Plan Review Details - Permit 22040185
Plan Review Stops For Permit 22040185
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-14 Cont ID  
Sent By pvalenti Date 2022-04-14 Time 06:45 Rev Time 0.00
Received By pvalenti Date 2022-04-14 Time 06:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-05 Cont ID  
Sent By pvalenti Date 2022-04-05 Time 13:47 Rev Time 0.00
Received By pvalenti Date 2022-04-05 Time 13:38 Sent To  
Notes
2022-04-05 14:05:49PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, THE SUBMITTED INFORMATION IS INCOMPLETE.
 PLEASE PROVIDE THE FOLLOWING:
  
 1.) FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A
 SPAN
 OF 30 FEET OR GREATER IN ANY DIRECTION:
 A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE
 BASEPLATE/TIEDOWN DETAILS.
 B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE,
 INCLUDING WINDLOAD DESIGN PRESSURES.
  
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL.
 NOTE: TENTS WITH A 30? SPAN ARE PERMITTED WITHOUT THE
 ADDITIONAL ENGINEERING
 AND STRUCTURAL CONNECTION DETAILS IF THE CONTRACTOR
 PLACES THE FOLLOWING NOTE ON THE
 PLAN ? THIS TENT SHALL BE REMOVED IF WINDS ARE
 EXPECTEDTO
 EXCEED 30 M.P.H.
 ***THERE WILL BE NO EXCEPTION TO THE ABOVE REQUIREMENT
 FOR TENTS WITH A SPAN IN ANY
 DIRECTION OF 40? OR MORE.***
  
 2.) FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH AN
 ?ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS?.
  
 FLORIDA STATUTE 553.79 ?THREHOLD STRUCTURE? SHALL APPLY
 A. PROVIDE THRESHOLD INSPECTOR AGREEMENT ? WILL BE
 PROVIDED TO APPLICANT
 B. PROVIDE THRESHOLD INSPECTION PLAN
 C. PROVIDE AFFIDAVIT ?CERTIFICATE OF CODE COMPLIANCE?
  
 3.) FBC B 3103.1.1,
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY,
 MEANS OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND
 SANITARY REQUIREMENTS OF THIS
 CODE AS NECESSARY TO ENSURE PUBLIC HEALTH, SAFETY AND
 GENERAL WELFARE.
 A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR
 STRUCTURES WITH SPANS OF 30 FEET OR GREATER.
 B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER
 NFPA 701 FOR EACH TENT
 C. MEANS OF EGRESS
 1) OPEN SIDES ? NO LIFE SAFETY PLAN REQUIRED.
 2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN
 A) STATE OCCUPANT LOAD.
 B) IDENTIFY MEANS OF EGRESS.
 C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO EXIT.
 D) PROVIDE FLOOR LAYOUT OF EVENT.
 D. ACCESSIBILITY
 1) IDENTIFY ACCESSIBLE ROUTE ON SITE PLAN
 E. LIGHT
 1) OPEN SIDES ? N/A
 2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE
 F. VENTILATION
 1) OPEN SIDES ? N/A
 2) CLOSED SIDES ? PER SEC. 1203
 G. SANITARY
 1) IDENTIFY EXISTING PERMANENT FACILITIES ON SITE PLAN
 2) PROVIDE PORTABLE FACILITIES PER TABLE 2902.1

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-13 Cont ID  
Sent By pleduc Date 2022-04-13 Time   Rev Time 0.00
Received By pleduc Date 2022-04-13 Time 16:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-04-06 Cont ID  
Sent By pleduc Date 2022-04-06 Time   Rev Time 0.00
Received By pleduc Date 2022-04-06 Time 11:22 Sent To  
Notes
2022-04-06 11:30:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF TENTS > 900 SQ FT WHICH
 WILL REQUIRE A LIFE SAFETY REVIEW; HOWEVER, THERE ARE
 NO INDICATIONS OF THOSE TENTS INDICATING, SIDEWALLS,
 DOORS, EXIT SIGNS, FE LOCATIONS, SEATING PLANS, ETC.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE ABOVE
 DETAILS FOR ALL TENTS > 900 SG FT.
  
  
 1A) THE SITE PLAN DOES NOT INDICATE THE LOCATION AND
 SIZE OF EACH OF THE TENTS INCLUDING THE SEPARATION
 DISTANCES FROM EACH OTHER AND BUIDLINGS IF APPLICABLE.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-07 Cont ID  
Sent By aoliver Date 2022-04-07 Time 11:10 Rev Time 0.00
Received By aoliver Date 2022-04-05 Time 10:54 Sent To  
Notes
***NONE***