Plan Review Details - Permit 22040177
Plan Review Stops For Permit 22040177
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-06-08 Cont ID  
Sent By aoliver Date 2022-06-08 Time 07:03 Rev Time 0.00
Received By aoliver Date 2022-06-08 Time 07:03 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-05-18 Cont ID  
Sent By jwitmer Date 2022-05-18 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2022-05-18 Time 14:44 Sent To  
Notes
2022-05-18 15:23:10TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-10 Cont ID  
Sent By jwitmer Date 2022-08-10 Time 09:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-03 Cont ID  
Sent By jwitmer Date 2022-08-03 Time 10:04 Rev Time 0.00
Received By jwitmer Date 2022-08-03 Time 09:36 Sent To  
Notes
2022-08-03 10:04:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22040177
 ADD: 525 S FLAGLER DR # 23B
 CONT: FACILITIES CONSRUCTION LLC
 TEL: 561-832-4950
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. AUGUST 03RD/ 2022
 ACTION: DENIED
  
 1) 2ND REVIEW. PLEASE NOTE THE PLANS SHEETS A0.0, A1.0
 & A2.0 ALL NEED TO BE REVISED DELETING ALL MENTIONS OF
 WINDOW, EXTERIOR DOOR REPLACEMENT. THIS WAS DISCUSSED
 WITH ASST. B. O. RICHARD GATHRIGHT. THE BUILDING
 OFFICIAL ROBERT BROWN RELAYED TO MR. GATHRIGHT LETTERS
 GET LOST PLEASE HAVE THE DESIGNER OF RECORD DELETING
 THIS SCOPE OF WORK.
 THE 2ND ISSUE WITH THE LETTER IS THERE IS A SIGNATURE
 BUT THERE IS NO PRINTED NAME SHOWING THIS LETTER IS
 FROM THE QUALIFIER OF THIS COMPANY.
 1ST ROUND OF COMMENTS. THE PERMIT APPLICATION UNDER THE
 HEADING OF DISCERPTION OF WORK LIST THE FOLLOWING;
 REDO KITCHEN, BATHROOMS, FLOORING, REPLACE EXTERIOR
 DOORS AND WINDOWS. PLEASE NOTE
 SHEET A0.0, A1.0 NOR A2.0 HAVE ANY INFORMATION ON WHICH
 WINDOWS AND DOORS THAT ARE
 PROPOSED TO BE REPLACED. AS TO DATE NO SEPARATE WINDOW/
 DOOR PERMIT HAS BEEN APPLIED
 FOR. THE FOLLOWING INFORMATION WOULD NEED TO BE
 SUPPLIED.
 2020 FBC-B 1603.1.4 WIND DESIGN CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 1.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 1.7) 2020 FBC-B 1709.5.1 HABITAT SPACES, WATER
 INTRUSION. EXTERIOR DOORS AND WINDOWS. EXCEPTION # 2.
 SILL LIMITING FACTOR.
  
 2) 2020 FBC-BUILDING 1609.4.3. EXPOSURE CATEGORIES,
 EXPOSURE D.
 EXPOSURE D SHALL APPLY WHERE THE GROUND SURFACE
 ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, PREVAILS
 IN THE UPWARD DIRECTION FOR A DISTANCE OF AT LEAST
 5,000 FEET OR 20 TIMES THE HEIGHT OF THE BUILDING,
 WHICHEVER IS GREATER. EXPOSURE SHALL ALSO APPLY WHERE
 THE GROUND SURFACE ROUGHNESS IMMEDIATELY UPWIND OF THE
 SITE IS B OR C , AND THE SITE IS WITHIN A DISTANCE OF
 600 FEET OR 20 TIMES THE BUILDING HEIGHT, WHICHEVER IS
 GREATER, FROM AN EXPOSURE D CONDITION AS DEFINED IN THE
 PREVIOUS SENTENCE.
  
