Plan Review Details - Permit 22040495
Plan Review Stops For Permit 22040495
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-06-28 Cont ID  
Sent By jwitmer Date 2022-06-28 Time 10:24 Rev Time 0.00
Received By jwitmer Date 2022-06-28 Time 10:19 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By jwitmer Date 2022-05-09 Time 11:19 Rev Time  
Received By jwitmer Date 2022-05-09 Time   Sent To  
Notes
2022-05-09 11:19:04TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-01-10 Cont ID  
Sent By jwitmer Date 2023-01-10 Time 13:39 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-12-27 Cont ID  
Sent By jwitmer Date 2022-12-27 Time 07:52 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-12-27 07:52:132020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22040495
 ADD: 2480 PRESIDENTIAL WAY # 303
 CONT: J & C CONSTRUCTION
 TEL: 954-880-4368
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUES. DEC. 27TH/2022
 ACTION: DENIED
 PLEASE, PLEASE CALL ME SO WE CAN DISCUSS THE PERMIT
 ISSUES!!!!!!!!!!!!!!
  
 1-2) COMPLIED.
  
 3) 4TH REQUEST. NARRATIVE STATES IF YOU NEED ANYTHING
 PLEASE GIVE US A CALL. NO CONTRACTOR SIGNED ON, THE
 NARRATIVE DOES NOT PROVIDE A TEL. CONTACT NUMBER.
 PROJECT DOCS PROVIDES ONLY A CONTACT E-MAIL OF:
 [email protected]. IN THIS REVIEW THE NARRATIVE
 STATES (1) UNDERLAYMENT USED TEST REPORT ON THE FILE
 NAME: ECLIPSE II-FLYER GREEN GUARD PDF. NOA WHISPER-MAT
 CS PDF.
  
 SUBMITTED 12/21/22 ECLIPSE-II-FLYER-GREEN-GUARD, THIS
 IS A SALES BROCHURE NOT A TEST REPORT, THE LISTED 3
 TEST REPORTS ARE LISTED BELOW IN SECTIONS 3A, 3B & 3C.
 ECLIPSE II-FLYER GREEN GUARD IS AN UNDERLAYMENT TO BE
 USED WITH FLOATING LAMINATES, ENGINEERED WOOD AND OR
 SOLID RIGID CORE VINYL. 2 PAGES. THE CITY OF WPB DOES
 NOT HAVE ANY TEST REPORTS (3) FOR THIS PRODUCT. FLOOR
 PLAN THIS ROUND SHOWS THIS PRODUCT TO BE INSTALLED IN
 THE DINING ROOM & LIVING ROOM. SUGGEST A NEW PRODUCT,
 IF THIS PRODUCT IS ALREADY INSTALLED PLEASE INDICATE AS
 SUCH AND WHAT TYPE OF FINISH FLOORING WAS REMOVED.
  
 SUBMITTED 12/21/22 THE SAME SUBMITTAL DAY. WHISPER MAT
 CS WHICH IS TO BE USED WITH EITHER MARBLE AND OR TILE,
 AGAIN SALES BROCHURE. THE BUILDING FLOOR PLAN NOW
 DESIGNATES (2) TYPES OF FLOOR FINISHES IN THE ENTRY &
 KITCHEN TILE AND THE UNDERLAYMENT WHISPER-MAT CS WHICH
 WE DO HAVE HE 3 REQUIRED TEST REPORTS WHICH WE HAVE
 UPLOADED.
  
 3RD REQUEST. SUBMITTED SALES BROCHURE PRIVACY ULTIMATE
 TILE / STONE UNDERLAYMENT, THIS IS NOT THE 3 REQUIRED
 TEST REPORTS. THE BUILDING FLOOR PLAN DATED 11/29/2022
 STATES INSTALL SOUNDPROOFING ECLIPSE II SOUNDPROOFING.
 IT IS ASSUMED FOR TILE OR MARBLE FLOORING, THIS REVIEW
 NONE OF THE 3 TEST REPORTS WERE SUBMITTED.
  
