| Plan Review Stops For Permit 22040264 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-06-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-06-04 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-06-04 |
Time |
06:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-06-03 |
|
|
Cont ID |
|
| Sent By |
jbrooks |
Date |
2022-06-03 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
jbrooks |
Date |
2022-06-03 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2022-06-03 13:16:45 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected]. | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-5; | | | EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); | | | ULTIMATE WIND SPEED (170). ZONE 3 IS MARKED ?N/A? WHICH | | | INDICATES SYSTEM CANNOT BE USED WITHIN THE PRESSURE | | | ZONE. THE CORRECT EXPOSURE FOR THE LISTED ADDRESS IS | | | EXPOSURE C. PLEASE SELECT THE CORRECT OPTIONS. | | | 2. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA | | | NO.20-1214.01 TILE BOND IS NOT AN APPROVED TILE | | | ADHESIVE AS PER THE MIAMI-DADE NOA NO. 18-0119.03 | | | VERREA BARREL TILE GRADE 1. PROVIDE A COMPLETE SET OF | | | 2020 CODE VERSION PRODUCT APPROVALS/NOA'S FOR AN | | | APPROVED ROOFING TILE ADHESIVE TO BE USED. (POLYSET | | | AH-160) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-05-10 |
|
|
Cont ID |
|
| Sent By |
jbrooks |
Date |
2022-05-10 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
jbrooks |
Date |
2022-05-10 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2022-05-10 11:22:37 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected]. | | | | | | 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL | | | FL16709-R10 IS INCOMPLETE, PROVIDE THE FOLLOWING | | | ADDITIONAL INFORMATION: COVER SHEET | | | (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE (CODE | | | VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL | | | INFORMATION ABOUT THE PRODUCT). EVALUATION REPORT PAGES | | | 1-4 TO INCLUDE LIMITATIONS PAGE(S). THE EVALUATION | | | REPORTS CAN BE PRINTED FROM THE SUMMARY OF PRODUCTS | | | LOCATED AT THE BOTTOM OF THE COVER PAGE. PRINT PAGES | | | 1-4 ONLY. | | | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R10 COVERS MULTIPLE ROOF SYSTEM TYPES | | | A-2 THROUGH E, NO. W-1 THRU W-5. PLEASE SELECT SYSTEM | | | NO.; EXPOSURE; ENCLOSURE; ROOF HEIGHT; ZONES WITH | | | NAILING PATTERNS AND ULTIMATE WIND SPEED. ALL | | | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS | | | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT | | | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-13 |
|
|
Cont ID |
|
| Sent By |
jbrooks |
Date |
2022-04-13 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
jbrooks |
Date |
2022-04-13 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2022-04-13 10:06:44 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected]. | | | | | | 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R6 IS THE 2017 CODE VERSION AND IS NO | | | LONGER VALID. PLEASE PROVIDE A COMPLETE SET OF 2020 | | | CODE VERSION PRODUCT APPROVALS/NOA?S FOR THE PROPOSED | | | FLAT ROOF SYSTEM TO BE USED. INCLUDE COVER PAGE, | | | EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR | | | SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS | | | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL | | | DRAWINGS. (FL16709-R9) | | | 2. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF | | | DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING | | | CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), | | | MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW | | | POSITIVE DRAINAGE. | | | 3. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR | | | THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL | | | HEIGHT(S). | | | 4. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT | | | COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL | | | AND CHAPTER 11 OF THE 2020 FBC-PLUMBING | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
4 |
Status |
P |
Date |
2022-05-26 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-05-26 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-05-26 |
Time |
10:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-05-18 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-05-18 |
Time |
14:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-04-29 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-04-29 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-04-29 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2022-04-29 14:45:15 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | TILED ROOF PORTION NEEDS TO HAVE A TRUE BARREL TILE | | | RATHER THAN AN S TILE. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-04-27 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-04-27 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2022-04-27 16:11:14 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | AS DISCUSSED, PLEASE REVISE THE TILE PORTION TO BE A | | | BARREL TILE RATHER THAN AN S TILE | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-06-03 |
|
|
Cont ID |
|
| Sent By |
jbrooks |
Date |
2022-06-03 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
jbrooks |
Date |
2022-05-22 |
Time |
12:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-05-19 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-05-19 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-04-29 |
Time |
13:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-04-28 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-04-28 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-04-12 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|