| Plan Review Stops For Permit 22040597 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2023-03-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-24 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-24 |
Time |
08:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-16 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-16 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2023-03-16 11:01:06 | 3RD REVIEW FBC-2020 RES. GAS | | | PERMIT- 22040597 | | | 3/16/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. THE PLAN HAS FAILED FOR A | | | THIRD TIME. PLEASE REVIEW THE COMMENTS AND IF YOU NEED | | | FURTHER ASSISTANCE PLEASE CONTACT ME. | | | | | | 1) GAS RISER: SHOW THE MAIN SUPPLY PIPE AND SIZE AT THE | | | METER AND THE PIPING CONNECTIONS TO THE TANKLESS WATER | | | HEATER, THE RANGE, AND THE NEW PE RISER CONNECTION | | | SUPPLYING THE POOL HEATER- SEC. G2412.3 & G2412.4 FBC- | | | RES. | | | 2) GAS RISER: THE CURRENT DRAWING SHOWS A LOW PRESSURE- | | | LESS THAN 2 PSI SYSTEM IS SUPPLYING ONLY THE POOL | | | HEATER. PLEASE REFER TO TABLES G2413.4(1) & G2413.4(7) | | | FBC RES AND PROVIDE THE FOLLOWING CORRECTIONS. | | | A) ENLARGE THE 3/4-INCH PE PIPE TO 1-INCH. | | | B) ENLARGE THE 3/4-INCH GALV. PIPE TO 1-INCH. | | | | | | 2) 2ND REQUEST TO PROVIDE A BASIC SITE PLAN THAT SHOWS | | | THE LOCATIONS OF THE METER, POOL HEATER, AND THE NEW | | | APPLIANCES SPECIFICED ON THE RESUBMITTED DRAWING- | | | TANKLESS WATER HEATER AND RANGE- SEC. 107.2.1 WPB. THE | | | DRAWING SHALL SHOW THE FOLLOWING ITEMS. | | | A) INSTALLATION CLEARANCES FOR THE POOL HEATER- MINIMUM | | | 4FT. FROM OPENINGS INTO THE BUILDING- SEC. G2427.8 FBC | | | RES. | | | B) INSTALLATION CLEARANCES FOR THE TANKLESS WATER | | | HEATER- MINIMUM 4FT. FROM OPENINGS INTO THE BUILDING- | | | SEC. G2427.8 & G2448.1 FBC RES. | | | C) COMBUSTION AIR CALCULATIONS FOR THE GAS RANGE. | | | PLEASE NOTE IF USING THE STANDARD METHOD OF INDOOR AIR | | | VOLUME, A TOTAL OF 900 CU.FT. IS REQUIRED. PLEASE NOTE | | | A STANDARD GAS RANGE IS VERY TYPICALLY AROUND 50,000 | | | BTUS. IS THE 18,000 SPECIFIED A MISTAKE? | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-02-13 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-02-13 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2023-02-13 10:41:47 | 2ND REVIEW FBC-2020 RES. GAS | | | PERMIT- 22040597 | | | 2/13/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED 1ST REVIEW COMMENTS | | | ARE LISTED BELOW WITH ADDITIONAL NOTES. PLEASE CONTACT | | | ME IF YOU HAVE QUESTIONS. | | | | | | 1) GAS RISER: ADDITIONAL INFORMATION REQUIRED ON THE | | | DRAWING- CHAPTER 24 FBC RES. | | | | | | A) SHOW THE GAS SYSTEM PRESSURE- 2 PSI OR LOW | | | PRESSURE.. | | | B) SHOW A REGULATOR AND SHUT OFF VALVE AT WATER HEATER. | | | C) SHOW THE TYPE AND SIZE OF MAIN SUPPLY PIPE FROM THE | | | METER TO THE PE RISER. | | | D) SHOW THE TYPE AND SIZE OF SUPPLY PIPE FROM THE | | | REGULATOR AT THE POOL HEATER TO THE HEATER. | | | E) SHOW PIPE CONNECTION AT THE METER TO EXISTING | | | APPLIANCES AND PROVIDE THE TOTAL BTU LOAD OF THE | | | EXISTING APPLIANCES AND THE NEW POOL HEATER. | | | | | | 2) PROVIDE A BASIC SITE PLAN THAT SHOWS THE LOCATIONS | | | OF THE METER, POOL HEATER, AND UNDERGROUND PIPING RUN- | | | SEC. 107.2.1 WPB. PLEASE INCLUDE THE INSTALLATION | | | CLEARANCES FOR THE POOL HEATER- MINIMUM 4FT. FROM | | | OPENINGS INTO THE BUILDING- SEC. G2427.8 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-09-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-14 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-14 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2022-09-14 16:52:52 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 22040597 | | | 9/14/22 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) GAS RISER: ADDITIONAL INFORMATION REQUIRED ON THE | | | DRAWING- CHAPTER 24 FBC RES- | | | | | | A) GAS SYSTEM PRESSURE. | | | B) REGULATOR AND SHUT OFF VALVE AT WATER HEATER. | | | C) TYPE AND SIZE OF SUPPLY FROM THE METER TO THE PE | | | RISER. | | | D) TYPE AND SIZE OF SUPPLY PIPE FROM THE PE TO THE POOL | | | HEATER. | | | E) TYPES AND SIZES OF PIPING TO EXISTING APPLIANCES AT | | | THE RESIDENCE. | | | F) BTU LOADS OF EXISTING APPLIANCES. | | | G) PRINTED NAME AND SIGNATURE OF THE CONTRACTOR OR | | | QUALIFIER OF RECORD WHO PREPARED THE DRAWING- SEC. | | | 107.2.1 WPB. | | | | | | 2) PROVIDE A BASIC SITE PLAN THAT SHOWS THE LOCATIONS | | | OF THE METER, POOL HEATER, AND UNDERGROUND PIPING RUN- | | | SEC. 107.2.1 WPB. PLEASE INCLUDE THE INSTALLATION | | | CLEARANCES FOR THE POOL HEATER- MINIMUM 4FT. FROM | | | OPENINGS INTO THE BUILDING- SEC. G2427.8 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-03-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-23 |
Time |
07:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-03-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-15 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-02-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-02-10 |
Time |
16:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-09-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
cdecoeur |
Date |
2022-09-14 |
Time |
07:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2023-03-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-24 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-24 |
Time |
08:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-16 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-16 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2023-03-16 11:05:05 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22040597 | | | 3/16/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE REVISED GAS RISER SHOWS A NEW TANKLESS WATER | | | HEATER WHICH WILL REQUIRE A PLUMBING SUB-PERMIT | | | APPLICATION TO BE SUBMITTED- SEC. 105.1 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-02-13 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-02-13 |
Time |
09:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2022-09-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-14 |
Time |
16:53 |
Rev Time |
|
| Received By |
ccole |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-03-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-24 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-24 |
Time |
08:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-16 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-16 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-02-13 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-02-13 |
Time |
10:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-09-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-14 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-14 |
Time |
16:53 |
Sent To |
|
|
| Notes |
|
|