Plan Review Details - Permit 22040359
Plan Review Stops For Permit 22040359
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-06-29 Cont ID  
Sent By jbrooks Date 2022-06-29 Time 10:10 Rev Time 0.00
Received By jbrooks Date 2022-06-29 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-06-17 Cont ID  
Sent By jbrooks Date 2022-06-17 Time 10:58 Rev Time 0.00
Received By jbrooks Date 2022-06-17 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-24 Cont ID  
Sent By jbrooks Date 2022-05-24 Time 13:11 Rev Time 0.00
Received By jbrooks Date 2022-05-24 Time 08:11 Sent To  
Notes
2022-05-24 13:12:12JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC B 107.2.1 SUBMITTED FORM 400 IS A PALM BEACH
 COUNTY BUILDING DEPARTMENT DOCUMENT AND IS NOT APPROVED
 FOR USE AS A SUBSTITUTE FOR SIGNED AND SEALED ENHANCED
 NAILING CALCULATIONS BY THE CITY OF WEST PALM BEACH
 BUILDING DEPARTMENT THE AUTHORITY OF JURISDICTION.
 GENERAL LIMITATION #7 IS SPECIFICALLY REFERRED TO IN
 THIS NOA. SUBMIT FASTENER DENSITY CALCULATIONS
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR
 REGISTERED ROOF CONSULTANT. SECOND REQUEST.
 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF
 SLOPE(S), MEAN ROOF HEIGHT(S). SECOND REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-28 Cont ID  
Sent By jbrooks Date 2022-04-28 Time 12:38 Rev Time 0.00
Received By jbrooks Date 2022-04-28 Time 07:56 Sent To  
Notes
2022-04-28 12:39:00JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. SUBMITTED MIAMI-DADE COUNTY NOA 17-1004.09 COVERS
 MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(8).
 SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED
 CALCULATIONS MAY BE REQUIRED. PLEASE NOTE THIS IS A
 CATEGORY C AREA.
 2. FBC B 107.2.1 SUBMITTED FORM 400 IS A PALM BEACH
 COUNTY BUILDING DEPARTMENT DOCUMENT AND IS NOT APPROVED
 FOR USE AS A SUBSTITUTE FOR SIGNED AND SEALED ENHANCED
 NAILING CALCULATIONS BY THE CITY OF WEST PALM BEACH
 BUILDING DEPARTMENT THE AUTHORITY OF JURISDICTION.
 GENERAL LIMITATION #7 IS SPECIFICALLY REFERRED TO IN
 THIS NOA. SUBMIT FASTENER DENSITY CALCULATIONS
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR
 REGISTERED ROOF CONSULTANT.
 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF
 SLOPE(S), MEAN ROOF HEIGHT(S). LOW SLOPE ROOFS MUST
 SHOW POSITIVE DRAINAGE.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-05-13 Cont ID  
Sent By amhamilt Date 2022-05-12 Time 09:34 Rev Time 0.00
Received By amhamilt Date 2022-05-12 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-06-29 Cont ID  
Sent By jbrooks Date 2022-06-29 Time 10:10 Rev Time 0.00
Received By jbrooks Date 2022-06-21 Time 06:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-17 Cont ID  
Sent By jbrooks Date 2022-06-17 Time 10:59 Rev Time 0.00
Received By jbrooks Date 2022-06-08 Time 13:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-24 Cont ID  
Sent By jbrooks Date 2022-05-24 Time 13:12 Rev Time 0.00
Received By jbrooks Date 2022-05-13 Time 15:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-12 Cont ID  
Sent By lmarchan Date 2022-05-12 Time 16:39 Rev Time 0.00
Received By lmarchan Date 2022-04-27 Time 08:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-29 Cont ID  
Sent By jbrooks Date 2022-06-29 Time 10:10 Rev Time 0.00
Received By jbrooks Date 2022-06-29 Time 10:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-17 Cont ID  
Sent By jbrooks Date 2022-06-17 Time 10:59 Rev Time 0.00
Received By jbrooks Date 2022-06-17 Time 10:58 Sent To  
Notes
2022-06-17 10:59:30JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 SUBMITTED SIGNED AND SEALED ENHANCED NAILING
 CALCULATIONS CAN NOT BE VERIFIED IT APPEARS TO BE A
 COPY OF A DIGITALLY SIGNED DOCUMENT.
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 EITHER UPLOAD A VALID ELECTRONICALLY SIGNED PLAN TO ME,
 OR YOU CAN MAIL OR DROP OFF ONE ORIGINAL SIGNED AND
 SEALED PAPER ORIGINAL WITH A WET SIGNATURE TO:
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  


Account Summary | Usage Policy | Privacy Policy