Plan Review Details - Permit 22040109
Plan Review Stops For Permit 22040109
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-04-12 Cont ID  
Sent By cpuell Date 2022-04-12 Time 08:26 Rev Time 0.00
Received By cpuell Date 2022-04-12 Time 08:26 Sent To  
Notes
2022-04-12 08:26:44TWO PERMITS APPLIED FOR THE TWO BUILDINGS. 22040109 AND
 22040110

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-04-11 Cont ID  
Sent By cpuell Date 2022-04-11 Time 14:55 Rev Time 0.00
Received By cpuell Date 2022-04-11 Time 14:55 Sent To  
Notes
2022-04-11 14:57:03TWO BUILDING ON PARCEL, IS WORK FOR BOTH BUILDINGS, IS
 THE WORK FOR ANY OF THE 19 UNITS IN THE BUILDINGS?
 PLEASE RESPOND TO [email protected] OR CALL 561-805-6659

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-04 Cont ID  
Sent By jleahy Date 2022-05-04 Time 08:54 Rev Time 0.00
Received By jleahy Date 2022-05-04 Time 08:54 Sent To  
Notes
2022-05-04 08:55:56ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) LOAD ON MDPA IS ABOVE 1600 AMPERES AND 1520 AMPERES
 OF THE FEEDERS, PLEASE PROVIDE DOCUMENTATION FOR SAFE
 LOAD LEVELS. 215.5
  
 2) PLEASE PROVIDE A COST BREAK DOWN OF MATERIALS AND
 LABOR OR A SIGNED CONTRACT WITH THE OWNER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-04 Cont ID  
Sent By jleahy Date 2022-05-04 Time 08:56 Rev Time 0.00
Received By jleahy Date 2022-04-11 Time 08:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-05-04 Cont ID  
Sent By jleahy Date 2022-05-04 Time 08:56 Rev Time 0.00
Received By jleahy Date 2022-05-04 Time 08:56 Sent To  
Notes
***NONE***