Plan Review Details - Permit 22040022
Plan Review Stops For Permit 22040022
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-04-06 Cont ID  
Sent By lcrespo Date 2022-04-06 Time 07:43 Rev Time 0.00
Received By lcrespo Date 2022-04-06 Time 07:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-14 Cont ID  
Sent By lcrespo Date 2022-04-14 Time 08:48 Rev Time 0.00
Received By lcrespo Date 2022-04-14 Time 08:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-13 Cont ID  
Sent By pvalenti Date 2022-04-13 Time 07:43 Rev Time 0.00
Received By pvalenti Date 2022-04-11 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-11 Cont ID  
Sent By aoliver Date 2022-04-11 Time 07:11 Rev Time 0.00
Received By aoliver Date 2022-04-05 Time 07:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-04-06 Cont ID  
Sent By lcrespo Date 2022-04-06 Time 07:43 Rev Time 0.00
Received By lcrespo Date 2022-04-06 Time 07:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-14 Cont ID  
Sent By lcrespo Date 2022-04-14 Time 08:48 Rev Time 0.00
Received By lcrespo Date 2022-04-14 Time 08:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-04-13 Cont ID  
Sent By pvalenti Date 2022-04-13 Time 07:40 Rev Time 0.00
Received By pvalenti Date 2022-04-13 Time 07:37 Sent To  
Notes
2022-04-13 07:43:37PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW DENIED:
  
 PLAN SHEET S-11, SIGNED/SEALED BY A DESIGN PROFESSIONAL
 IS NOT A 3RD PARTY VERIFIABLE DIGITAL SIGNATURE. PLEASE
 SEE NOTES BELOW:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-06 Cont ID  
Sent By lcrespo Date 2022-04-06 Time 07:43 Rev Time 0.00
Received By lcrespo Date 2022-04-06 Time 07:43 Sent To  
Notes
2022-04-06 07:47:0404/06/22 SIGNATURE REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE TIE-DOWN IS NOT ACCEPTABLE;
  
 A. IT REFER TO THE FLORIDA BUILDING CODE 6 TH EDITION
 AND WE ARE USING THE 7 TH EDITION.
  
 B. THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS
 SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE
 DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE
 CODE SEC. 61G15-23.005. YOU MAY GO TO TIE DOWN AND
 PURCHASE AN UPDATED AND SEAL DOCUMENT OR VISIT
 HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY BE ABLE TO
 PROVIDE THIS DOCUMENT.
  
 C. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF THE ORIGINAL SIGNED AND
 SEALED DOCUMENT ALONG WITH A "PLAN REVIEW REQUEST FORM"
 EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT OR
 DRAWINGS. THE PLAN REVIEW REQUEST FORM CAN BE OBTAINED
 BY EMAILING [email protected] AND ASKING FOR THE FORM.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-04-08 Cont ID  
Sent By ckimmerl Date 2022-04-08 Time 10:39 Rev Time 0.00
Received By ckimmerl Date 2022-04-08 Time 10:26 Sent To  
Notes
2022-04-08 10:39:49PROVISOS:
  
 1. EXPOSED PROPANE TANKS ARE NOT PERMITTED, IT MUST BE
 SCREENED FROM VIEW VIA SEC. 94-315 (A.)
 - IF THE PROPANE TANK IS INTERNAL TO THE COFFEE
 ROASTING UNIT, THEN THIS PROVISO DOES NOT APPLY.
  
 2. SEC. 94-305 MECHANICAL EQUIPMENT. MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK.
 - MECHANICAL EQUIPMENT REQUIRES AT LEAST 1 FT. OF
 SEPARATION FROM THE SIDE PROPERTY LINE.
  
  