Plan Review Details - Permit 22040284
Plan Review Stops For Permit 22040284
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-05-12 Cont ID  
Sent By rmcphers Date 2022-05-12 Time 07:46 Rev Time 0.00
Received By rmcphers Date 2022-05-12 Time 07:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-05 Cont ID  
Sent By rmcphers Date 2022-07-05 Time 10:32 Rev Time 0.00
Received By rmcphers Date 2022-07-05 Time 10:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-09 Cont ID  
Sent By rmcphers Date 2022-06-09 Time 15:52 Rev Time 0.00
Received By rmcphers Date 2022-06-09 Time 15:52 Sent To  
Notes
2022-06-09 15:54:00CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 THE FRONT DOOR - DOES IT OPEN TO A CORRIDOR OR THE
 EXTERIOR OF THE BUILDING?
  
 1) PLEASE SHOW THE FIRE RATING FOR THE ENTRY DOOR PER
 FBC 716.5
  
 2) PLEASE SHOW THE FIRE RATED DOOR TO BE SELF CLOSING
 PER 716.5.9
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-12 Cont ID  
Sent By rmcphers Date 2022-05-12 Time 08:22 Rev Time 0.00
Received By rmcphers Date 2022-05-12 Time 07:37 Sent To  
Notes
2022-05-12 08:22:49CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE FIRE RATING FOR THE ENTRY DOOR PER
 FBC 716.5
  
 2) PLEASE SHOW THE FIRE RATED DOOR TO BE SELF CLOSING
 PER 716.5.9
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-07-06 Cont ID  
Sent By fgiaquin Date 2022-07-06 Time 21:27 Rev Time 0.00
Received By fgiaquin Date 2022-07-06 Time 20:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-18 Cont ID  
Sent By fgiaquin Date 2022-06-18 Time 23:48 Rev Time 0.00
Received By fgiaquin Date 2022-06-18 Time 21:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-23 Cont ID  
Sent By fgiaquin Date 2022-05-23 Time 23:52 Rev Time 0.00
Received By fgiaquin Date 2022-05-23 Time 22:53 Sent To  
Notes
2022-05-23 23:52:18ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO SMOKE/CO ALARMS SHOWN. FBC-R 314 AND 315 FBC
 107.2.1
  
 2. RECEPTACLE REQUIRED ON BALCONY NEC 210.52E3
  
 3. PROVIDE RISER DIAGRAM OF EXISTING SERVICE/PANEL. FBC
 107.2.1
  
 4. LOCATION OF PANEL NOT SHOWN? FBC 107.2.1
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-06-24 Cont ID  
Sent By cwalker Date 2022-06-24 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-06-06 Cont ID  
Sent By cwalker Date 2022-06-06 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-06-06 11:01:34FIRE COMMENT:
 PROVIDE THE SPECIFIC FIRE RATING OF THE ENTRY DOOR,
 DOOR 100.1, TO INCLUDE THE FIRE DOOR, FRAME, HARDWARE
 INCLUDING SELF-CLOSING DEVICE, AND OTHER ACCESSORIES
 THAT TOGETHER PROVIDE A SPECIFIC DEGREE OF FIRE
 PROTECTION TO THE OPENING. NFPA 80, CHAPTER 6.
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-05-02 Cont ID  
Sent By cwalker Date 2022-05-02 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-05-02 09:36:51FIRE REVIEW COMMENTS:
 1) PROVIDE DETAIL ON THE FIRE RATED ENTRY DOOR
 REQUIREMENTS TO COMPLY WITH NFPA 80, CHAPTER 6. PER
 NFPA 80, 3.3.50 A FIRE DOOR ASSEMBLY INCLUDES THE FIRE
 DOOR, FRAME, HARDWARE, AND OTHER ACCESSORIES THAT
 TOGETHER PROVIDE A SPECIFIC DEGREE OF FIRE PROTECTION
 TO THE OPENING.
 2) PROVIDE THE TYPE OF CARPET TO BE INSTALLED TO COMPLY
 WITH NFPA 101, 10.2.7.1
 3) PROVIDE LOCATIONS AND TYPE OF SMOKE ALARMS TO BE
 PROVIDED INCLUDING THE BEDROOM AND PROPOSED LIBRARY.
 NFPA 101 31.3.4.5
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-06 Cont ID  
Sent By fgiaquin Date 2022-07-06 Time 21:27 Rev Time 0.00
Received By fgiaquin Date 2022-06-23 Time 09:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-18 Cont ID  
Sent By fgiaquin Date 2022-06-18 Time 23:48 Rev Time 0.00
Received By fgiaquin Date 2022-06-02 Time 06:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-23 Cont ID  
Sent By fgiaquin Date 2022-05-23 Time 23:52 Rev Time 0.00
Received By fgiaquin Date 2022-04-29 Time 08:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-05-13 Cont ID  
Sent By medwards Date 2022-05-13 Time 07:08 Rev Time 0.00
Received By medwards Date 2022-05-13 Time 07:07 Sent To  
Notes
2022-05-13 07:08:19NO MECHANICAL WORK SHOWN FOR THIS PROJECT. ME

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-06-24 Cont ID  
Sent By rwbrown Date 2022-06-24 Time 12:54 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-05-09 Cont ID  
Sent By rwbrown Date 2022-05-09 Time 10:21 Rev Time 0.00
Received By rwbrown Date 2022-05-09 Time 10:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-05 Cont ID  
Sent By rmcphers Date 2022-07-05 Time 10:34 Rev Time 0.00
Received By rmcphers Date 2022-07-05 Time 10:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-06-09 Cont ID  
Sent By rmcphers Date 2022-06-09 Time 15:55 Rev Time 0.00
Received By rmcphers Date 2022-06-09 Time 15:55 Sent To  
Notes
2022-06-09 15:56:55SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS PROVIDED DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).- OR - IF YOUR ARCHITECT,
 ENGINEER OR SURVEYOR DOES NOT HAVE A VERIFIABLE
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-23 Cont ID  
Sent By fgiaquin Date 2022-05-23 Time 23:48 Rev Time  
Received By fgiaquin Date   Time   Sent To  
Notes
2022-05-23 23:47:20PLANS MUST BE DIGITALLY SIGNED BY ARCHITECT.