| 2022-05-04 09:42:23 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22040577 |
| | ADD: 2425 PRESIDENTIAL WAY # 606 |
| | CONT: LAR CONSTRUCTION |
| | TEL: 561-853-6608 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 5/04/2022 |
| | ACTION: DENIED |
| | |
| | 1) THE FLOOR PLAN A-1 BY LAR CONSTRUCTION NEEDS TO |
| | COMPLY WITH CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE |
| | CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF |
| | PLANS AND OR SCHEDULES WILL NEED TO IDENTIFY THEMSELVES |
| | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| | LICENSED IN AND PLANS AND OR SCHEDULES DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE |
| | LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR |
| | THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE |
| | CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF |
| | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF |
| | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| | PLANS DRAWN. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |
| | 2) NOTE # 6 STATES REPLACE THE EXISTING FLOOR FOR |
| | VINYL. INSTALL INTERTEK G8060.01-113.11.R1. PLEASE |
| | REVIEW THE SUBMITTED INTERTEK REPORT IS FOR A 6 INCH |
| | CONCRETE SLAB WITH DROP CEILING FILLED WITH R-13 |
| | INSULATION. |
| | FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| | STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND |
| | WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| | CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| | CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| | THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253. |
| | |
| | 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |