| Plan Review Stops For Permit 22040542 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2022-08-10 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-08-10 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-08-10 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2022-08-10 11:31:14 | ADDRESS UPDATED TO 132 VALENCIA RD |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-04-27 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-04-27 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2022-04-27 15:27:29 | MAIN ENTRANCE FACES VALENCIA RD, THE ADDRESS FOR THE | | | PROPERTY WILL NEED TO BE CHANGED TO VALENCIA RD. PLEASE | | | HAVE OWNER CONTACT [email protected] OR CALL 561-805-6659 | | | TO DISCUSS ADDRESSING OPTIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-07 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-07 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-07 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-07 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2022-09-07 15:04:27 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA | | | PRODUCT APPROVALS FL10765, FL11002, FL18655, FL21061, | | | FL21195, FL5259, FL15279, FL6332 AND FL17908. FRONT | | | PAGES ARE NEEDED TO DETERMINE IF THE PRODUCT IS | | | APPROVED BY THE FLORIDA PRODUCT APPROVAL SYSTEM. | | | | | | 2) DOOR AND WINDOW OPENING WIND PRESSURES SHOULD BE | | | SHOWN - WHEN USING THE WIND DESIGN PRESSURES IN FBC | | | TABLER301.2(2) - SOME OF THE PRODUCT APPROVALS FOR THE | | | WINDOWS AND DOORS IN WIND ZONE 5 MAY NOT MEET THE | | | REQUIRED WIND PRESSURES - PLEASE AT LEAST SHOW BUILDING | | | WIND ZONE 5 LOCATIONS. | | | | | | 3) THE DRAWINGS PROVIDED FOR THE OVERHEAD DOOR PRODUCT | | | APPROVAL FL15279 ARE FOR A 16' WIDE DOOR (DRAWINGS SHOW | | | DOOR TO BE 18' WIDE) AND DO NOT MEET THE REQUIRED WIND | | | DESIGN PRESSURES PER FBC TABLER301.2(2) | | | | | | 4) THE DRAWINGS PROVIDED FOR PRODUCT APPROVAL FL11002 - | | | CASEMENT WINDOWS DO NOT MEET IMPACT REQUIREMENTS - | | | PLEASE PROVIDE THE REQUIRED SHUTTER PRODUCT APPROVALS. | | | | | | 5) CANNOT FIND PRODUCT APPROVAL FL20107 FOR THE | | | NANAWALL DOOR IN PROJECTDOX - AS LISTED ON THE DRAWINGS | | | DOOR SCHEDULE. | | | | | | 6) DRAWING A403 SAYS TO SEE CUT SECTION A-502 - DRAWING | | | A-502 IS NOT IN PROJECTDOX. | | | | | | 7) DRAWING A-403 SHOWS A GUARD HEIGHT OF 2'10" (PLEASE | | | SHOW GUARD HEIGHT TO COMPLY WITH FBC R312.1.2) - | | | DRAWING A-401 SHOWS AN ADDED RAILING WITH A HEIGHT OF | | | 3' FOR THE GUARD HEIGHT (PLEASE SHOW ALL GUARD RAIL | | | HEIGHTS) | | | | | | 8) PROPOSED ELEVATION OF THE MECHANICAL EQUIPMENT | | | SERVICING THE BUILDING SHOULD BE SHOWN ON THE DRAWINGS | | | FBC R322.1.6 | | | | | | 9) ELEVATION CERTIFICATE - DOES NOT SHOW AS | | | DIGITALLY/ELECTRONICALLY SIGNED. | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-08-18 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-18 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2022-08-18 10:30:42 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA | | | PRODUCT APPROVALS FL18655, FL21061, FL21195, FL5259, | | | FL15279, FL6332 AND FL17908. FRONT PAGES ARE NEEDED TO | | | DETERMINE IF THE PRODUCT IS APPROVED BY THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. | | | | | | 2) PLEASE PROVIDE A NOTE ON THE DRAWINGS FOR THE | | | TERMITE PROTECTION - FBC R318 | | | | | | 3) THE ELEVATION CERTIFICATE NEEDS CORRECTIONS - C2(A) | | | ELEVATION SHOWN SHOULD BE THE LOWEST FLOOR ELEVATION | | | (LIVING ROOM IS LOWER THAN MAIN HOUSE) - FBC | | | 107.3.5.1.1 | | | | | | 4) DRAWING A-101.1 SHOWS THE GARAGE FLOOR AT 9.00 AT | | | THE DOOR TO THE LIVING SPACE - - PLEASE SHOW THE LOWEST | | | FLOOR ELEVATION AT THE OVERHEAD DOOR OPENING - - OR YOU | | | WILL NEED TO SHOW FLOOD VENTS PER FBC R322.2.2 - | | | | | | 5) UNABLE TO FIND THE INTERIOR DOOR SCHEDULE - R302.5.1 | | | OPENING PROTECTION. | | | OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM | | | USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED. | | | OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL | | | BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 13/8 | | | INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMBCORE | | | STEEL DOORS NOT LESS THAN 13/8 INCHES (35 MM) THICK, OR | | | 20-MINUTE FIRE-RATED DOORS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-07 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-06 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2022-07-07 10:42:43 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA | | | PRODUCT APPROVALS LISTED ON THE DRAWINGS. FRONT PAGES | | | ARE NEEDED TO DETERMINE IF THE PRODUCT IS APPROVED BY | | | THE FLORIDA PRODUCT APPROVAL SYSTEM. | | | | | | 2) PLEASE SHOW THE SITE STORM WATER DRAINAGE ON THE | | | SITE PLAN OR PROVIDE A SEPARATE STORM WATER PLAN. FBC | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT | | | SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) | | | | | | 3) PLEASE SHOW THE TYPE OF TERMITE PROTECTION - FBC | | | R318 | | | | | | 4) DRAWING S-500 ROOF WIND LOADS - PLEASE SHOW THE WIND | | | PRESSURES FOR ALL ROOF ZONES INVOLVED | | | (1,2E,2N,2R,3,3E,3R ETC..) PER FBC TABLE R301.2(2) | | | | | | 5) ON THE PROVIDED ROOF TILE UNDERLAYMENT PRODUCT | | | APPROVAL - THERE ARE MANY DIFFERENT SYSTEMS TO BE USED | | | - PLEASE CIRCLE THE ROOF SYSTEM TO BE USED ON THE | | | PRODUCT APPROVAL MAKING SURE THAT THE WIND PRESSURE | | | MEETS THE REQUIRED WIND PRESSURE PER THE DRAWINGS. | | | | | | 6) THE NANA FOLDING DOOR PRODUCT APPROVAL PROVIDED HAS | | | A HEIGHT LIMIT AT 8' - THE DRAWINGS SHOW THE DOOR TO BE | | | 10' HIGH - PLEASE CLARIFY. | | | | | | 7) PLEASE SHOW THE EQUIPMENT PAD ELEVATIONS TO MEET THE | | | FEMA AND CITY ORD. REQUIREMENTS (2' ABOVE BASE FLOOD | | | ELEVATION) SEC. 18-296 (A) (5) AND FBC R322.1.6 | | | | | | 8) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - | | | FBC 107.3.5.1.1 | | | | | | 9) A SEPARATE PERMIT IS REQUIRED FOR - EXISTING | | | BUILDING DEMO, POOL LOGGIA, SITEWALL, FENCING. PLEASE | | | ACKNOWLEDGE THIS. | | | | | | 10) STRUCTURAL DRAWINGS SHOW A SLOPE ON THE GARAGE SLAB | | | AS IT SHOULD - PLEASE SHOW THE LOWEST FLOOR ELEVATION | | | AT THE DOOR OPENING - - OR YOU WILL NEED TO SHOW FLOOD | | | VENTS PER FBC R322.2.2 - ELEVATION OF THE MIN. 9.00 | | | NAVD IS SHOWN IN THE CENTER OF THE GARAGE - NEAR THE | | | DOOR WILL BE LOWER THAN THE 2' ABOVE FEMA BASE FLOD | | | ELEVATION - WHICH WILL REQUIRE FLOOD VENTS FOR THE | | | GARAGE WALLS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-09-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-09-15 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-09-15 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-08-17 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-08-17 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-08-17 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2022-08-17 09:06:28 | ELECTRIC REVIEW FAILED | | | 1) CONDUCTORS DETAILED, ON SHEET E 100, AS 2 SETS OF | | | 1/0, WITH AN MAXIMUM AMPACITY OF 300 AMPS, BETWEEN ATS, | | | AND LOAD CENTER, A, ARE INCORRECTLY SIZED, AS PER NEC | | | 310.15 (B)(7)(2) AND NEC 110.14 (C)(1)(B)(1) AND (2). | | | CONDUCTORS OVER 100 AMPERES SHALL BE LIMITED TO SIZING | | | AT 75 DEGREE C TEMPERATURES AND SERVICE CONDUCTORS OR | | | FEEDERS SERVING THE ENTIRE LOAD OF A SINGLE-FAMILY | | | DWELLING SHALL BE SIZED AT 83% OF THE SERVICE RATING. | | | THESE CONDUCTORS SHOULD BE SIZED FOR A MINIMUM AMPACITY | | | OF 400 AMP X 83% = 332 AMPS. PLEASE CORRECT CONDUCTOR | | | SIZE AS APPLICABLE. | | | 2) CONDUCTORS DETAILED, ON SHEET E 100, AS 2/0, WITH A | | | MAXIMUM AMPACITY OF 175 AMPS, BETWEEN LOAD CENTER, A, | | | AND LOAD CENTER, MP, ARE INCORRECTLY SIZED, AS PER NEC | | | 310.15 AND NEC 110.14 (C)(1)(B)(1) AND (2). CONDUCTORS | | | OVER 100 AMPERES SHALL BE LIMITED TO SIZING AT 75 | | | DEGREE C TEMPERATURES AND SERVICE CONDUCTORS OR | | | FEEDERS, ONLY, SERVING THE ENTIRE LOAD OF A | | | SINGLE-FAMILY DWELLING SHALL BE SIZED AT 83% OF THE | | | SERVICE RATING. THESE CONDUCTORS DO NOT FEED THE ENTIRE | | | LOAD OF THE DWELLING, AND, THEREFORE, MUST BE SIZED AT | | | 100 %. THESE CONDUCTORS SHOULD BE SIZED FOR A MINIMUM | | | AMPACITY OF 200 AMPERES. PLEASE CORRECT CONDUCTOR SIZE | | | AS APPLICABLE. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-05-24 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-05-24 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-24 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2022-05-24 09:43:29 | ELECTRIC REVIEW FAILED | | | 1) IT APPEARS THE ELECTRICAL RISER DIAGRAM IS | | | ATTEMPTING TO DETAIL A 300 AMP SERVICE. THE METER MAIN | | | IS DETAILED AS 400-AMP. PLEASE DETAIL THE OVERCURRENT | | | PROTECTION IN THIS METER MAIN AS 300-AMP OR DETAIL HOW | | | THIS RISER COMPLIES WITH NEC 110.3, NEC 310.15 | | | 2) PLEASE DETAIL CONDUCTOR SIZES BETWEEN METER MAIN AND | | | ATS. NEC 215.5 | | | 3) IT APPEARS LOAD CENTER B IS FED WITH INCORRECT SIZED | | | CONDUCTORS. PLEASE DETAIL CORRECT SIZED CONDUCTORS OR | | | DETAIL HOW THESE CONDUCTORS COMPLY WITH NEC 310.15 | | | (B)(7)(2). PLEASE NOTE IN ORDER FOR FEEDER OR SERVICE | | | CONDUCTORS TO BE REDUCED IN AMPACITY TO 83%, THEY MUST | | | SERVE THE ENTIRE LOAD ASSOCIATED WITH THE STRUCTURE | | | 4) PLEASE PROVIDE PANEL SCHEDULES FOR ALL LOAD CENTERS. | | | NEC 215.5 AND FBC 107.2 | | | 5) PLEASE DETAIL GROUNDING ELECTRODE SYSTEM FOR LOAD | | | CENTER PH OR DETAIL HOW THIS PANEL COMPLIES WITH NEC | | | 250.32 | | | 6) PLEASE DETAIL NOTES STATING GENERATOR, POOL, AND LOW | | | VOLTAGE WIRING REQUIRES A SEPARATE PERMIT | | | 7) PLEASE DETAIL THE REQUIRED RECEPTACLE AT CONDENSING | | | UNITS AS REQUIRED BY NEC 210.63 | | | 8) PLEASE DETAIL ELEVATOR LOAD IN LOAD CALCULATIONS. | | | NEC 215.5 | | | 9) PLEASE PROVIDE ELEVATOR SPECIFICATIONS. FBC 107.2 | | | 10) PLEASE DETAIL SMOKE/CARBON ALARMS AS REQUIRED | | | R315.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2022-10-14 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-14 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-14 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2022-10-12 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-12 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-12 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2022-10-12 13:19:51 | 3RD GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2415.11 - THE PORTION OF GAS LINE TO THE | | | TANKLESS WATER HEATER IS STILL SHOWN AS GALVANIZED AND | | | IS NOT APPROVED FOR UNDERGROUND, EVEN WHEN ENCASED IN A | | | SLEEVE IT IS STILL NOT ALLOWED UNDERGROUND. IT WOULD | | | ONLY BE ALLOWED UNDERGROUND IF IF WAS PROTECTED PER | | | G2415.11.2. TYPICALLY IT WOULD TRANSITION TO CSST | | | OUTSIDE AND USE AN APPROVED UNDERGROUND TYPE OF CSST. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-07 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-07 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2022-10-07 10:45:43 | 3RD GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | THE CHANGES MADE HAVE CREATED NEW COMMENTS. | | | | | | 1. 2020 FRC G2415.11.1 - IT APPEARS THAT THE PORTION OF | | | PIPING GOING TO TWH1 IS GALVANIZED. GALVANIZED PIPE IS | | | NOT ALLOWED UNDER GROUND. PE IS NOT ALLOWED WITHIN THE | | | BUILDING EITHER (G2415.17.1). PLEASE RECONFIGURE THE | | | METHOD AND PIPING MATERIAL FOR TWH1. | | | | | | 2. 2020 FRC G2415.14/G2415.14.1 - PIPING BENEATH | | | BUILDINGS IS PROHIBITED UNLESS IT IS ENCASED IN CONDUIT | | | IN ACCORDANCE WITH THIS SECTION. PLEASE DETAIL THE | | | SLEEVE TO SHOW COMPLIANCE WITH G2415.14.1 SINCE ONE END | | | TERMINATES OUTDOORS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-08-30 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-11 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-08-11 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2022-08-11 07:44:37 | 1ST GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2415.11.2 - THE UNDERGROUND GAS PIPING | | | CANNOT BE SCH 40 METALLIC PIPE. PLEASE DETAIL AN | | | APPROVED GAS PIPING FOR ALL UNDERGROUND SECTIONS. | | | | | | 2. 2020 FRC G2415.17.1 - PLASTIC PIPE (P.E) IS NOT | | | ALLOWED WITHIN OR UNDER ANY BUILDING. YOUR ROUTING | | | APPEARS TO CONFLICT WITH THAT CODE. PLEASE CLARIFY THE | | | ROUTING. | | | | | | 3. ACCORDING TO THE INDICATED INLET PRESSURE AND | | | PRESSURE DROP, YOU WOULD BE USING TABLE 402.4(2). WITH | | | A LONGEST RUN OF 260' AND A TOTAL LOAD OF 958,000 BTU, | | | YOU APPEAR TO BE UNDERSIZED. ACCORDING TO THE LONGEST | | | RUN METHOD, YOU WOULD NEED 2 1/2" ON THE 1ST PIECE OF | | | PIPING. PLEASE CLARIFY THE GAS PRESSURE, AND RESUBMIT | | | THE SIZING. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-05-04 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-05-04 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-10-17 |
Time |
07:27 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-10-14 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-10-12 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-12 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-12 |
Time |
06:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-07 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-05 |
Time |
06:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-09-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-09-15 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-08-30 |
Time |
07:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-08-29 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-08-09 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-07-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-12 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-04-27 |
Time |
07:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-10-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-10-24 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-10-14 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2022-10-24 16:06:03 | RECEIPT MU-2022-047983 - $22.46 PAID | | 2022-10-14 09:17:24 | 10/14/22 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-07-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-07 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-07 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2022-07-07 10:47:47 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-02 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-02 |
Time |
08:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-08-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-15 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-15 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2022-08-15 16:13:57 | THE FOLLOWING COMMENTS ARE FROM THE 1ST REVIEW CYCLE | | | AND STILL NEED TO BE ADDRESSED: | | | | | | 1) THE DOCUMENTS IN THE SUPPORTING DOCUMENTS FOLDER | | | LABELED ENERGY CALCULATIONS ARE NOT ENERGY | | | CALCULATIONS, THEY ARE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. RELABEL THIS DOCUMENT AND PROVIDE THE | | | ENERGY CALCULATIONS. FEC 101.5.1.1.2 THE ENERGY | | | CALCULATIONS STILL HAVE NOT BEEN SUBMITTED. | | | | | | 2) IT APPEARS THAT AHU-4 IS SUPPLY AIR TO THE GARAGE | | | AND THE LIVING SPACE. THIS CANNOT HAPPEN SO PLEASE | | | CORRECT THE DESIGN. FRC M1601.6 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-05-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-11 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-11 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2022-05-11 10:34:40 | 1ST REVIEW FMC | | | PERMIT: 22040542 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. I SPOKE TO THE MECHANICAL | | | ENGINEER, HE WAS DRIVING AND COULDN?T TALK AND SAID HE | | | WOULD CALL BACK IN 10 MINUTES. I DID NOT HEAR BACK. MY | | | COMMENTS ARE LISTED BELOW: | | | | | | 1) THE DOCUMENTS IN THE SUPPORTING DOCUMENTS FOLDER | | | LABELED ENERGY CALCULATIONS ARE NOT ENERGY | | | CALCULATIONS, THEY ARE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. RELABEL THIS DOCUMENT AND PROVIDE THE | | | ENERGY CALCULATIONS. FEC 101.5.1.1.2 | | | | | | 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THE | | | LOGGIA INDICATES A TOTAL CONDITIONED AREA OF 566 SQ. | | | FT., SHEET A-003 INDICATES A TOTAL CONDITIONED SQ. FT. | | | OF 628. PLEASE BE CONSISTENT. FBC 107.2.1 | | | | | | 3) THE MECHANICAL PLANS ARE NOT CLEAR AS TO THE | | | LOCATION OF AHU-1 AND AHU-4. THEY BOTH ARE SHOWN ON THE | | | FIRST AND SECOND FLOOR DRAWINGS. IS AHU-1 HUNG BELOW | | | THE CEILING IN THE GARAGE? IS AHU-4 IN THE 2ND STORY | | | ATTIC AREA THE SYSTEM BEING DUCTED TO THE GALLERY, | | | BEDROOM AND THE FIRST FLOOR GARAGE? FBC 107.2.1 | | | | | | 4) AHU-1 THE RETURN IS BEING TAKEN FROM THE MASTER | | | CLOSET. REMOVE FROM THE CLOSET AS IT CANNOT BE LOCATED | | | IN A CLOSET. FRC M1602.2 | | | | | | 5) SHEET M-101: AHU-5: THERE IS A 4X12 SUPPLY GRILLE IN | | | THE BATHROOM BUT NO DUCT SHOWN FOR THE SUPPLY. SHOW THE | | | DUCTWORK FOR THIS GRILLE. FBC 107.2.1 | | | | | | 6) SHEET M-102: AHU-6: REMOVE THE RETURN AIR GRILLE | | | FROM THE GUEST ROOM #2 WIC. FRC M1602.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
P |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-07 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-07 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
P |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-07 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-07 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
P |
Date |
2022-07-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-07 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-07 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2022-07-07 10:47:14 | AE 7 | | | PROPOSED LOWEST FLOOR = 9.33 NAVD | | | PROPOSED ATTACHED GARAGE = 9.00 NAVD |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2022-10-14 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-14 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-14 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2022-10-12 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-12 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-07 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2022-08-30 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-30 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-30 16:37:54 | 3RD PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. DONE | | | | | | 2. DONE | | | | | | 3. DONE | | | | | | 4. CHANGES DO NOT COMPLY WITH THE CODE. THE BAR SINK | | | MUST DISCHARGE DOWNSTREAM OF THE WET VENT SYSTEM. -- | | | 2020 FRC P3108.1 - THE BAR SINK IS NOT ALLOWED TO WET | | | VENT THE WATER CLOSET. ONLY BATHROOM GROUP FIXTURES ARE | | | ALLOWED TO BE USED AS WET VENTING FIXTURES FOR OTHER | | | BATHROOM GROUP FIXTURES. THE BAR SINK MUST DISCHARGE | | | DOWNSTREAM OF THE WET VENTED SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-08-11 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-11 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-08-11 |
Time |
07:29 |
Sent To |
|
|
| Notes |
