Plan Review Details - Permit 22040495
| Plan Review Stops For Permit 22040495 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2022-06-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-06-28 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2022-06-28 |
Time |
10:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2022-05-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-05-09 |
Time |
11:19 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2022-05-09 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-05-09 11:19:04 | TO THE BUILDING CONTRACTOR: | | | PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION | | | THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE. | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT | | | LINE. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-01-10 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2022-12-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-12-27 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-12-27 07:52:13 | 2020 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 22040495 | | | ADD: 2480 PRESIDENTIAL WAY # 303 | | | CONT: J & C CONSTRUCTION | | | TEL: 954-880-4368 | | | E-MAIL: [email protected] | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 4TH REVIEW | | | DATE: TUES. DEC. 27TH/2022 | | | ACTION: DENIED | | | PLEASE, PLEASE CALL ME SO WE CAN DISCUSS THE PERMIT | | | ISSUES!!!!!!!!!!!!!! | | | | | | 1-2) COMPLIED. | | | | | | 3) 4TH REQUEST. NARRATIVE STATES IF YOU NEED ANYTHING | | | PLEASE GIVE US A CALL. NO CONTRACTOR SIGNED ON, THE | | | NARRATIVE DOES NOT PROVIDE A TEL. CONTACT NUMBER. | | | PROJECT DOCS PROVIDES ONLY A CONTACT E-MAIL OF: | | | [email protected]. IN THIS REVIEW THE NARRATIVE | | | STATES (1) UNDERLAYMENT USED TEST REPORT ON THE FILE | | | NAME: ECLIPSE II-FLYER GREEN GUARD PDF. NOA WHISPER-MAT | | | CS PDF. | | | | | | SUBMITTED 12/21/22 ECLIPSE-II-FLYER-GREEN-GUARD, THIS | | | IS A SALES BROCHURE NOT A TEST REPORT, THE LISTED 3 | | | TEST REPORTS ARE LISTED BELOW IN SECTIONS 3A, 3B & 3C. | | | ECLIPSE II-FLYER GREEN GUARD IS AN UNDERLAYMENT TO BE | | | USED WITH FLOATING LAMINATES, ENGINEERED WOOD AND OR | | | SOLID RIGID CORE VINYL. 2 PAGES. THE CITY OF WPB DOES | | | NOT HAVE ANY TEST REPORTS (3) FOR THIS PRODUCT. FLOOR | | | PLAN THIS ROUND SHOWS THIS PRODUCT TO BE INSTALLED IN | | | THE DINING ROOM & LIVING ROOM. SUGGEST A NEW PRODUCT, | | | IF THIS PRODUCT IS ALREADY INSTALLED PLEASE INDICATE AS | | | SUCH AND WHAT TYPE OF FINISH FLOORING WAS REMOVED. | | | | | | SUBMITTED 12/21/22 THE SAME SUBMITTAL DAY. WHISPER MAT | | | CS WHICH IS TO BE USED WITH EITHER MARBLE AND OR TILE, | | | AGAIN SALES BROCHURE. THE BUILDING FLOOR PLAN NOW | | | DESIGNATES (2) TYPES OF FLOOR FINISHES IN THE ENTRY & | | | KITCHEN TILE AND THE UNDERLAYMENT WHISPER-MAT CS WHICH | | | WE DO HAVE HE 3 REQUIRED TEST REPORTS WHICH WE HAVE | | | UPLOADED. | | | | | | 3RD REQUEST. SUBMITTED SALES BROCHURE PRIVACY ULTIMATE | | | TILE / STONE UNDERLAYMENT, THIS IS NOT THE 3 REQUIRED | | | TEST REPORTS. THE BUILDING FLOOR PLAN DATED 11/29/2022 | | | STATES INSTALL SOUNDPROOFING ECLIPSE II SOUNDPROOFING. | | | IT IS ASSUMED FOR TILE OR MARBLE FLOORING, THIS REVIEW | | | NONE OF THE 3 TEST REPORTS WERE SUBMITTED. | | | | | | 2ND REQUEST. THE DEMO FLOOR PLAN INDICATES THE REMOVAL | | | OF FLOOR TILE NOTE 2 BUT DOES NOT INDICATE THE NEW | | | FLOOR FINISH MATERIAL NOR SOUND UNDERLAYMENT. FLOOR | | | INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, | | | MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD | | | FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT | | | TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND | | | MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE | | | STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO | | | DROPPED CEILING: | | | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR | | | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: | | | | | | 3A) 4TH REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE | | | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS | | | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. | | | | | | 3B) 4TH REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 3C) 4TH REQUEST. FLAME SPREAD- FBC-B 2020 603.1. | | | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED | | | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE | | | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT | | | MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ SEMI-RETIRED. | | | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | | BACK INTO THE OFFICE CALL | | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | | THANK YOU. