| 2022-10-06 07:57:12 | 10/6/22 I TALKED WITH CUSTOMER YESTERDAY AND ALL ITEMS |
| | HAVE BEEN SATISFIED. MP |
| 2022-07-25 16:34:29 | ELECTRIC REVIEW FAILED |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW.PLEASE PROVIDE A BREAKDOWN OF ALL MATERIALS AND |
| | LABOR, OR, AT YOUR DISCRETION, PROVIDE A SIGNED |
| | CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB F.B.C. |
| | 109.3 |
| | 2. PLEASE PROVIDE SPECIFICATIONS FOR GENERATOR, |
| | GENERATOR SLAB, TRANSFER SWITCH AND LOAD SHED MODULES. |
| | FBS 107.2 |
| | 3.PLEASE DETAIL ALL LOADS TO BE SHED DURING GENERATOR |
| | USE.NEC 215.5 |
| | 4. PLEASE PROVIDE A SITE PLAN DETAILING ALL EQIPMENT |
| | LOCATIONS. FBC 107.2 |
| | 5. PROVIDE AN APPLICABLE SURVEY. FBC 107.2 |
| | 6. ENSURE ALL DOCUMENTS SUBMITTED CONTAIN APPROPRIATE |
| | SIGNATURE AND IDENTIFICATION OF DESIGNER OF RECORD. |
| | SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) |
| | & 471.025./FS481 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |