Plan Review Details - Permit 22040203
Plan Review Stops For Permit 22040203
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By rmcphers Date 2022-05-18 Time 11:48 Rev Time 0.00
Received By rmcphers Date 2022-05-18 Time 11:48 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-05-04 Cont ID  
Sent By rmcphers Date 2022-05-04 Time 08:02 Rev Time 0.00
Received By rmcphers Date 2022-05-04 Time 08:02 Sent To  
Notes
2022-05-04 08:03:17PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By rmcphers Date 2022-05-18 Time 11:47 Rev Time 0.00
Received By rmcphers Date 2022-05-18 Time 11:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-04 Cont ID  
Sent By rmcphers Date 2022-05-04 Time 08:03 Rev Time 0.00
Received By rmcphers Date 2022-05-04 Time 08:03 Sent To  
Notes
2022-05-04 08:07:46CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE TYPE OF FLOORING TO BE INSTALLED ON
 THE DRAWINGS
  
 2) FOR THE FLOORING - THE FOLLOWING ACUSTICAL TEST
 REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY
 THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING TO
 PROJECTDOX ( [email protected] )
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-01 Cont ID  
Sent By mpeterso Date 2022-06-01 Time 11:01 Rev Time 0.00
Received By mpeterso Date 2022-06-01 Time 11:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By mpeterso Date 2022-04-27 Time 15:49 Rev Time 0.00
Received By mpeterso Date 2022-04-27 Time 15:49 Sent To  
Notes
2022-04-27 15:52:53ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE A DRAWING OF THE ELECTRIC WORK BEING
 DONE.FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-13 Cont ID  
Sent By cwalker Date 2022-05-13 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-04-08 Cont ID  
Sent By cwalker Date 2022-04-08 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-04-08 09:54:26FIRE COMMENTS:
 1) THE SUBMITTAL DOES NOT INDICATE THE TYPE OF FLOORING
 TO BE INSTALLED. FLOORING MATERIALS MAY REQUIRE
 INFORMATION TO BE PROVIDED FOR FIRE PERFORMANCE
 INCLUDING THE CRITICAL RADIANT FLUX OF THE MATERIAL PER
 NFPA 101 10.2.7
 2) THE REMOVAL OF ANY WALLS MAY REQUIRE THE EVALUATION
 OF THE FIRE AND LIFE SAFETY SYSTEMS INCLUDING FIRE
 SPRINKLER IF APPLICABLE, AND FIRE ALARMS TO INSURE
 ADEQUATE COVERAGE.
 3) ALL EXISTING LIFE SAFETY SYSTEMS INCLUDING FIRE
 SPRINKLER IF APPLICABLE AND FIRE ALARM DEVICES MUST BE
 PROTECTED FROM DAMAGE AND MAINTAINED IN WORKING
 CONDITION DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION.
 4) ANY MODIFICATIONS TO ANY LIFE SAFETY SYSTEM
 INCLUDING FIRE SPRINKLERS IF APPLICABLE AND FIRE ALARM
 SYSTEMS WILL REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS
 AND THE WORK MUST BE CONDUCTED BY ONLY QUALIFIED
 CONTRACTORS.
 FIRE REVIEW PERFORMED BY:
 C.R. WALKER
 [email protected]
 561-804-4762
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-01 Cont ID  
Sent By mpeterso Date 2022-06-01 Time 11:02 Rev Time 0.00
Received By mpeterso Date 2022-05-12 Time 14:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-04 Cont ID  
Sent By rmcphers Date 2022-05-04 Time 08:08 Rev Time 0.00
Received By rmcphers Date 2022-04-07 Time 08:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-19 Cont ID  
Sent By ccole Date 2022-05-19 Time 10:06 Rev Time 0.00
Received By ccole Date 2022-05-19 Time 09:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-13 Cont ID  
Sent By ccole Date 2022-04-13 Time 16:52 Rev Time 0.00
Received By ccole Date 2022-04-13 Time 11:13 Sent To  
Notes
2022-04-13 16:56:301ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22040203
 4/13/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE CHANGE GENERAL NOTE 5 TO INDICATE BATHTUB TO
 SHOWER CONVERSION IN BATH 1- SEC. 107.2.1 WPB.
  
 2) PROVIDE A SANITARY RISER DRAWING FOR THE NEW
 LAVATORY INSTALLATION- SEC. 107.3.5.1.3 WPB.
  
 3) PROVIDE A SHOWER PAN DETAIL- SECS 421.5 & 421.5.2
 FBC P.
  
 4) THE PLANS DO NOT MAKE CLEAR IF ANY NEW PLUMBING
 PIPES WILL BE PENETRATING THE EXISTING FLOOR SLAB.
 PLEASE NOTE THE FOLLOWING ITEMS MAY APPLY-
 NEW PIPE PENETRATIONS OF THE FLOOR SLAB WILL REQUIRE
 THE SLAB TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
 NEW PIPE PENETRATIONS OF THE EXISTING SLAB WILL REQUIRE
 FIRESTOPPING TO SEAL THE ANNULAR SPACE AROUND THE
 PIPING. PROVIDE A UL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 FBC P AND
 SECTION 714.4.1.2 FBC B.
 THE HORIZONTAL DISTANCE FROM THE CENTERLINE OF THE NEW
 SHOWER DRAIN OUTLET TO THE CENTERLINE OF THE INLET OF
 THE EXISTING TRAP SHALL NOT EXCEED 30". PLEASE PLACE A
 NOTE ON THE PLAN INDICATING COMPLIANCE- SEC. 1002.1 FBC
 P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By rmcphers Date 2022-05-18 Time 11:48 Rev Time 0.00
Received By rmcphers Date 2022-05-18 Time 11:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-04 Cont ID  
Sent By rmcphers Date 2022-05-04 Time 08:07 Rev Time 0.00
Received By rmcphers Date 2022-05-04 Time 08:07 Sent To  
Notes
***NONE***