| Plan Review Stops For Permit 22040290 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2022-09-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-27 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-27 |
Time |
16:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2022-09-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-27 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-27 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2022-09-27 11:52:39 | SFR ADDITION - REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THERE ARE MULTIPLE ROOFING SYSTEMS IN THE ROOFING | | | PRODUCT APPROVAL - - PRODUCT APPROVAL (16-0203.01) FOR | | | THE FLAT DECK ROOFING = NEED TO CHOOSE A ROOFING SYSTEM | | | IN THE PRODUCT APPROVAL THAT MEETS THE REQUIRED WIND | | | DESIGN PRESSURE - PLEASE CIRCLE THE ROOFING SYSTEM TO | | | BE USED IN THE PRODUCT APPROVAL - IF NEEDED PLEASE | | | PROVIDE ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT | | | OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY | | | REQUIRE A HIGHER WIND PRESSURE THEN THE CHOSEN ROOFING | | | SYSTEM - SEE GENERAL LIMITATION NOTE 7 ON THE PRODUCT | | | APPROVAL. | | | | | | 2) ROOFING SYSTEM PRODUCT APPROVALS MAY BE DEFERRED | | | SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE | | | CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1 DEFERRED | | | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED | | | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN | | | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION | | | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL | | | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL | | | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING | | | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS | | | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE | | | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL | | | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW | | | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A | | | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL | | | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL | | | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED | | | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE | | | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE | | | BUILDING OFFICIAL. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-16 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-16 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2022-09-16 11:03:47 | SFR ADDITION - REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THERE ARE MULTIPLE ROOFING SYSTEMS IN THE ROOFING | | | PRODUCT APPROVAL - - PRODUCT APPROVAL (18-0919.07) FOR | | | THE FLAT DECK ROOFING = NEED TO CHOOSE A ROOFING SYSTEM | | | IN THE PRODUCT APPROVAL THAT MEETS THE REQUIRED WIND | | | DESIGN PRESSURE - PLEASE CIRCLE THE ROOFING SYSTEM TO | | | BE USED IN THE PRODUCT APPROVAL - IF NEEDED PLEASE | | | PROVIDE ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT | | | OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY | | | REQUIRE A HIGHER WIND PRESSURE THEN THE CHOSEN ROOFING | | | SYSTEM - SEE GENERAL LIMITATION NOTE 7 ON THE PRODUCT | | | APPROVAL. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-08-12 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-12 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2022-08-12 16:07:14 | SFR ADDITION - REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THERE ARE MULTIPLE ROOFING SYSTEMS IN THE ROOFING | | | PRODUCT APPROVAL - - PRODUCT APPROVAL (18-0919.07) FOR | | | THE FLAT DECK ROOFING = NEED TO CHOOSE A ROOFING SYSTEM | | | IN THE PRODUCT APPROVAL THAT SHOWS THE REQUIRED WIND | | | DESIGN PRESSURE (ROOFING WIND DESIGN PRESSURES ARE NOT | | | SHOWN ON THE DRAWINGS ) PER FBC R TABLE R301.2(2) - | | | PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE | | | PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE ADDITIONAL | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER WIND | | | PRESSURE THEN THE CHOSEN ROOFING SYSTEM - SEE NOTES ON | | | THE PRODUCT APPROVAL. | | | | | | | | | FYI - - ROOFING SYSTEM PRODUCT APPROVALS MAY BE | | | DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON | | | THE CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED | | | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED | | | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN | | | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION | | | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL | | | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL | | | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING | | | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS | | | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE | | | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL | | | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW | | | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A | | | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL | | | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL | | | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED | | | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE | | | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE | | | BUILDING OFFICIAL. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-12 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-12 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2022-07-12 16:14:16 | SFR ADDITION - REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE ROOFING SYSTEM PRODUCT APPROVAL | | | LISTED ON THE DRAWINGS. | | | | | | 2) PLEASE PROVIDE THE SINGLE HUNG WINDOW PRODUCT | | | APPROVAL LISTED ON THE DRAWINGS. | | | | | | 3) THE PROVIDED PRODUCT APPROVAL 17-0411.06 HAS EXPIRED | | | AND IS NOT LISTED ON THE DRAWINGS. ALL PRODUCT | | | APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY | | | THE BUILDING DESIGNER OR BE LISTED ON THE DRAWINGS BY | | | THE PRODUCT APPROVAL NUMBER. FBC WPB 107.3.4 | | | | | | 4) DRAWING S2.1 SHOWS ROOF FRAMING AS 2X8 JOIST SPACED | | | 24" OC. - DRAWING S1.1 SHOWS 2X12 RAFTERS SPACED 16" OC | | | - PLEASE CLARIFY - R30 INSULATION WILL NOT WORK IN 2X8 | | | JOIST (A 1" AIR GAP IS REQUIRED BETWEEN THE INSULATION | | | AND THE ROOF DECKING. | | | | | | 5) PLEASE SHOW THE VENTILATION FOR THE RAFTER SPACE FBC | | | R806.1 VENTILATION REQUIRED. | | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE | | | ENTRANCE OF RAIN OR SNOW. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-08-16 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-08-16 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-06-10 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-10 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-10 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2022-06-10 10:32:08 | ELECTRIC REVIEW FAILED | | | 1) SMOKE ALARMS ARE NOT DETAILED IN AND OUTSIDE OF | | | BEDROOM 4 AS PER FBC R314.3 | | | 2) PLEASE DETAIL THE REQUIRE OUTDOOR RECEPTACLE AT | | | MASTER BEDROOM EXIT AS PER NEC 210.52(E)(3) BALCONIES, | | | DECKS, AND PORCHES | | | 3) PLANS DETAIL A NEW LOCATION FOR METER AND PANEL. | | | RISER DETAILS AN EXISTING METER MAIN AND EXISTING | | | PANEL. FLOOR PLANS DO NOT DETAIL A SYMBOL FOR THE 200 | | | AMP PANEL. PLEASE CORRECT NOMENCLATURE FOR METER ON | | | RISER AS NEW AND DETAIL 200 AMP ELECTRIC PANEL | | | LOCATION. NEC 215.5 AND FBC 107.2 | | | 4) LOAD CALCULATION APPEARS TO HAVE INCORRECT NUMBERS. | | | IT APPEARS TO BE MISSING LOADS SUCH AS LAUNDRY, SMALL | | | APPLIANCE AND OTHERS. PLEASE CORRECT AS APPLICABLE. NEC | | | 215.5 | | | 5) PLEASE DETAIL APPLICABLE LIGHTING AND RECEPTACLES AS | | | GROUND FAULT PROTECTED, ARC FAULT PROTECTED AND TAMPER | | | RESISTANT AS PER NEC 210.12, NEC 406.4, NEC 406.12, NEC | | | 406.4(D)(5) AND NEC 210.8 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-09-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-27 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-23 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-16 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-30 |
Time |
16:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-08-16 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-08-05 |
Time |
06:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-07-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-12 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-22 |
Time |
13:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-10-05 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-09-29 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2022-10-05 17:26:36 | RECEIPT MU-2022-0454350 - $0.00 DUE | | 2022-09-29 10:18:00 | 9/29/22 EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-07-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-12 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-12 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2022-07-12 16:15:19 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-02 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-02 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-12 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-12 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2022-08-12 10:52:28 | PROVIDE AN EXPLAINATION FOR THE NEW DUCTWORK. IS THERE | | | TO BE A NEW MECHANICAL SYSTEM? IS THIS TO BE THE | | | EXISTING UNIT? PROVIDE ENERGY CALCULATIONS AND | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS. FBC 107.2.1 | | | THE DETAILS FOR THE M1 DRAWING IS BLURRED AND NOT | | | READABLE. PROVIDE A CLEAR DRAWING TO REVIEW. FBC | | | 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-05-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-27 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-27 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2022-05-27 14:20:14 | PROVIDE A SCOPE OF WORK FOR THE MECHANICAL ON THIS | | | PROJECT. THE ENERGY CALCULATIONS SHOW 829 SQ.FT. THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOW 1918 | | | SQ.FT. THERE IS A DRAWING IN THE MANUAL J SUBMITTAL | | | THAT DOES NOT SHOW THE RETURN AIR PATH BACK TO THE AHU, | | | IT APPEARS TO BE FOR THE ENTIRE HOUSE AND NOT JUST THE | | | EDITION. THIS DRAWING IS NOT SIGNED BY THE DESIGNER. | | | THEN THERE IS ANOTHER MECHANICAL DRAWING SIGNED BY | | | DAVID FORKEY FOR WHAT APPEARS TO BE FOR THE NEW | | | ADDITION AND THE KITCHEN AREA. I DONT KNOW WHAT I'M | | | SUPPOSE TO LOOK AT. PLEASE CLEAN THIS SUBMITTAL UP AND | | | BE CONSISTENT WITH THE DOCUMENTS SUBMITTED. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-05-21 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-05-21 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-05-21 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2022-09-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-27 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-27 |
Time |
16:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2022-09-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-27 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-27 |
Time |
11:54 |
Sent To |
|
|
| Notes |
| 2022-09-27 11:55:10 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-16 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-16 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2022-09-16 11:04:24 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-08-12 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-12 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2022-08-12 16:08:03 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-07-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-12 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-12 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2022-07-12 16:15:51 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-02 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-02 |
Time |
10:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-12 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-12 |
Time |
10:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-07-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-12 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-12 |
Time |
16:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-08-12 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-08-12 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-05-24 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-05-24 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-05-24 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2022-05-24 11:56:50 | 5/24/2022 | | | FAIL | | | THE VALUE OF THE CONSTRUCTION ($200,000) EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE ($122,368) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | ALSO PLEASE LABEL THE SETBACKS ON SURVEY OF PROPOSED | | | ADDITION TO THE REAR OF THE PROPERTY. | | | | | | | | | | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] |
|
|