 3) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS
  
 4) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-24 Cont ID  
Sent By jwitmer Date 2022-05-18 Time 15:27 Rev Time 0.00
Received By jwitmer Date 2022-05-18 Time 14:44 Sent To  
Notes
2022-05-18 15:22:32WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22040177
 ADD: 525 S FLAGLER DR # 23B
 CONT: FACILITIES CONSRUCTION LLC
 TEL: 561-832-4950
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 18TH/ 2022
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION UNDER THE HEADING OF
 DISCERPTION OF WORK LIST THE FOLLOWING;
 REDO KITCHEN, BATHROOMS, FLOORING, REPLACE EXTERIOR
 DOORS AND WINDOWS. PLEASE NOTE
 SHEET A0.0, A1.0 NOR A2.0 HAVE ANY INFORMATION ON WHICH
 WINDOWS AND DOORS THAT ARE
 PROPOSED TO BE REPLACED. AS TO DATE NO SEPARATE WINDOW/
 DOOR PERMIT HAS BEEN APPLIED
 FOR. THE FOLLOWING INFORMATION WOULD NEED TO BE
 SUPPLIED.
 2020 FBC-B 1603.1.4 WIND DESIGN CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 1.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 1.7) 2020 FBC-B 1709.5.1 HABITAT SPACES, WATER
 INTRUSION. EXTERIOR DOORS AND WINDOWS. EXCEPTION # 2.
 SILL LIMITING FACTOR.
  
 2) 2020 FBC-BUILDING 1609.4.3. EXPOSURE CATEGORIES,
 EXPOSURE D.
 EXPOSURE D SHALL APPLY WHERE THE GROUND SURFACE
 ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, PREVAILS
 IN THE UPWARD DIRECTION FOR A DISTANCE OF AT LEAST
 5,000 FEET OR 20 TIMES THE HEIGHT OF THE BUILDING,
 WHICHEVER IS GREATER. EXPOSURE SHALL ALSO APPLY WHERE
 THE GROUND SURFACE ROUGHNESS IMMEDIATELY UPWIND OF THE
 SITE IS B OR C , AND THE SITE IS WITHIN A DISTANCE OF
 600 FEET OR 20 TIMES THE BUILDING HEIGHT, WHICHEVER IS
 GREATER, FROM AN EXPOSURE D CONDITION AS DEFINED IN THE
 PREVIOUS SENTENCE.
  
 3) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS
  
 4) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 10:51 Rev Time 0.00
Received By mpeterso Date 2022-06-07 Time 10:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-11 Cont ID  
Sent By pleduc Date 2022-08-11 Time   Rev Time 0.00
Received By pleduc Date 2022-08-11 Time 12:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-02 Cont ID  
Sent By pleduc Date 2022-08-02 Time   Rev Time 0.00
Received By pleduc Date 2022-08-02 Time 10:37 Sent To  
Notes
2022-08-02 10:40:57FIRE PROVISO:
  
 THE REMOVAL AND CONSTRUCTION OF NEW SPACES/AREAS
 REQUIRE A REVIEW BY A FIRE SPRINKLER CONTRACTOR FOR
 MODIFICATIONS.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-17 Cont ID  
Sent By pleduc Date 2022-05-17 Time   Rev Time 0.00
Received By pleduc Date 2022-05-17 Time 12:05 Sent To  
Notes
2022-05-17 12:21:37FIRE PROVISO:
  
 THE REMOVAL AND CONSTRUCTION OF NEW SPACES/AREAS
 REQUIRE A REVIEW BY A FIRE SPRINKLER CONTRACTOR FOR
 MODIFICATIONS.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-15 Cont ID  
Sent By medwards Date 2022-08-15 Time 16:36 Rev Time 0.00
Received By medwards Date 2022-08-09 Time 16:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-09 Cont ID  
Sent By medwards Date 2022-08-09 Time 05:38 Rev Time 0.00
Received By medwards Date 2022-08-01 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-08 Cont ID  
Sent By aoliver Date 2022-06-08 Time 07:03 Rev Time 0.00
Received By aoliver Date 2022-05-16 Time 08:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-05-18 Cont ID  
Sent By jwitmer Date 2022-05-18 Time 15:02 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2022-08-15 Cont ID  
Sent By medwards Date 2022-08-15 Time 16:33 Rev Time 0.00
Received By medwards Date 2022-08-15 Time 16:33 Sent To  
Notes
2022-08-15 16:34:28PER ARCHITECT'S COMMENTS IN 3RD CYCLE REVIEW COMMENTS-
 MECHANICAL SUBMITTED UNDER A SEPARATE PERMIT. ME