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-12-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-12-13 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-12-13 09:59:12 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2020 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 22040495 | | | ADD: 2480 PRESIDENTIAL WAY # 303 | | | CONT: J & C CONSTRUCTION | | | TEL: 954-880-4368 | | | E-MAIL: [email protected] | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: TUES. DEC. 13TH/ 2022 | | | ACTION: DENIED | | | | | | 1-2) COMPLIED. | | | | | | 3) 3RD REQUEST. SUBMITTED SALES BROCHURE PRIVACY | | | ULTIMATE TILE / STONE UNDERLAYMENT, THIS IS NOT THE 3 | | | REQUIRED TEST REPORTS. THE BUILDING FLOOR PLAN DATED | | | 11/29/2022 STATES INSTALL SOUNDPROOFING ECLIPSE II | | | SOUNDPROOFING. IT IS ASSUMED FOR FILE OR MARBLE | | | FLOORING, THIS REVIEW NONE OF THE 3 TEST REPORTS WERE | | | SUBMITTED. | | | 2ND REQUEST. THE DEMO FLOOR PLAN INDICATES THE REMOVAL | | | OF FLOOR TILE NOTE 2 BUT DOES NOT INDICATE THE NEW | | | FLOOR FINISH MATERIAL NOR SOUND UNDERLAYMENT. FLOOR | | | INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, | | | MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD | | | FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT | | | TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND | | | MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE | | | STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO | | | DROPPED CEILING: | | | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR | | | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: | | | | | | 3A) 3RD REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE | | | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS | | | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. | | | | | | 3B) 3RD REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 3C) 3RD REQUEST. FLAME SPREAD- FBC-B 2020 603.1. | | | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED | | | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE | | | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT | | | MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ SEMI-RETIRED. | | | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | | BACK INTO THE OFFICE CALL | | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | | THANK YOU. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-06-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-06-28 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2022-06-28 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2022-06-28 10:31:28 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2020 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 22040495 | | | ADD: 2480 PRESIDENTIAL WAY # 303 | | | CONT: J & C CONSTRUCTION | | | TEL: 954-880-4368 | | | E-MAIL: [email protected] | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: TUES. JUNE 28TH/ 2022 | | | ACTION: DENIED | | | | | | REPEAT COMMENTS NOTHING HAS GHANGED. | | | ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA | | | STATUTE 553.80(2)(B) | | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | | | | | | | 1) THE DEMOLITION SHEET SHOWS THE REMOVAL OF FLOOR TILE | | | IN THE LIVING ROOM, DINING ROOM, KITCHEN AND LAUNDRY | | | ROOM, AND NEW FLOOR TILE PLUS REMOVAL OF CABINETS IN | | | THE KITCHEN AND LAUNDRY WITH NEW CABINETRY. | | | THE DECLARED DOLLAR AMOUNT ON THE PERMIT APPLICATION IS | | | $15,000.00 DOLLARS. THAT AMOUNT IS EXTREMELY LOW FOR | | | THE LISTED AMOUNT OF WORK DECLARED. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDING OR ALTERATION THE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF THE ALTERATION SHALL | | | BE THE TOTAL REPLACEMENT VALUE TO INCLUDE DEMOLITION, | | | DISPOSAL OF DEBRIS, FLOOR FLASH PATCH, UNDERLAYMENT | | | COST AND LABOR, THE FLOOR FINISH COST OF MATERIALS AND | | | LABOR PLUS, CABINETRY DEMO & INSTALL, COUNTER TOPS, | | | REPAIR OF DROPPED CEILING WHERE WALLS WERE REMOVED, | | | OVERHEAD AND PROFIT. VALUATION REFERENCES MAY INCLUDE | | | THE LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST | | | ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.) WITH | | | REGIONAL ADJUSTMENTS FOR LOCATION AS PUBLISHED BY THE | | | INTERNATIONAL CODE CONGRESS. | | | 