 2ND REQUEST. THE DEMO FLOOR PLAN INDICATES THE REMOVAL
 OF FLOOR TILE NOTE 2 BUT DOES NOT INDICATE THE NEW
 FLOOR FINISH MATERIAL NOR SOUND UNDERLAYMENT. FLOOR
 INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) 4TH REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) 4TH REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) 4TH REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-12-13 Cont ID  
Sent By jwitmer Date 2022-12-13 Time 09:59 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-12-13 09:59:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22040495
 ADD: 2480 PRESIDENTIAL WAY # 303
 CONT: J & C CONSTRUCTION
 TEL: 954-880-4368
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. DEC. 13TH/ 2022
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) 3RD REQUEST. SUBMITTED SALES BROCHURE PRIVACY
 ULTIMATE TILE / STONE UNDERLAYMENT, THIS IS NOT THE 3
 REQUIRED TEST REPORTS. THE BUILDING FLOOR PLAN DATED
 11/29/2022 STATES INSTALL SOUNDPROOFING ECLIPSE II
 SOUNDPROOFING. IT IS ASSUMED FOR FILE OR MARBLE
 FLOORING, THIS REVIEW NONE OF THE 3 TEST REPORTS WERE
 SUBMITTED.
 2ND REQUEST. THE DEMO FLOOR PLAN INDICATES THE REMOVAL
 OF FLOOR TILE NOTE 2 BUT DOES NOT INDICATE THE NEW
 FLOOR FINISH MATERIAL NOR SOUND UNDERLAYMENT. FLOOR
 INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) 3RD REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) 3RD REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) 3RD REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-28 Cont ID  
Sent By jwitmer Date 2022-06-28 Time 10:31 Rev Time 0.00
Received By jwitmer Date 2022-06-28 Time 10:19 Sent To  
Notes
2022-06-28 10:31:28WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22040495
 ADD: 2480 PRESIDENTIAL WAY # 303
 CONT: J & C CONSTRUCTION
 TEL: 954-880-4368
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 28TH/ 2022
 ACTION: DENIED
  
 REPEAT COMMENTS NOTHING HAS GHANGED.
 ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
 1) THE DEMOLITION SHEET SHOWS THE REMOVAL OF FLOOR TILE
 IN THE LIVING ROOM, DINING ROOM, KITCHEN AND LAUNDRY
 ROOM, AND NEW FLOOR TILE PLUS REMOVAL OF CABINETS IN
 THE KITCHEN AND LAUNDRY WITH NEW CABINETRY.
 THE DECLARED DOLLAR AMOUNT ON THE PERMIT APPLICATION IS
 $15,000.00 DOLLARS. THAT AMOUNT IS EXTREMELY LOW FOR
 THE LISTED AMOUNT OF WORK DECLARED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDING OR ALTERATION THE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF THE ALTERATION SHALL
 BE THE TOTAL REPLACEMENT VALUE TO INCLUDE DEMOLITION,
 DISPOSAL OF DEBRIS, FLOOR FLASH PATCH, UNDERLAYMENT
 COST AND LABOR, THE FLOOR FINISH COST OF MATERIALS AND
 LABOR PLUS, CABINETRY DEMO & INSTALL, COUNTER TOPS,
 REPAIR OF DROPPED CEILING WHERE WALLS WERE REMOVED,
 OVERHEAD AND PROFIT. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS PUBLISHED BY THE
 INTERNATIONAL CODE CONGRESS.
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) WORK THAT IS $25,000 DOLLARS OR MORE NEEDS TO BE
 COMPLETED BY A DESIGN PROFESSIONAL.
 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1) (C)
 ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER
 BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE
 SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE
 REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45.
 WORK THAT IS LESS THAN $25,000.00 DOLLARS NEEDS TO MEET
 THIS REQUIREMENT. CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS AND OR SCHEDULES WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS AND OR
 SCHEDULES DRAWN. IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS AND OR SCHEDULES DRAWN.
  
 3) THE DEMO FLOOR PLAN INDICATES THE REMOVAL OF FLOOR
 TILE NOTE 2 BUT DOES NOT INDICATE THE NEW FLOOR FINISH
 MATERIAL NOR SOUND UNDERLAYMENT. FLOOR INSULATION/
 UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD FLOORING
 ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED
 FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET
 THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS
 FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED
 CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By jwitmer Date 2022-05-09 Time 11:18 Rev Time  
Received By jwitmer Date 2022-05-09 Time   Sent To  
Notes
2022-05-09 11:18:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22040495
 ADD: 2480 PRESIDENTIAL WAY # 303
 CONT: J & C CONSTRUCTION
 TEL: 954-880-4368
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) THE DEMOLITION SHEET SHOWS THE REMOVAL OF FLOOR TILE
 IN THE LIVING ROOM, DINING ROOM, KITCHEN AND LAUNDRY
 ROOM, AND NEW FLOOR TILE PLUS REMOVAL OF CABINETS IN
 THE KITCHEN AND LAUNDRY WITH NEW CABINETRY.
 THE DECLARED DOLLAR AMOUNT ON THE PERMIT APPLICATION IS
 $15,000.00 DOLLARS. THAT AMOUNT IS EXTREMELY LOW FOR
 THE LISTED AMOUNT OF WORK DECLARED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDING OR ALTERATION THE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF THE ALTERATION SHALL
 BE THE TOTAL REPLACEMENT VALUE TO INCLUDE DEMOLITION,
 DISPOSAL OF DEBRIS, FLOOR FLASH PATCH, UNDERLAYMENT
 COST AND LABOR, THE FLOOR FINISH COST OF MATERIALS AND
 LABOR PLUS, CABINETRY DEMO & INSTALL, COUNTER TOPS,
 REPAIR OF DROPPED CEILING WHERE WALLS WERE REMOVED,
 OVERHEAD AND PROFIT. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS PUBLISHED BY THE
 INTERNATIONAL CODE CONGRESS.
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) WORK THAT IS $25,000 DOLLARS OR MORE NEEDS TO BE
 COMPLETED BY A DESIGN PROFESSIONAL.
 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1) (C)
 ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER
 BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE
 SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE
 REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45.
 WORK THAT IS LESS THAN $25,000.00 DOLLARS NEEDS TO MEET
 THIS REQUIREMENT. CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS AND OR SCHEDULES WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS AND OR
 SCHEDULES DRAWN. IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS AND OR SCHEDULES DRAWN.
  
 3) THE DEMO FLOOR PLAN INDICATES THE REMOVAL OF FLOOR
 TILE NOTE 2 BUT DOES NOT INDICATE THE NEW FLOOR FINISH
 MATERIAL NOR SOUND UNDERLAYMENT. FLOOR INSULATION/
 UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD FLOORING
 ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED
 FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET
 THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS
 FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED
 CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-01-06 Cont ID  
Sent By jleahy Date 2023-01-06 Time 15:31 Rev Time 0.00
Received By jleahy Date 2023-01-06 Time 15:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-20 Cont ID  
Sent By jleahy Date 2022-12-20 Time 15:50 Rev Time 0.00
Received By jleahy Date 2022-12-20 Time 13:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-06 Cont ID  
Sent By jleahy Date 2022-05-06 Time 14:51 Rev Time 0.00
Received By jleahy Date 2022-05-06 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2023-01-10 Cont ID  
Sent By cwalker Date 2023-01-10 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-01-10 09:38:17FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ANY IMPAIRMENTS TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A FIRE
 WATCH.
  
 (3) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE,
 INCLUDING PAINT, DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION.
  
 (4) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-12-22 Cont ID  
Sent By cwalker Date 2022-12-22 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-12-22 09:50:40FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (3) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE,
 INCLUDING PAINT, DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION.
  
 (4) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2022-12-01 Cont ID  
Sent By cwalker Date 2022-12-01 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-12-01 11:49:21FIRE REVIEW COMMENTS:
  
 THE PLAN SUBMITTAL SHEET D-1 UNDER SCOPE OF WORK (1)
 REMOVE EXISTING INTERIOR PARTITION, AND CLEARLY WALLS
 ARE PROPOSED TO BE DEMOLISHED.
  
 WITH THE REMOVAL OF WALLS, FIRE SPRINKLER HEAD COVERAGE
 CAN BE IMPACTED.
  
