Plan Review Details - Permit 22040402
Plan Review Stops For Permit 22040402
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-12 Cont ID  
Sent By cthroop Date 2022-04-12 Time 13:04 Rev Time 0.00
Received By cthroop Date 2022-04-12 Time 13:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-08 Cont ID  
Sent By cthroop Date 2022-04-08 Time 12:28 Rev Time 0.00
Received By cthroop Date 2022-04-08 Time 12:23 Sent To  
Notes
2022-04-08 12:34:11BUILDING PLAN REVIEW TENTS
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CONFORMANCE PER SECTION 3103.1.1
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC
 HEALTH, SAFETY AND GENERAL WELFARE.
 A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR
 STRUCTURES WITH SPANS OF 30 FEET OR GREATER. APPROVED
 4-8-22 CT
 B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER
 NFPA 701 FOR EACH TENT. APPROVED 4-8-22 CT
 C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN
 REQUIRED.
  2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN
  A) STATE OCCUPANT LOAD.
  B) IDENTIFY MEANS OF EGRESS.
  C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO
 EXIT.
  D) PROVIDE FLOOR LAYOUT OF EVENT.
  D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE
 PLAN N/A MEYER AMPITHEATER
  E. LIGHT 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE
  F. VENTILATION 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1203
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2022-04-08 Cont ID  
Sent By pleduc Date 2022-04-08 Time   Rev Time 0.00
Received By pleduc Date 2022-04-08 Time 12:34 Sent To  
Notes
2022-04-08 12:40:27THE TENTS ARE EACH LESS THAN 900SQ FT, A LIFE SAFETY
 REVIEW IS NOT REQUIRED BY FIRE,
  
 PER FS 633.202 - FLORIDA FIRE PREVENTION CODE. (17) A
 TENT UP TO 900 SQUARE FEET IS EXEMPT FROM THE FLORIDA
 FIRE PREVENTION CODE, INCLUDING THE NATIONAL CODES
 INCORPORATED BY REFERENCE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-12 Cont ID  
Sent By cthroop Date 2022-04-12 Time 13:05 Rev Time 0.00
Received By cthroop Date 2022-04-12 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-04-08 Time   Rev Time 0.00
Received By amcgrego Date 2022-04-08 Time 10:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-08 Cont ID  
Sent By cthroop Date 2022-04-08 Time 12:23 Rev Time 0.00
Received By cthroop Date 2022-04-08 Time 12:23 Sent To  
Notes
***NONE***