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, | | | PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE | | | WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD | | | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION | | | REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF | | | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | 2) WORK THAT IS $25,000 DOLLARS OR MORE NEEDS TO BE | | | COMPLETED BY A DESIGN PROFESSIONAL. | | | 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1) (C) | | | ANY OTHER TYPE OF BUILDING COSTING LESS THAN | | | $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER | | | BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE | | | SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE | | | REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45. | | | WORK THAT IS LESS THAN $25,000.00 DOLLARS NEEDS TO MEET | | | THIS REQUIREMENT. CERTIFICATION BY CONTRACTOR. | | | 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED / | | | DREW THE SET OF PLANS AND OR SCHEDULES WILL NEED TO | | | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE | | | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR | | | THE TRADE YOU ARE LICENSED IN AND PLANS AND OR | | | SCHEDULES DRAWN. IDENTIFY THEMSELVES AS THE AUTHOR OF | | | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND | | | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND | | | PLANS AND OR SCHEDULES DRAWN. | | | | | | 3) THE DEMO FLOOR PLAN INDICATES THE REMOVAL OF FLOOR | | | TILE NOTE 2 BUT DOES NOT INDICATE THE NEW FLOOR FINISH | | | MATERIAL NOR SOUND UNDERLAYMENT. FLOOR INSULATION/ | | | UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE, | | | VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD FLOORING | | | ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED | | | FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET | | | THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS | | | FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED | | | CEILING: | | | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR | | | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: | | | | | | 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. | | | | | | 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, | | | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR | | | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E | | | 90. | | | | | | 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ SEMI-RETIRED. | | | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | | BACK INTO THE OFFICE CALL | | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | | THANK YOU. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-05-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-05-09 |
Time |
11:18 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2022-05-09 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-05-09 11:18:12 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2020 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 22040495 | | | ADD: 2480 PRESIDENTIAL WAY # 303 | | | CONT: J & C CONSTRUCTION | | | TEL: 954-880-4368 | | | E-MAIL: [email protected] | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: | | | ACTION: DENIED | | | | | | 1) THE DEMOLITION SHEET SHOWS THE REMOVAL OF FLOOR TILE | | | IN THE LIVING ROOM, DINING ROOM, KITCHEN AND LAUNDRY | | | ROOM, AND NEW FLOOR TILE PLUS REMOVAL OF CABINETS IN | | | THE KITCHEN AND LAUNDRY WITH NEW CABINETRY. | | | THE DECLARED DOLLAR AMOUNT ON THE PERMIT APPLICATION IS | | | $15,000.00 DOLLARS. THAT AMOUNT IS EXTREMELY LOW FOR | | | THE LISTED AMOUNT OF WORK DECLARED. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDING OR ALTERATION THE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF THE ALTERATION SHALL | | | BE THE TOTAL REPLACEMENT VALUE TO INCLUDE DEMOLITION, | | | DISPOSAL OF DEBRIS, FLOOR FLASH PATCH, UNDERLAYMENT | | | COST AND LABOR, THE FLOOR FINISH COST OF MATERIALS AND | | | LABOR PLUS, CABINETRY DEMO & INSTALL, COUNTER TOPS, | | | REPAIR OF DROPPED CEILING WHERE WALLS WERE REMOVED, | | | OVERHEAD AND PROFIT. VALUATION REFERENCES MAY INCLUDE | | | THE LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST | | | ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.) WITH | | | REGIONAL ADJUSTMENTS FOR LOCATION AS PUBLISHED BY THE | | | INTERNATIONAL CODE CONGRESS. | | | 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, | | | PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE | | | WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD | | | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION | | | REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF | | | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | 2) WORK THAT IS $25,000 DOLLARS OR MORE NEEDS TO BE | | | COMPLETED BY A DESIGN PROFESSIONAL. | | | 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1) (C) | | | ANY OTHER TYPE OF BUILDING COSTING LESS THAN | | | $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER | | | BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE | | | SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE | | | REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45. | | | WORK THAT IS LESS THAN $25,000.00 DOLLARS NEEDS TO MEET | | | THIS REQUIREMENT. CERTIFICATION BY CONTRACTOR. | | | 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED / | | | DREW THE SET OF PLANS AND OR SCHEDULES WILL NEED TO | | | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE | | | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR | | | THE TRADE YOU ARE LICENSED IN AND PLANS AND OR | | | SCHEDULES DRAWN. IDENTIFY THEMSELVES AS THE AUTHOR OF | | | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND | | | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND | | | PLANS AND OR SCHEDULES DRAWN. | | | | | | 3) THE DEMO FLOOR PLAN INDICATES THE REMOVAL OF FLOOR | | | TILE NOTE 2 BUT DOES NOT INDICATE THE NEW FLOOR FINISH | | | MATERIAL NOR SOUND UNDERLAYMENT. FLOOR INSULATION/ | | | UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE, | | | VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD FLOORING | | | ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED | | | FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET | | | THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS | | | FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED | | | CEILING: | | | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR | | | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: | | | | | | 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. | | | | | | 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, | | | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR | | | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E | | | 90. | | | | | | 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ SEMI-RETIRED. | | | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | | BACK INTO THE OFFICE CALL | | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | | THANK YOU. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-01-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-06 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-01-06 |
Time |
15:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-12-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-12-20 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-12-20 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-05-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-05-06 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-05-06 |
Time |
14:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2023-01-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-01-10 09:38:17 | FIRE PROVISO COMMENTS: | | | | | | (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL | | | PHASES OF DEMOLITION AND CONSTRUCTION. | | | | | | (2) ANY IMPAIRMENTS TO ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | | IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A FIRE | | | WATCH. | | | | | | (3) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE, | | | INCLUDING PAINT, DURING ALL PHASES OF DEMOLITION AND | | | CONSTRUCTION. | | | | | | (4) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY | | | PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS | | | AND SHOP DRAWINGS. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2022-12-22 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-12-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-12-22 09:50:40 | FIRE PROVISO COMMENTS: | | | | | | (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL | | | PHASES OF DEMOLITION AND CONSTRUCTION. | | | | | | (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | | HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A | | | FIRE WATCH. | | | | | | (3) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE, | | | INCLUDING PAINT, DURING ALL PHASES OF DEMOLITION AND | | | CONSTRUCTION. | | | | | | (4) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY | | | PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS | | | AND SHOP DRAWINGS. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2022-12-01 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-12-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-12-01 11:49:21 | FIRE REVIEW COMMENTS: | | | | | | THE PLAN SUBMITTAL SHEET D-1 UNDER SCOPE OF WORK (1) | | | REMOVE EXISTING INTERIOR PARTITION, AND CLEARLY WALLS | | | ARE PROPOSED TO BE DEMOLISHED. | | | | | | WITH THE REMOVAL OF WALLS, FIRE SPRINKLER HEAD COVERAGE | | | CAN BE IMPACTED. | | | | | | AN EVALUATION SHALL BE MADE BY A QUALIFIED FIRE | | | SPRINKLER CONTRACTOR, AND IF ANY WORK OR MODIFICATIONS | | | TO THE FIRE SPRINKLER HEAD LOCATIONS ARE NECESSARY, THE | | | WORK MUST BE PERFORMED UNDER SEPARATE PERMITS AND SHOP | | | DRAWINGS. | | | | | | PROVIDE A NOTE OF EITHER RECOGNITION OF THE PARTITION | | | WALL REMOVAL, OR REVISE THE PLANS SUBMITTED. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2022-06-09 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-06-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-06-09 10:38:18 | FIRE COMMENTS: | | | THE PLAN SUBMITTAL CLEARLY INDICATES THE REMOVAL OF | | | INTERIOR WALLS. WITH THE REMOVAL OF WALLS, FIRE | | | SPRINKLER HEAD COVERAGE CAN BE IMPACTED. AN EVALUATION | | | OF THE FIRE SPRINKLER COVERAGE SHALL BE MADE BY A | | | QUALIFIED FIRE SPRINKLER CONTRACTOR, AND IF ANY WORK OR | | | MODIFICATION TO THE FIRE SPRINKLER SYSTEM IS NECESSARY, | | | IT MUST BE CONDUCTED UNDER SEPARATE PERMITS AND SHOP | | | DRAWINGS. | | | THE TYPE FINISHED FLOORING SHALL BE SUBMITTED AS PART | | | OF THE OFFICIAL RECORD (NOT VIA E-MAIL) TO ENSURE | | | COMPLIANCE WITH NFPA 101, 10.2.7 FOR FIRE PERFORMANCE. | | | | | | C. WALKER | | | 561-804-4762 | | | | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-04-15 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-04-15 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
2022-04-15 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-15 11:08:13 | FIRE COMMENTS: | | | PROVIDE DOCUMENTATION ON THE TYPE OF NEW TILE FLOORING | | | TO BE INSTALLED, SPECIFICALLY IF IT IS A COMBUSTIBLE | | | MATERIAL SUCH AS VINYL PLANK, SUPPLY THE INFORMATION ON | | | THE FIRE PERFORMANCE OF THE MATERIAL INCLUDING THE | | | CRITICAL RADIANT FLUX. NFPA 101 10.2.7 | | | WITH THE REMOVAL OF WALLS, AN EVALUATION SHALL BE | | | PERFORMED TO ENSURE ALL LIFE SAFETY SYSTEMS (FIRE | | | SPRINKLER AND/OR FIRE ALARM) PROVIDE ADEQUATE COVERAGE. | | | ANY AND ALL WORK ON ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED UNDER | | | SEPARATE PERMITS AND SHOP DRAWINGS BY QUALIFIED | | | CONTRACTORS. | | | ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR | | | FIRE ALARM) SHALL BE MAINTAINED OPERATIONAL DURING | | | DEMOLITION AND CONSTRUCTION AND ANY IMPAIRMENT TO THESE | | | SYSTEMS THAT EXCEEDS 4 CONTINUOUS HOURS IN DURATION | | | WILL REQUIRE THE IMPLEMENTATION OF A FIRE WATCH. | | | FIRE REVIEWER: | | | C. WALKER | | | 561-804-4762 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-01-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-09 |
Time |
16:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-01-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-06 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-12-22 |
Time |
07:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-12-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-12-20 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-11-29 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-06-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-06-28 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2022-06-08 |
Time |
13:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-05-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-05-09 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2022-04-14 |
Time |
06:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-12-05 |
Time |
05:58 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-04-26 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-04-26 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
N |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2023-01-10 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
N |
Date |
2022-12-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-12-20 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-05-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-05-09 |
Time |
11:19 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2022-05-09 |
Time |
|
Sent To |
|
|
| Notes |
|
|
|