| 2022-08-11 07:31:40 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. DONE | | | | | | 2. 2020 FRC P3108.1 - THE SHOWER IN THE MASTER BATH - | | | TWO TRAPS ARE NOT ALLOWED ON THE HIGH SIDE OF THE VENT | | | CONNECTION. PLEASE RECONFIGURE SO THAT ONLY ONE TRAP IS | | | UPSTREAM OF THE VENT CONNECTION. | | | | | | 3. DONE | | | | | | 4. NOT ADDRESSED -- 2020 FRC P3108.1 - THE BAR SINK IS | | | NOT ALLOWED TO WET VENT THE WATER CLOSET. ONLY BATHROOM | | | GROUP FIXTURES ARE ALLOWED TO BE USED AS WET VENTING | | | FIXTURES FOR OTHER BATHROOM GROUP FIXTURES. THE BAR | | | SINK MUST DISCHARGE DOWNSTREAM OF THE WET VENTED | | | SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-04-28 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-04-28 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-04-28 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2022-04-28 15:42:35 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.2.1 - YOU'VE DETAILED A GAS | | | WATER HEATER BUT I DO NOT SEE A GAS DIAGRAM. EITHER | | | SUPPLY A GAS DIAGRAM AND A GAS SUB PERMIT FOR THIS | | | MASTER PERMIT OR HAVE A SEPERATE GAS PERMIT IN PLACE TO | | | SATISFY THIS COMMENT. | | | | | | 2. 2020 FRC P3108.1 - THE MASTER BATH SHOWER SHOWS A | | | VENT ON P-100 AND NOT ON P-200. PLEASE MAKE THEM MATCH. | | | ALSO, BOTH TRAPS ARE NOT ALLOWED ON THE HIGH SIDE OF | | | THE VENT CONNECTION. PLEASE RECONFIGURE SO THAT ONLY | | | ONE TRAP IS UPSTREAM OF THE VENT CONNECTION. | | | | | | 3. 2020 FRC P3108.1 - THE LAVATORIES IN THE BATHROOM | | | NEAR THE CLOTHES WASHER HAS TWO TRAPS UPSTREAM OF THE | | | VENT CONNECTION. ONLY ONE TRAP IS ALLOWED UPSTREAM OF | | | THE VENT CONNECTION. | | | | | | 4. 2020 FRC P3108.1 - THE BAR SINK IS NOT ALLOWED TO | | | WET VENT THE WATER CLOSET. ONLY BATHROOM GROUP FIXTURES | | | ARE ALLOWED TO BE USED AS WET VENTING FIXTURES FOR | | | OTHER BATHROOM GROUP FIXTURES. THE BAR SINK MUST | | | DISCHARGE DOWNSTREAM OF THE WET VENTED SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-08-29 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-08-29 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-08-18 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-18 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-07-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-07 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-07 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2022-07-07 10:48:27 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
6 |
Status |
P |
Date |
2022-10-14 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-14 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2022-10-12 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-12 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-07 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-07 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2022-10-07 10:46:24 | PLUMBING PAGES OKAY | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-07 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-07 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2022-09-07 15:44:08 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) ELEVATION CERTIFICATE DOES NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-08-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-15 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-15 |
Time |
16:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-05-24 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-05-24 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-24 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2022-05-11 10:35:35 | DIGITAL SIGNATURES FOR MECHANICAL DOCUMENTS APPROVED ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-09-01 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-09-01 |
Time |
15:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-08-25 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-08-25 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-08-25 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2022-08-25 09:09:26 | REQUIRES SEPEARATE LANDSCAPE PERMIT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-05-04 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-05-04 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|