Plan Review Details - Permit 22040335
Plan Review Stops For Permit 22040335
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-04-28 Cont ID  
Sent By cpuell Date 2022-04-28 Time 12:09 Rev Time 0.00
Received By cpuell Date 2022-04-28 Time 12:09 Sent To  
Notes
2022-04-28 12:10:32NEW PERMIT APPLICATION SUBMIT TO REFLECT THE SCOPE OF
 WORK TO BE ON THE 10TH FLOOR.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By cpuell Date 2022-04-27 Time 15:37 Rev Time 0.00
Received By cpuell Date 2022-04-27 Time 15:37 Sent To  
Notes
2022-04-27 15:38:02INCONSISTENCY BETWEEN THE APPLICATION FORM WHICH LISTS
 SUITE 100 AND THE PLANS THAT LIST THE 10TH FLOOR.
 PLEASE UPDATE THE PLANS OR THE APPLICATION FORM TO SHOW
 THE CORRECT ADDRESS AND LOCATION FOR THIS SCOPE OF
 WORK. PLEASE CONTACT [email protected] OR CALL
 561-805-6659 TO DISCUSS FURTHER IF NEEDED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-07-12 Cont ID  
Sent By mpeterso Date 2022-07-12 Time 11:40 Rev Time 0.00
Received By mpeterso Date 2022-07-12 Time 11:40 Sent To  
Notes
2022-07-12 11:40:59AUDIT OF VOICE AND DATA PLAN PASSED

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-07-12 Cont ID  
Sent By mpeterso Date 2022-07-12 Time 11:41 Rev Time 0.00
Received By mpeterso Date 2022-07-08 Time 08:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status F Date 2022-06-07 Cont ID  
Sent By jleahy Date 2022-06-06 Time 16:15 Rev Time 0.00
Received By shill Date 2022-06-02 Time 06:24 Sent To  
Notes
2022-06-07 07:13:33THIS REVIEW WAS ADDED TO PROVIDE FURTHER CLARIFICATION
 FOR THE PRIVATE PROVIDER PLAN REVIEW.
  
 22030685 (MASTER) - SHEET IA-310 PREPARED BY DIEGO
 ROBERTO MARTINEZ ([email protected]), AR99036. THE
 PLAN SUBMITTED IS DATED 11/23/21.
  
 THE PAGE SUBMITTED FOR 22040335 HAS A DIFFERENT DATE,
 CLIENT REVISIONS 12/7/2021, IS OF POOR QUALITY (APPEARS
 TO BE A SCAN), AND IS NOT DIGITALLY SIGNED. BECAUSE THE
 PAGE SUBMITTED IS A SCAN RATHER THAN A PDF FROM THE
 ARCHITECT'S OFFICE, WE CANNOT EASILY DETERMINE CTHE
 CHANGS TO SEE IF A REVISION SHOULD BE REQUIRED.
  
 TWO PAGES WERE UPLOADED, ONE WAS THE POOR QUALITY
 REVISED PLAN, THE SECOND PAGE IS THE SAME PAGE FROM THE
 ISSUED PERMIT, VERSION 11/23/21. IT IS NOT CLEAR WHY
 THAT WAS SUBMITTED, PLEASE EMAIL
 [email protected] AND REQUEST THAT IT BE REMOVED.
  
 THE AFFIDAVIT IS NOT CORRECT FOR THE PAGE SUBMITTED,
 REFERS TO WRONG VERSION.
  
 IT APPEARS THAT A REVISION IS REQUIRED.
  
 THE AFFIDAVIT FOR THE MASTER WAS EVALUATED ONLY FOR
 CONSISTENCY BETWEEN THE AFFIDAVIT AND THE PLANS
 SUBMITTED. HOWEVER IN REEVALUATION, IT IS NOT CLEAR WHY
 AN ELECTRICAL PAGE WOULD APPEAR ON THE BUILDING
 REVIEWER'S AFFIDAVIT. SHEET IA-310 IS LOW VOLTAGE AND
 ELECTRICAL, NOT WITHIN THE SCOPE OF A BUILDING PLANS
 EXAMINER LICENSE.
  
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-30 Cont ID  
Sent By shill Date 2022-04-30 Time 08:57 Rev Time 0.00
Received By shill Date 2022-04-28 Time 07:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-27 Cont ID  
Sent By cpuell Date 2022-04-27 Time 15:38 Rev Time 0.00
Received By cpuell Date 2022-04-26 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-14 Cont ID  
Sent By shill Date 2022-04-14 Time 17:12 Rev Time 0.00
Received By shill Date 2022-04-12 Time 17:10 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status P Date 2022-07-12 Cont ID  
Sent By mpeterso Date 2022-07-12 Time 11:40 Rev Time 0.00
Received By mpeterso Date 2022-07-12 Time 11:40 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status F Date 2022-06-06 Cont ID  
Sent By jleahy Date 2022-06-06 Time 16:13 Rev Time 0.00
Received By jleahy Date 2022-06-06 Time 16:13 Sent To  
Notes
2022-06-06 16:14:54FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NEW PAGE SUBMITTED 1A-310 HAS THE CORRECT DATE BUT THE
 PLAN IS NOT SIGNED AND SEALED BY THE PERSON OF RECORD.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2022-04-30 Time   Rev Time 0.00
Received By   Date 2022-04-30 Time   Sent To  
Notes
2022-04-30 08:51:42IA301 HAS A DIFFERENT REVISION DATE THAN THE AFFIDAVIT.
  
 FS553.791, THE AFFIDAVIT SHOULD REFLECT THE PAGE(S)
 REVIEWED BY THE PRIVATE PROVIDER.
  
2022-04-29 12:54:27PLAN AND AFFIDAVIT WERE APPROVED UNDER THE MASTER-
 22030685.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2022-04-27 Cont ID  
Sent By cthroop Date 2022-04-27 Time 12:52 Rev Time 0.00
Received By cthroop Date 2022-04-27 Time 12:38 Sent To  
Notes
2022-04-27 12:58:07PRIVATE PROVIDER PER SEC. 553.791 F.S.
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 4TH REVIEW
  
 AFFIDAVIT REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLAN PAGES LISTED ON AFFIDAVIT ARE: COVER PAGE,
 IA-410 AND IA-801.
 PLAN PAGE SUBMITTED FOR REVIEW IS IA-310.
 CORRECT AND RE-SUBMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-04-14 Cont ID  
Sent By shill Date 2022-04-14 Time 17:11 Rev Time 0.00
Received By shill Date 2022-04-14 Time 17:11 Sent To  
Notes
2022-04-14 17:12:30FS553.791, THIS PROJECT IS PRIVATE PROVIDER PLAN REVIEW
 & INSPECTIONS.
  
 AFFIDAVIT IS REQUIRED PRIOR TO BUILDING DIVISION AUDIT.
 FOR ADDITIONAL INFORMATION CONTACT:
  
 [email protected]
 [email protected], 305-246-0696
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-12 Cont ID  
Sent By mpeterso Date 2022-07-12 Time 11:41 Rev Time 0.00
Received By mpeterso Date 2022-07-12 Time 11:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-27 Cont ID  
Sent By cthroop Date 2022-04-27 Time 12:52 Rev Time 0.00
Received By cthroop Date 2022-04-27 Time 12:38 Sent To  
Notes
2022-04-29 12:54:55PLAN SHEET SIG WAS APPROVED UNDER THE MASTER- 22030685.