 107, THE PLAN IS TO INCLUDE THE PRINTED NAME AND
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE DESIGN. CALCULATIONS MAY BE REQUIRED.
  
 3. PROVIDE A SITE PLAN THAT SHOWS THE FOOTING RELATIVE
 TO THE PROPERTY LINE.

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2022-09-08 Cont ID  
Sent By sberglun Date 2022-09-08 Time 09:41 Rev Time 0.00
Received By sberglun Date 2022-09-08 Time 09:41 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2022-08-29 Cont ID  
Sent By rrossano Date 2022-08-29 Time   Rev Time 0.00
Received By rrossano Date 2022-08-29 Time   Sent To  
Notes
2022-08-29 10:06:26SHOW ANY EXISTING CITY OWNED UTILITIES IN VICINITY OF
 PROPOSED WALL.
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS-DETAILS
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2022-08-02 Cont ID  
Sent By rrossano Date 2022-08-02 Time   Rev Time 0.00
Received By rrossano Date 2022-08-02 Time   Sent To  
Notes
2022-08-02 15:38:51PLEASE ADDRESS BUILDING COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-07-25 Cont ID  
Sent By rrossano Date 2022-07-25 Time   Rev Time 0.00
Received By rrossano Date 2022-07-25 Time   Sent To I
Notes
2022-07-25 15:30:04ADDRESS BUILDING COMMENTS.
  
 GATE MAY NOT SWING OUT/ENCROACH CITY RIGHT OF WAY.
  
 INDICATE ANY CITY UTILITIES ON PLANS AS PER PREVIOUS
 COMMENT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-05-31 Cont ID  
Sent By rrossano Date 2022-05-31 Time   Rev Time 0.00
Received By rrossano Date 2022-05-31 Time   Sent To  
Notes
2022-05-31 08:11:35PLEASE SHOW EXISTING WATER METER AND SANITARY CLEANOUT
 FOR PROPERTY; BOTH SHALL REMAIN ACCESSIBLE AS POINTS OF
 SERVICE FOR MAINTANANCE BY CITY STAFF FOR WATER AND
 SEWER SERVICES. ADJUST PROPOSED FENCE ACCORDINGLY.
  
 YOU MAY CALL 811 FOR UTILITY LOCATES AT NO CHARGE. MORE
 INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORDINATOR, CITY OF WPB
 ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected] HTTPS://WWW.WPB.ORG/GOVERNMENT/
 ENGINEERING/ENGINEERING-STANDARDS-DETAILS
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-06-06 Cont ID  
Sent By amhamilt Date 2022-06-06 Time 12:43 Rev Time 0.00
Received By amhamilt Date 2022-06-06 Time 12:43 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-05-02 Cont ID  
Sent By amhamilt Date 2022-05-02 Time 16:47 Rev Time 0.00
Received By amhamilt Date 2022-05-02 Time 16:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-09-20 Cont ID  
Sent By shill Date 2022-09-20 Time 17:48 Rev Time 0.00
Received By shill Date 2022-08-29 Time 16:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 10:15 Rev Time 0.00
Received By shill Date 2022-08-23 Time 07:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-17 Cont ID  
Sent By aoliver Date 2022-08-17 Time 06:50 Rev Time 0.00
Received By aoliver Date 2022-07-26 Time 16:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-25 Cont ID  
Sent By lmarchan Date 2022-07-25 Time 16:48 Rev Time 0.00
Received By lmarchan Date 2022-07-21 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-07 Cont ID  
Sent By lmarchan Date 2022-06-07 Time 07:42 Rev Time 0.00
Received By lmarchan Date 2022-05-24 Time 10:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-16 Cont ID  
Sent By shill Date 2022-05-16 Time 10:27 Rev Time 0.00
Received By shill Date 2022-04-15 Time 12:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-09-01 Cont ID  
Sent By rmcdouga Date 2022-09-01 Time 17:07 Rev Time 0.00
Received By rmcdouga Date 2022-09-01 Time 17:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 10:15 Rev Time 0.00
Received By shill Date 2022-08-29 Time 10:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-27 Cont ID  
Sent By shill Date 2022-07-27 Time 06:35 Rev Time 0.00
Received By shill Date 2022-07-27 Time 06:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-22 Cont ID  
Sent By shill Date 2022-07-22 Time 09:56 Rev Time 0.00
Received By shill Date 2022-07-22 Time 09:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-05-16 Cont ID  
Sent By shill Date 2022-05-16 Time 10:27 Rev Time 0.00
Received By shill Date 2022-05-16 Time 10:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2022-09-19 Cont ID  
Sent By amhamilt Date 2022-09-19 Time 16:13 Rev Time 0.00
Received By amhamilt Date 2022-09-19 Time 16:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2022-08-25 Cont ID  
Sent By amhamilt Date 2022-08-25 Time 11:21 Rev Time 0.00
Received By amhamilt Date 2022-08-25 Time 11:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2022-08-16 Cont ID  
Sent By amhamilt Date 2022-08-16 Time 16:43 Rev Time 0.00
Received By amhamilt Date 2022-08-16 Time 16:43 Sent To  
Notes
2022-08-16 16:45:37THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 FOOTER CANNOT EXTEND OUTSIDE OF PROPERTY LINE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-06-06 Cont ID  
Sent By amhamilt Date 2022-06-06 Time 12:43 Rev Time 0.00
Received By amhamilt Date 2022-06-06 Time 12:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-05-02 Cont ID  
Sent By amhamilt Date 2022-05-02 Time 16:45 Rev Time 0.00
Received By amhamilt Date 2022-05-02 Time 16:45 Sent To  
Notes
2022-05-02 16:45:43THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 WALLS CANNOT EXCEED 4FT IN HEIGHT WITHIN THE FRONT 25
 FT SETBACK. PLEASE REVISE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  