| Plan Review Stops For Permit 22040143 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-07-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-08 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-08 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-06-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-06-23 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-06-23 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2022-06-23 09:06:03 | POOL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) REVISED DRAWINGS A.01 AND A.07 NEED TO BE SIGNED AND | | | SEALED BY THE DESIGNER - FBC 107.1 | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2022-05-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-25 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-25 |
Time |
14:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2022-07-20 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-07-20 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-07-20 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2022-07-15 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-07-15 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-07-15 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2022-07-15 13:01:20 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.CALCULATED LOAD ON PLAN EXCEEDS 200A SERVICE AT THIS | | | ADDRESS. | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER | | | | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-06-23 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-06-23 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-06-22 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2022-06-23 09:00:57 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | 2.APPROVED PLAN FOR THIS ADDRESS HAS 200A AMP SERVICE | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER | | | | | | 561-805-6742 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-04-26 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-04-26 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2022-04-26 10:28:59 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER | | | | | | 561-805-6742 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-07-20 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-07-20 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-07-19 |
Time |
17:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-07-15 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-07-15 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-06-28 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-06-23 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-06-23 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-06-07 |
Time |
07:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-05-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-25 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-04-06 |
Time |
07:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-04-07 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-04-07 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-04-07 |
Time |
10:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-07-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-08 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-08 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-06-23 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-06-23 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-06-23 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2022-06-23 09:07:56 | CORRECTIONS NEEDED - | | | | | | 1) REVISED DRAWINGS A.01 AND A.07 NEED TO BE SIGNED AND | | | SEALED BY THE DESIGNER - FBC 107.1 | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-05-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-25 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-25 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-07-01 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-07-01 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-07-01 |
Time |
10:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-06-10 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-06-10 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-06-10 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2022-06-10 11:23:55 | 06/10/22 - FAILED | | | | | | EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR | | | SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS | | | BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE | | | RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | | HEIGHT ABOVE GRADE. THE SITE PLAN AND SURVEY DO NOT | | | SHOW A FENCE. PLEASE KEEP IN MIND THAT ACCESS TO AN | | | ACCESSORY SWIMMING POOL MUST BE THROUGH A BUILDING OR | | | THROUGH A SELF-CLOSING AND SELF-LATCHING GATE OR | | | THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES PLACED AT | | | LEAST 54 INCHES ABOVE BOTTOM OF GATE. PLEASE SHOW | | | EITHER ON THE SURVEY OR SITE PLAN THAT THERE IS A | | | LOCKING FENCE OR GATE ENCLOSING THE POOL | | | | | | ALEXANDER FOWLKES | | | PLANNER | | | 5618221431 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-04-15 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-04-15 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-04-15 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2022-04-15 13:54:40 | 04/15/22 FAILED - PER CITY CODE, IF A PATIO OR PAVED | | | AREA IS PROVIDED ADJACENT TO OR SURROUNDING A POOL, IT | | | SHALL BE DESIGNED TO DRAIN AWAY FROM THE POOL, BUT NOT | | | ONTO ADJACENT PROPERTIES. THE SITE PLAN DOES NOT | | | SPECIFY ANY DRAINAGE DIRECTIONS | | | | | | ADDITIONALLY, EVERY SWIMMING POOL SHALL BE ENCLOSED BY | | | A FENCE OR SIMILAR STRUCTURE WHICH IS INSTALLED TO | | | OBSTRUCT ACCESS BY PERSONS OTHER THAN THE OWNERS OR | | | OCCUPANTS OF THE RESIDENCE WITHIN WHICH A SWIMMING POOL | | | IS LOCATED. BARRIERS OR FENCES SHALL BE AT LEAST FOUR | | | FEET IN HEIGHT ABOVE GRADE. THE SITE PLAN AND SURVEY DO | | | NOT SHOW A FENCE. PLEASE KEEP IN MIND THAT ACCESS TO AN | | | ACCESSORY SWIMMING POOL MUST BE THROUGH A BUILDING OR | | | THROUGH A SELF-CLOSING AND SELF-LATCHING GATE OR | | | THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES PLACED AT | | | LEAST 54 INCHES ABOVE BOTTOM OF GATE | | | | | | ALEXANDER FOWLKES | | | PLANNER | | | 5618221431 | | | [email protected] | | | | | | |
|
|