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-08-09 Cont ID  
Sent By medwards Date 2022-08-09 Time 05:36 Rev Time 0.00
Received By medwards Date 2022-08-09 Time 05:35 Sent To  
Notes
2022-08-09 05:37:07PLEASE ADDRESS 1ST REVIEW CYCLE COMMENTS BELOW:
  
 SHEET A0.0: THE SCOPE OF WORK FOR THE MECHANIAL SYSTEM
 IS HVAC BY OTHERS> PLEASE PROVIDE A MECHANICAL SCOPE OF
 WORK AND MECHANICAL DRAWING SHOWING THE MECHANICAL
 WORK. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By medwards Date 2022-05-25 Time 10:50 Rev Time 0.00
Received By medwards Date 2022-05-25 Time 10:50 Sent To  
Notes
2022-05-25 10:53:24SHEET A0.0: THE SCOPE OF WORK FOR THE MECHANIAL SYSTEM
 IS HVAC BY OTHERS> PLEASE PROVIDE A MECHANICAL SCOPE OF
 WORK AND MECHANICAL DRAWING SHOWING THE MECHANICAL
 WORK. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-02 Cont ID  
Sent By rwbrown Date 2022-08-02 Time 07:37 Rev Time 0.00
Received By rwbrown Date 2022-08-02 Time 07:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-24 Cont ID  
Sent By rwbrown Date 2022-05-24 Time 12:11 Rev Time 0.00
Received By rwbrown Date 2022-05-24 Time 11:32 Sent To  
Notes
2022-05-24 12:11:531ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - PLEASE INCLUDE AN EXISTING
 FLOOR PLAN AND A PROPOSED FLOOR PLAN TO INDICATE THE
 CHANGES BEING MADE.
  
 2. 2020 FPC 1002.1 - THEE WASHING MACHINE IS NOT SHOWN
 WITH A TRAP. ALL FIXTURES SHALL BE TRAPPED.
  
 3. 2017 WPB AMENDS 107.3.5.1.3 - THE PLUMBING RISER
 NEEDS TO INCLUDE THE NEW WALL MOUNTED WATER CLOSET
 CONNECTION AND OTHER AFFECTED FIXTURES. THE WATER
 CLOSETS NEW CONNECTION WILL BE ABOVE THE FLOOR AND WILL
 NEED TO BE SHOWN IN ORDER TO REVIEW FOR CODE
 COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-07-01 Cont ID  
Sent By rgathrig Date 2022-07-01 Time 12:59 Rev Time 0.00
Received By rgathrig Date 2022-07-01 Time 12:57 Sent To  
Notes
2022-07-01 12:59:15PRIVATE PROVIDER INSPECTIONS ONLY
  
 REVIEWED DOCUMENTS FOR NTBO, INSURANCE AND RESUMES
 ALL ACCEPTABLE
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-15 Cont ID  
Sent By medwards Date 2022-08-15 Time 16:36 Rev Time 0.00
Received By medwards Date 2022-08-15 Time 16:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-09 Cont ID  
Sent By medwards Date 2022-08-09 Time 05:38 Rev Time 0.00
Received By medwards Date 2022-08-09 Time 05:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 10:53 Rev Time 0.00
Received By mpeterso Date 2022-06-07 Time 10:53 Sent To  
Notes
2022-06-07 10:53:51ALL PLANS PASSED SIGNATURE REVIEW


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved