Plan Review Details - Permit 22040124
Plan Review Stops For Permit 22040124
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-04-15 Cont ID  
Sent By cpuell Date 2022-04-15 Time 09:52 Rev Time 0.00
Received By cpuell Date 2022-04-15 Time 09:52 Sent To  
Notes
2022-04-15 09:53:15NEW ADDRESS ASSIGNED TO PARCEL 6055 PINEWOOD AVE
 UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-04-14 Cont ID  
Sent By cpuell Date 2022-04-14 Time 13:38 Rev Time 0.00
Received By cpuell Date 2022-04-14 Time 13:38 Sent To  
Notes
2022-04-14 13:40:01AN ADDRESS NEEDS TO BE ASSIGNED TO THE PARCEL, PLEASE
 HAVE OWNER CONTACT [email protected] OR CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-07-28 Cont ID  
Sent By rmcphers Date 2022-07-28 Time 11:13 Rev Time 0.00
Received By rmcphers Date 2022-07-28 Time 11:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-07-18 Cont ID  
Sent By rmcphers Date 2022-07-18 Time 14:53 Rev Time 0.00
Received By rmcphers Date 2022-07-18 Time 14:53 Sent To  
Notes
2022-07-18 14:55:41NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVALS FOR THE DOOR AND WINDOW PRODUCT
 APPROVALS - THE INSTALLATION INSTRUCTIONS FOR BOTH HAVE
 BEEN PROVIDED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-23 Cont ID  
Sent By rmcphers Date 2022-06-23 Time 16:42 Rev Time 0.00
Received By rmcphers Date 2022-06-23 Time 16:33 Sent To  
Notes
2022-06-23 16:42:31NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVALS FOR THE WINDOWS AND EXTERIOR SWING
 DOORS. FBC WPB 107.2.1
  
 2) DRAWING S-0 "STRUCTURAL DESIGN CRITERIA" SHOWS THE
 WIND SPEED AT 165MPH - SHOULD BE 170MPH PER FBC WPB
 SECTION 120
  
 3) UNABLE TO FIND THE TRUSS STRAPPING SCHEDULE - FOR
 "H3" AND "H7" - PLEASE SHOW THE STRAP TYPE, BRAND,
 NAILING ETC. FBC WPB 107.2.1
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By rmcphers Date 2022-05-26 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2022-05-26 Time 11:45 Sent To  
Notes
2022-05-26 12:36:32NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS -
 ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.3.4
  
 2) DRAWING S-0 SHOWS THE DESIGN USING ASCE 7-10 -
 SHOULD BE ASCE 7-16 PER FBC R CHAPTER 46
  
 3) PLEASE SHOW ALL OF THE TRUSS STRAPPING AND OR
 ATTACHMENTS TO THE STRUCTURE - FBC 2303.4.4 ANCHORAGE.
 THE DESIGN FOR THE TRANSFER OF LOADS AND ANCHORAGE OF
 EACH TRUSS TO THE SUPPORTING STRUCTURE IS THE
 RESPONSIBILITY OF THE REGISTERED DESIGN PROFESSIONAL.
  
 4) PLEASE SHOW THE ATTIC ACCESS LOCATION FBC R807.1
  
 5) PLEASE PROVIDE A STORM WATER DRAINAGE PLAN OR
 INCLUDE SITE DRAINAGE ON THE SITE PLAN - FBC WPB
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-28 Cont ID  
Sent By mpeterso Date 2022-06-28 Time 14:46 Rev Time 0.00
Received By mpeterso Date 2022-06-28 Time 14:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-09 Cont ID  
Sent By mpeterso Date 2022-05-09 Time 11:45 Rev Time 0.00
Received By mpeterso Date 2022-05-09 Time 11:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-28 Cont ID  
Sent By rmcphers Date 2022-07-28 Time 11:14 Rev Time 0.00
Received By rmcphers Date 2022-07-19 Time 16:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-18 Cont ID  
Sent By rmcphers Date 2022-07-18 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2022-07-06 Time 07:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-28 Cont ID  
Sent By mpeterso Date 2022-06-28 Time 14:46 Rev Time 0.00
Received By mpeterso Date 2022-06-13 Time 07:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-26 Cont ID  
Sent By rmcphers Date 2022-05-26 Time 12:47 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 08:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-08-19 Cont ID  
Sent By lmarchan Date 2022-08-19 Time 10:48 Rev Time 0.00
Received By lmarchan Date 2022-07-28 Time 11:30 Sent To  
Notes
2022-08-18 15:30:27RECEIPT MU-2022-036151-0000 $11,623.07 PAID AO
2022-07-28 11:30:137/28/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By rmcphers Date 2022-05-26 Time 11:45 Rev Time 0.00
Received By rmcphers Date 2022-05-26 Time 11:45 Sent To  
Notes
2022-05-26 11:46:07PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-06-17 Cont ID  
Sent By medwards Date 2022-06-17 Time 11:04 Rev Time 0.00
Received By medwards Date 2022-06-17 Time 11:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-03 Cont ID  
Sent By medwards Date 2022-05-03 Time 07:44 Rev Time 0.00
Received By medwards Date 2022-05-03 Time 07:44 Sent To  
Notes
2022-05-03 07:44:341ST REVIEW FMC
 PERMIT: 22040124
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE DUCT SIZES ON THE MECHANICAL
 DRAWING. FBC 107.2.1
  
 2) PLEASE SHOW THE RETURN AIR PATH FROM ALL HABITUAL
 ROOMS WITH DOORS. FRC M1602.3
  
 3) PLEASE SHOW THE REQUIRED BATH EXHAUST FAN IN THE
 MASTER SHOWER AREA. FRC R303.3
  
 4) IS THERE A DUCTED HOOD TO BE INSTALLED ABOVE THE GAS
 RANGE? IF SO PLEASE PROVIDE THE CFM?S OF THE FAN. FRC
 M1503
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-04-26 Cont ID  
Sent By rwbrown Date 2022-04-26 Time 14:56 Rev Time 0.00
Received By rwbrown Date 2022-04-26 Time 14:28 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-05-26 Cont ID  
Sent By rmcphers Date 2022-05-26 Time 11:45 Rev Time 0.00
Received By rmcphers Date 2022-05-26 Time 11:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-28 Cont ID  
Sent By rmcphers Date 2022-07-28 Time 11:14 Rev Time 0.00
Received By rmcphers Date 2022-07-28 Time 11:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-18 Cont ID  
Sent By rmcphers Date 2022-07-18 Time 14:56 Rev Time 0.00
Received By rmcphers Date 2022-07-18 Time 14:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-06-23 Cont ID  
Sent By rmcphers Date 2022-06-23 Time 16:44 Rev Time 0.00
Received By rmcphers Date 2022-06-23 Time 16:44 Sent To  
Notes
2022-06-23 16:44:51SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE PROVIDED SURVEY DOES NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).- OR - IF YOUR ARCHITECT,
 ENGINEER OR SURVEYOR DOES NOT HAVE A VERIFIABLE
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  
2022-06-17 11:05:35DIGITAL MECHANICAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By rmcphers Date 2022-05-26 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2022-05-26 Time 12:38 Sent To  
Notes
2022-05-26 12:39:37SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE PROVIDED SURVEY DOES NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).- OR - IF YOUR ARCHITECT,
 ENGINEER OR SURVEYOR DOES NOT HAVE A VERIFIABLE
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-06-22 Cont ID  
Sent By afowlkes Date 2022-06-22 Time 15:49 Rev Time 0.00
Received By afowlkes Date 2022-06-22 Time 15:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-22 Cont ID  
Sent By afowlkes Date 2022-04-22 Time 10:28 Rev Time 0.00
Received By afowlkes Date 2022-04-22 Time 10:24 Sent To  
Notes
2022-04-22 10:27:5204/22/21 FAILED - SIDE SETBACKS ARE NOT INCLUDED ON THE
 SITEPLAN. ALTHOUGH IT SAYS THERE IS A 15 FT SETBACK, I
 NEED TO SEE THIS REFLECTED IN THE SITEPLAN DRAWING.
  
 ADDITIONALLY, I NEED THE ROOF OVERHANG AND AC EQUIPMENT
 WIDTH IN ORDER TO DETERMINE IF THEY ENCROACH TOO FAR
 INTO THE SETBACKS. SEE SECTION 94-305 FOR THESE SETBAK
 REQUIREMENTS.
  
 ALSO THE LANDSCAPE PLAN WAS LOCKE DOUT AS THIS NEEDS TO
 BE FILED FOR UNDER A SEPERATE PERMIT
  
 ALEXANDER FOWLKES
 5618221431
 [email protected]