Plan Review Details - Permit 22040557
Plan Review Stops For Permit 22040557
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-12-19 Cont ID  
Sent By pvalenti Date 2022-12-19 Time 09:43 Rev Time 0.00
Received By pvalenti Date 2022-12-19 Time 09:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-11-29 Cont ID  
Sent By pvalenti Date 2022-11-29 Time 07:42 Rev Time 0.00
Received By pvalenti Date 2022-11-29 Time 07:17 Sent To  
Notes
2022-11-29 08:20:28PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC R 322.2.2.1, THERE MUST BE NO LESS THAN (2)
 OPENINGS/FLOOD VENTS ON DIFFERENT SIDES OF THE ENCLOSED
 AREA. THE SOUTH SIDE OF GARAGE ONLY HAS (1) OPENING.
 THE NFIP REVIEW STOP NEEDS TO BE APPROVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-30 Cont ID  
Sent By pvalenti Date 2022-06-30 Time 08:55 Rev Time 0.00
Received By pvalenti Date 2022-06-29 Time 12:10 Sent To  
Notes
2022-06-30 10:26:18PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1 & FBC R 401.3, PROVIDE A DRAINAGE
 PLAN INDICATING THE DIRECTIONS OF SURFACE WATER FLOW.
 2.) FBC B 107.2.1 & FBC B 107.2.6, PROVIDE A SURVEY &
 SITE PLAN COMPLETE WITH ELEVATIONS (EXISTING &
 PROPOSED) AND SET BACKS MEASUREMENTS.
 3.) FBC B 107.2.1, PROVIDE APPROVED REVIEW STAMPS BY
 THE DESIGNER OF RECORD ON ALL PRODUCT APPROVALS.
 4.) FBC B 107.2.1 & FBC R 703.7.3, THE WOOD FRAMED
 TRUSS GABLE END AREAS ARE TO MEET THE REQUIREMENTS OF
 WATER RESISTIVE BARRIERS (TYPICALLY 2-LAYERS OF
 MOISTURE BARRIER BETWEEN SHEATHING AND LATH). PLEASE
 SHOW ON PLANS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-18 Cont ID  
Sent By mpeterso Date 2022-10-18 Time 15:23 Rev Time 0.00
Received By mpeterso Date 2022-10-18 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-19 Cont ID  
Sent By mpeterso Date 2022-05-19 Time 14:36 Rev Time 0.00
Received By mpeterso Date 2022-05-19 Time 14:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-09 Cont ID  
Sent By vbroglia Date 2023-01-09 Time 16:28 Rev Time 0.00
Received By vbroglia Date 2022-12-19 Time 08:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-30 Cont ID  
Sent By pvalenti Date 2022-11-30 Time 17:31 Rev Time 0.00
Received By pvalenti Date 2022-10-04 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-30 Cont ID  
Sent By pvalenti Date 2022-06-30 Time 10:27 Rev Time 0.00
Received By pvalenti Date 2022-04-21 Time 05:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-12-22 Cont ID  
Sent By aoliver Date 2022-12-22 Time 07:50 Rev Time 0.00
Received By aoliver Date 2022-12-22 Time 07:50 Sent To  
Notes
2022-12-22 07:53:09NO IMPACT FEES DUE, SEE EMAIL UPLOADED AO
2022-12-19 08:44:0612/19/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-06-30 Cont ID  
Sent By pvalenti Date 2022-06-30 Time 08:07 Rev Time 0.00
Received By pvalenti Date 2022-06-29 Time 12:10 Sent To  
Notes
2022-06-30 08:30:06IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-05-06 Cont ID  
Sent By medwards Date 2022-05-06 Time 06:29 Rev Time 0.00
Received By medwards Date 2022-05-06 Time 06:29 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2022-12-19 Cont ID  
Sent By pvalenti Date 2022-12-19 Time 09:42 Rev Time 0.00
Received By pvalenti Date 2022-12-19 Time 09:06 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-11-30 Cont ID  
Sent By pvalenti Date 2022-11-30 Time 09:53 Rev Time 0.00
Received By pvalenti Date 2022-11-29 Time 08:21 Sent To  
Notes
2022-11-30 10:59:45PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 NFIP REVIEW DENIED:
  
 1. FBC B 107.2.1, PROVIDE THE PRODUCT APPROVAL FOR THE
 MASTER FLOW FLOOD VENTS THAT ARE INDICATED ON PLAN
 SHEET A-101.
 2. FBC R 322.2.2.1, AN ADDITIONAL FLOOD VENT IS
 REQUIRED AT THE REAR WALL OF GARAGE (2 OPENINGS ON
 DIFFERENT SIDES OF ENCLOSED AREA). PLEASE SHOW ALL
 FLOOD OPENINGS ON PLAN SHEETS.
 3. SECTION A-4 OF THE ELEVATION CERTIFICATE, PLEASE
 CLARIFY AS IT APPEARS THAT THIS SHOULD BE ATTACHED
 GARAGE IN-LIEU OF NON-RESIDENTIAL.
 4. SECTION A-9(B) OF THE ELEVATION CERTIFICATE, IT
 APPEARS THAT THE NUMBER OF PERMANENT FLOOD OPENINGS
 SHOULD BE (4) IN-LIEU OF (0). PLEASE ADJUST ELEVATION
 CERTIFICATE.
 5. SECTION A-9(C) OF THE ELEVATION CERTIFICATE, IT
 APPEARS THAT THE TOTAL NET AREA OF THE FLOOD OPENINGS
 SHOULD NOT BE (0). THIS NUMBER SHOULD BE 4X THE NET
 AREA OF EACH FLOOD OPENING. PLEASE ADJUST ELEVATION
 CERTIFICATE.
 6. SECTION D (COMMENTS) OF THE ELEVATION CERTIFICATE;
 PLEASE CLARIFY WHAT EQUIPMENT AND LOCATION OF EQUIPMENT
 PER INDICATIONS IN SECTION C2 E. ALSO CLARIFY "LARC
 3.7' IN THIS SECTION D COMMENTS.
  
  
  
 NOTE: ADDITIONAL INFORMATION WILL BE REQUIRED WHEN
 SUBMITTING THE ELEVATION CERTIFICATE FOR THE "BUILDING
 UNDER CONSTRUCTION" AND "FINISHED CONSTRUCTION" PHASES.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-06-30 Cont ID  
Sent By pvalenti Date 2022-06-30 Time 06:25 Rev Time 0.00
Received By pvalenti Date 2022-06-30 Time 06:25 Sent To  
Notes
2022-06-30 06:35:46PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 NFIP REVIEW DENIED:
  
 FBC B 107.2.1, FBC R 322.1, PLEASE SUBMIT A FEMA NFIP
 ELEVATION CERTIFICATE AND A SURVEY COMPLETE WITH
 ELEVATIONS.
 NOTE: FBC R 322.2.2.1, FLOOD VENTS MAY BE REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-10-06 Cont ID  
Sent By rwbrown Date 2022-10-06 Time 14:26 Rev Time 0.00
Received By rwbrown Date 2022-10-06 Time 14:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-05-02 Cont ID  
Sent By rwbrown Date 2022-05-02 Time 14:51 Rev Time 0.00
Received By rwbrown Date 2022-05-02 Time 14:51 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-06-30 Cont ID  
Sent By pvalenti Date 2022-06-30 Time 06:36 Rev Time 0.00
Received By pvalenti Date 2022-06-29 Time 12:10 Sent To  
Notes
2022-06-30 06:38:08PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ROOFING REVIEW APPROVED WITH NOTE:
  
 PRIOR TO ANY ROOF WORK A ROOFING SUB-PERMIT IS
 REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-19 Cont ID  
Sent By dbattles Date 2022-12-19 Time 08:28 Rev Time 0.00
Received By dbattles Date 2022-12-19 Time 08:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-11-08 Cont ID  
Sent By rwbrown Date 2022-11-08 Time 13:18 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-11-08 13:19:13SIGNATURE REVIEW FAILED - SEVERAL OF THE FILES ARE NOT
 ELECTRONICALLY SEALED, MOST OF THE A PAGES AND S PAGES,
 TOO MANY TO LIST INDIVIDUALLY.
  
 * PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS
 PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001
 AND BE EITHER DIGITALLY SIGNED AND SEALED -OR-
 ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH
 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY.
 * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-19 Cont ID  
Sent By mpeterso Date 2022-05-19 Time 14:46 Rev Time 0.00
Received By mpeterso Date 2022-05-19 Time 14:45 Sent To  
Notes
2022-05-19 14:48:03SIGNATURE REVIEW FAILED
  
 1)IT APPEARS ALL DRAWINGS ARE COPIES/SCANS OF
 ENGINEERED, DIGITALLY SIGNED AND SEALED DRAWINGS. PLANS
 SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED AND
 SEALED BY THE ENGINEER OF RECORD. PLEASE FOLLOW THE
 DIRECTIONS OUTLINED BELOW TO CORRECT THIS ISSUE.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING
 DEPARTMENT.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
 PLEASE EMAIL [email protected] AND CC TO
 [email protected] WITH ANY QUESTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
2022-05-02 14:52:21PLUMBING PAGES NOT SIGNED

Review Stop Z ZONING
Rev No 3 Status P Date 2023-01-09 Cont ID  
Sent By VBroglia Date 2023-01-09 Time 16:28 Rev Time 0.00
Received By vbroglia Date 2023-01-09 Time 16:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-10-19 Cont ID  
Sent By afowlkes Date 2022-10-19 Time 16:06 Rev Time 0.00
Received By afowlkes Date 2022-11-08 Time 10:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-25 Cont ID  
Sent By afowlkes Date 2022-04-25 Time 15:19 Rev Time 0.00
Received By afowlkes Date 2022-04-25 Time 15:08 Sent To  
Notes
2022-04-25 15:09:0604/25/22 FAILED - NEED TO KNOW THE TOTAL SIDE SETBACK
 OF THE HOUSE (BOTH SIDES MUST BE GREATER OR EQUAL TO 15
 FT)
  
 ALSO NEED TO KNOW THE ROOF OVERHANG DISTANCE OF THE NEW
 EXPANISON
  
 AND PLEAS ENOTW THAT A SEPERATE PERMIT IS REQUIRED FOR
 DRIVEWAY EXPANSIONS.
  
 ALEXANDER FOWLKES
 5618221431
 [email protected]