| 2022-05-17 10:09:35 | 2ND REVIEW FMC |
| | PERMIT: 22031582 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGY CALCULATIONS ARE FOR A NEW FINISHED |
| | BUILDING- WAREHOUSE. THE ENERGY CALCULATIONS DO NOT |
| | SHOW ANY INSULATION VALUES FOR THIS BUILDING I.E. |
| | WALLS, FLOORS, ROOF, DOORS. THIS MUST BE INCLUDED IF |
| | THIS BUILDING IS TO BE CONDITIONED. FEC C402 |
| | |
| | 2) THE PLAN SUBMITTED BY JOHN C. CASSIDY AND THE PLAN |
| | SUBMITTED BY ENERGY HOUSE TECHNOLOGY DO NOT MATCH. THE |
| | ENERGY HOUSE PLAN SHOWS SUPPLY GRILLES IN THE ROOMS IN |
| | FRONT OF THE WAREHOUSE AREAS. IT SHOWS BATHROOMS WITH |
| | NO EXHAUST VENTILATION. THE PLAN SUBMITTED BY JOHN C. |
| | CASSIDY DOES NOT SHOW ANYTHING IN THESE AREAS. THIS IS |
| | A NEW BUILDING, PROVIDE A COMPLETE DESIGN FOR THIS |
| | BUILDING INCLUDING THE OUTDOOR AIR CALCULATIONS AS |
| | DETERMINED BY FMC 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 3) REVISE THE PLAN TO SHOW THE CONDENSING UNITS TIE |
| | DOWN METHOD AND SHOW HOW THE CONDENSING UNITS WILL BE |
| | PROTECTED FROM DAMAGE. FMC 303.4 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |