Plan Review Details - Permit 22040572
Plan Review Stops For Permit 22040572
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-25 Cont ID  
Sent By rmcdouga Date 2022-08-25 Time 14:55 Rev Time 0.00
Received By rmcdouga Date 2022-08-25 Time 14:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By rmcdouga Date 2022-07-19 Time 11:18 Rev Time 0.00
Received By rmcdouga Date 2022-07-19 Time 10:56 Sent To  
Notes
2022-07-19 11:18:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A SURVEY SHOWING THE LOCATION OF THE EXISTING
 POOL PERMIT AND THE PROPOSED LOCATION. FBC 107.2.1
  
 2) PROVIDE DETAILS FOR THE NEW POOL EQUIPMENT PAD AND
 SPECIFY HOW THE POOL EQUIPMENT WILL BE ANCHORED TO
 RESIST WIND LOADS. FBC-R301.2.1
  
 3) IT APPEARS THAT THE POOL EQUIPMENT WILL BE TOO CLOSE
 TO THE A/C EQUIPMENT. IT MAY AFFECT CLEARANCES FOR AIR
 CIRCULATION AND MAINTAINENCE. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-09 Cont ID  
Sent By ppetty Date 2022-06-09 Time 09:24 Rev Time 0.00
Received By ppetty Date 2022-06-09 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-25 Cont ID  
Sent By rmcdouga Date 2022-08-25 Time 14:55 Rev Time 0.00
Received By rmcdouga Date 2022-07-27 Time 07:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-20 Cont ID  
Sent By medwards Date 2022-07-20 Time 07:44 Rev Time 0.00
Received By medwards Date 2022-05-19 Time 05:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-07-28 Cont ID  
Sent By medwards Date 2022-07-28 Time 08:48 Rev Time 0.00
Received By medwards Date 2022-07-28 Time 08:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-20 Cont ID  
Sent By medwards Date 2022-07-20 Time 07:29 Rev Time 0.00
Received By medwards Date 2022-07-20 Time 07:29 Sent To  
Notes
2022-07-20 07:34:37PROVIDE A DRAWING SHOWING THAT THE CLEARANCES FOR THE
 CONDENSING UNIT WILL BE MAINTAINED. FRC M1305.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-07-28 Cont ID  
Sent By ccole Date 2022-07-28 Time 07:52 Rev Time 0.00
Received By ccole Date 2022-07-28 Time 07:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-31 Cont ID  
Sent By ccole Date 2022-05-31 Time 13:41 Rev Time 0.00
Received By ccole Date 2022-05-31 Time 13:20 Sent To  
Notes
2022-05-31 13:42:191ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22040572
 5/31/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A DRAWING SHOWING THE EXISTING AND
 PROPOSED LOCATIONS OF THE POOL EQUIPMENT AND PIPING-
 SEC. 107.2.1 WPB. THE SUBMITTED PHOTO IS ACCEPTABLE AS
 SUPPLEMENTAL INFORMATION ONLY. PLEASE PROVIDE A SCOPE
 OF WORK ON THE DRAWING, WORKING CLEARANCES, AND PAD AND
 ANCHORING DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-07-28 Cont ID  
Sent By medwards Date 2022-07-28 Time 08:50 Rev Time 0.00
Received By medwards Date 2022-07-28 Time 08:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By rmcdouga Date 2022-07-19 Time 11:18 Rev Time 0.00
Received By rmcdouga Date 2022-07-19 Time 11:18 Sent To  
Notes
2022-07-19 11:21:07IF ELECTRONIC DOCUMENTS FROM AN ARCHITECT OR ENGINEER
 ARE SUBMITTED THE DESIGN PROFESSIONAL'S DIGITAL
 SIGNATURE IS REQUIRED. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15

Review Stop Z ZONING
Rev No 2 Status P Date 2022-07-28 Cont ID  
Sent By afowlkes Date 2022-07-28 Time 15:16 Rev Time 0.00
Received By afowlkes Date 2022-07-28 Time 15:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-05-24 Cont ID  
Sent By afowlkes Date 2022-05-24 Time 10:04 Rev Time 0.00
Received By afowlkes Date 2022-05-24 Time 10:04 Sent To  
Notes
2022-05-24 10:05:2505/24/22 FAILED - IMPROVEMENTS NEED TO BE SHOWN ON A
 SURVEY.
  
 PER CITY CODE, MECHANICAL EQUIPMENT CANNOT PROTRUDE
 MORE THAN 4 FEET INTO ANY SETBACK.
  
 ALEXANDER FOWLKES
 5618221431
 [email protected]