| Plan Review Stops For Permit 22040203 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-18 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-18 |
Time |
11:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-04 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-04 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2022-05-04 08:03:17 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-18 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-18 |
Time |
11:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-04 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-04 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2022-05-04 08:07:46 | CONDO REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE TYPE OF FLOORING TO BE INSTALLED ON | | | THE DRAWINGS | | | | | | 2) FOR THE FLOORING - THE FOLLOWING ACUSTICAL TEST | | | REPORTS ARE REQUIRED: | | | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. | | | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING | | | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY | | | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP | | | CEILING DESCRIPTION) | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP | | | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING | | | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED | | | DROP CEILING DESCRIPTION) | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | | ATTACHED TO THE FLOORING) | | | | | | YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY | | | THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING TO | | | PROJECTDOX ( [email protected] ) | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-06-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-01 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-01 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-04-27 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-04-27 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2022-04-27 15:52:53 | ELECTRIC REVIEW FAILED | | | 1) PLEASE PROVIDE A DRAWING OF THE ELECTRIC WORK BEING | | | DONE.FBC 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-05-13 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-05-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-04-08 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-04-08 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-08 09:54:26 | FIRE COMMENTS: | | | 1) THE SUBMITTAL DOES NOT INDICATE THE TYPE OF FLOORING | | | TO BE INSTALLED. FLOORING MATERIALS MAY REQUIRE | | | INFORMATION TO BE PROVIDED FOR FIRE PERFORMANCE | | | INCLUDING THE CRITICAL RADIANT FLUX OF THE MATERIAL PER | | | NFPA 101 10.2.7 | | | 2) THE REMOVAL OF ANY WALLS MAY REQUIRE THE EVALUATION | | | OF THE FIRE AND LIFE SAFETY SYSTEMS INCLUDING FIRE | | | SPRINKLER IF APPLICABLE, AND FIRE ALARMS TO INSURE | | | ADEQUATE COVERAGE. | | | 3) ALL EXISTING LIFE SAFETY SYSTEMS INCLUDING FIRE | | | SPRINKLER IF APPLICABLE AND FIRE ALARM DEVICES MUST BE | | | PROTECTED FROM DAMAGE AND MAINTAINED IN WORKING | | | CONDITION DURING ALL PHASES OF DEMOLITION AND | | | CONSTRUCTION. | | | 4) ANY MODIFICATIONS TO ANY LIFE SAFETY SYSTEM | | | INCLUDING FIRE SPRINKLERS IF APPLICABLE AND FIRE ALARM | | | SYSTEMS WILL REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS | | | AND THE WORK MUST BE CONDUCTED BY ONLY QUALIFIED | | | CONTRACTORS. | | | FIRE REVIEW PERFORMED BY: | | | C.R. WALKER | | | [email protected] | | | 561-804-4762 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-06-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-01 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-12 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-04 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-04-07 |
Time |
08:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-05-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-19 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-19 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-04-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-04-13 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-04-13 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2022-04-13 16:56:30 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22040203 | | | 4/13/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE CHANGE GENERAL NOTE 5 TO INDICATE BATHTUB TO | | | SHOWER CONVERSION IN BATH 1- SEC. 107.2.1 WPB. | | | | | | 2) PROVIDE A SANITARY RISER DRAWING FOR THE NEW | | | LAVATORY INSTALLATION- SEC. 107.3.5.1.3 WPB. | | | | | | 3) PROVIDE A SHOWER PAN DETAIL- SECS 421.5 & 421.5.2 | | | FBC P. | | | | | | 4) THE PLANS DO NOT MAKE CLEAR IF ANY NEW PLUMBING | | | PIPES WILL BE PENETRATING THE EXISTING FLOOR SLAB. | | | PLEASE NOTE THE FOLLOWING ITEMS MAY APPLY- | | | NEW PIPE PENETRATIONS OF THE FLOOR SLAB WILL REQUIRE | | | THE SLAB TO BE X-RAYED TO IN ORDER TO LOCATE | | | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. | | | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE | | | WILL BE MET- SECTION 107.2.1 WPB. | | | NEW PIPE PENETRATIONS OF THE EXISTING SLAB WILL REQUIRE | | | FIRESTOPPING TO SEAL THE ANNULAR SPACE AROUND THE | | | PIPING. PROVIDE A UL TESTED AND APPROVED FIRESTOPPING | | | ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 FBC P AND | | | SECTION 714.4.1.2 FBC B. | | | THE HORIZONTAL DISTANCE FROM THE CENTERLINE OF THE NEW | | | SHOWER DRAIN OUTLET TO THE CENTERLINE OF THE INLET OF | | | THE EXISTING TRAP SHALL NOT EXCEED 30". PLEASE PLACE A | | | NOTE ON THE PLAN INDICATING COMPLIANCE- SEC. 1002.1 FBC | | | P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-18 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-18 |
Time |
11:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-04 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-04 |
Time |
08:07 |
Sent To |
|
|
| Notes |
|
|