 AN EVALUATION SHALL BE MADE BY A QUALIFIED FIRE
 SPRINKLER CONTRACTOR, AND IF ANY WORK OR MODIFICATIONS
 TO THE FIRE SPRINKLER HEAD LOCATIONS ARE NECESSARY, THE
 WORK MUST BE PERFORMED UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
 PROVIDE A NOTE OF EITHER RECOGNITION OF THE PARTITION
 WALL REMOVAL, OR REVISE THE PLANS SUBMITTED.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-06-09 Cont ID  
Sent By cwalker Date 2022-06-09 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-06-09 10:38:18FIRE COMMENTS:
 THE PLAN SUBMITTAL CLEARLY INDICATES THE REMOVAL OF
 INTERIOR WALLS. WITH THE REMOVAL OF WALLS, FIRE
 SPRINKLER HEAD COVERAGE CAN BE IMPACTED. AN EVALUATION
 OF THE FIRE SPRINKLER COVERAGE SHALL BE MADE BY A
 QUALIFIED FIRE SPRINKLER CONTRACTOR, AND IF ANY WORK OR
 MODIFICATION TO THE FIRE SPRINKLER SYSTEM IS NECESSARY,
 IT MUST BE CONDUCTED UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
 THE TYPE FINISHED FLOORING SHALL BE SUBMITTED AS PART
 OF THE OFFICIAL RECORD (NOT VIA E-MAIL) TO ENSURE
 COMPLIANCE WITH NFPA 101, 10.2.7 FOR FIRE PERFORMANCE.
  
 C. WALKER
 561-804-4762
  
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-04-15 Cont ID  
Sent By cwalker Date 2022-04-15 Time   Rev Time  
Received By cwalker Date 2022-04-15 Time   Sent To  
Notes
2022-04-15 11:08:13FIRE COMMENTS:
 PROVIDE DOCUMENTATION ON THE TYPE OF NEW TILE FLOORING
 TO BE INSTALLED, SPECIFICALLY IF IT IS A COMBUSTIBLE
 MATERIAL SUCH AS VINYL PLANK, SUPPLY THE INFORMATION ON
 THE FIRE PERFORMANCE OF THE MATERIAL INCLUDING THE
 CRITICAL RADIANT FLUX. NFPA 101 10.2.7
 WITH THE REMOVAL OF WALLS, AN EVALUATION SHALL BE
 PERFORMED TO ENSURE ALL LIFE SAFETY SYSTEMS (FIRE
 SPRINKLER AND/OR FIRE ALARM) PROVIDE ADEQUATE COVERAGE.
 ANY AND ALL WORK ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS BY QUALIFIED
 CONTRACTORS.
 ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR
 FIRE ALARM) SHALL BE MAINTAINED OPERATIONAL DURING
 DEMOLITION AND CONSTRUCTION AND ANY IMPAIRMENT TO THESE
 SYSTEMS THAT EXCEEDS 4 CONTINUOUS HOURS IN DURATION
 WILL REQUIRE THE IMPLEMENTATION OF A FIRE WATCH.
 FIRE REVIEWER:
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2023-01-10 Time   Rev Time 0.00
Received By lmarchan Date 2023-01-09 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-06 Cont ID  
Sent By jleahy Date 2023-01-06 Time 15:31 Rev Time 0.00
Received By jleahy Date 2022-12-22 Time 07:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-20 Cont ID  
Sent By jleahy Date 2022-12-20 Time 15:51 Rev Time 0.00
Received By jleahy Date 2022-11-29 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-28 Cont ID  
Sent By jwitmer Date 2022-06-28 Time 10:32 Rev Time 0.00
Received By jwitmer Date 2022-06-08 Time 13:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-09 Cont ID  
Sent By jwitmer Date 2022-05-09 Time 11:19 Rev Time 0.00
Received By jwitmer Date 2022-04-14 Time 06:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-12-05 Cont ID  
Sent By rwbrown Date 2022-12-05 Time 05:58 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-04-26 Cont ID  
Sent By rwbrown Date 2022-04-26 Time 15:52 Rev Time 0.00
Received By rwbrown Date 2022-04-26 Time 15:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2023-01-10 Cont ID  
Sent By jwitmer Date 2023-01-10 Time 13:39 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-12-20 Cont ID  
Sent By jleahy Date 2022-12-20 Time 15:51 Rev Time 0.00
Received By jleahy Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-05-09 Cont ID  
Sent By jwitmer Date 2022-05-09 Time 11:19 Rev Time  
Received By jwitmer Date 2022-05-09 Time   Sent To  
Notes
***NONE***