Plan Review Details - Permit 22031580
Plan Review Stops For Permit 22031580
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2023-02-22 Cont ID  
Sent By cpuell Date 2023-02-22 Time 09:28 Rev Time 0.00
Received By cpuell Date 2023-02-22 Time 09:28 Sent To  
Notes
2023-02-22 09:29:16ADDRESS APPROPRIATE FOR PROJECT.

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2022-12-12 Cont ID  
Sent By cpuell Date 2022-12-12 Time 12:57 Rev Time 0.00
Received By cpuell Date 2022-12-12 Time 12:57 Sent To  
Notes
2022-12-12 12:58:40PAPA HAS CREATED THE WEST AND EAST PARCEL, PLANS DO NOT
 INCIDATE WHIHC PARCEL THIS IS FOR, IS THE SCOPE OF WORK
 FOR THE EAST OR WEST PARCEL. PLEASE CONTACT
 DS_ADDRESSING OR CALL TO DISCUSS ADDRESSING ISSUES

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-11-19 Cont ID  
Sent By cpuell Date 2022-11-19 Time 10:17 Rev Time 0.00
Received By cpuell Date 2022-11-19 Time 10:17 Sent To  
Notes
2022-11-19 10:19:38PROPERTY APPRAISERS HAS CHANGED THE PARCEL NUMBERS, NO
 PARCEL NUMBER IS ASSIGNED TO THE WEST PARCEL, PLEASE
 CONTACT THE PROPERTY APPRAISERS AND FIND OUT WHAT PCNS
 HAVE BEEN ASSIGNED TO WHICH PARCEL. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-05-09 Cont ID  
Sent By cpuell Date 2022-05-09 Time 11:04 Rev Time  
Received By cpuell Date 2022-04-30 Time 10:57 Sent To  
Notes
2022-05-09 11:05:41LOT SPLIT THIS PARCEL HAS A NEW PCN 74434328060250240
 BUT KEEPS THE OLD ADDRESS OF 849 ARDMORE RD
2022-04-30 10:57:50THIS LOT HAS BEEN SPLIT NEED TO ENSURE THAT THE CORRECT
 PARCEL IS ASSIGNED TO THE ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-02-27 Cont ID  
Sent By dbattles Date 2023-02-27 Time 10:28 Rev Time 0.00
Received By dbattles Date 2023-02-27 Time 10:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-12-16 Cont ID  
Sent By jgomez Date 2022-12-16 Time 08:50 Rev Time 0.00
Received By jgomez Date 2022-12-15 Time 16:54 Sent To  
Notes
2022-12-16 08:50:11RESIDENTIAL (R3)ALTERATION THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22031580
 849 ARDMORE RD
  
 PROVISO: NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
  
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
  
 1- OK.
 2- OK.
 3- OK.
 4- OK.
 5- OK.
 6- OK.
 7- OK.
 8- OK.
 9- OK.
 10-OK.
 11-OK.
  
 ORIGINAL COMMENT:
 12- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 DRAWING A102 WAS REVISED TO SHOW OUTSWING DOOR. IT IS
 NOT CLEAR IF THE ENTRY DOOR IS THE SAME TYPE AS THE
 FRENCH DOORS TYPE SHOWN ON THE BEDROOM #3 AND KITCHEN
 AREAS.
 DOORS PRODUCT APPROVALS UPLOADED TO PROJECTDOX DON'T
 HAVE THE REVIEW STAMP OF THE DESIGNER OF RECORD. IT IS
 VERY CONFUSING TO KNOW WHICH ARE THE PRODUCT APPROVALS
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE STAMP THE
 REVIEW STAMP ON ALL PRODUCT APPROVALS AND CLEARLY
 SPECIFY IF ENTRY DOOR OR REAR FRENCH DOORS TO AVOID
 MORE CONFLICT/CONFUSION.
 NOTE: PLEASE COORDINATE WITH THE PERMIT LIBRARIAN TO
 SEE WHAT PRODUCT APPROVALS NEED TO BE REMOVED TO AVOID
 MORE CONFLICTS/DELAYS.
  
  
 B)REAR FRENCH DOORS.
  
 RESPONSE:
 PLEASE COORDINATE WITH ITEM ABOVE TO AVOID MORE
 CONFLICTS/DELAYS.
  
 E)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
  
 RESPONSE:
 NEED TO SPECIFY MULLION SIZES, INCLUDING MULLIONS AT
 THE BAY WINDOWS.
  
 ORIGINAL COMMENT:
 H) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 FASTENING OPTION #2 SELECTED ON PAGE 53 NOA 18-0919.12
 CANNOT BE USED. THIS ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9. THIS LIMITATION DOESN'T ALLOW NAIL
 ENHANCEMENT. SEE GENERAL LIMITATION #9 ON LAST PAGE OF
 NOA.
  
 NOTE: ENGINEER NEEDS TO REVISE RAS 117 CALCULATIONS.
 SEE COMMENT ABOVE.
 AND NEEDS TO REFERENCE THE SPECIFIC FASTENING OPTION
 FROM NOA 18-0919.12.
  
 ORIGINAL COMMENT:
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 COORDINATE ALL PRODUCT APPROVALS WITH CONTRACTOR. SEE
 COMMENT 12(A) ABOVE.
  
  
 14-OK.
 15-OK.
 16-OK.
 17-OK.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-11-16 Cont ID  
Sent By jgomez Date 2022-11-16 Time 14:24 Rev Time 0.00
Received By jgomez Date 2022-11-15 Time 16:41 Sent To  
Notes
2022-11-02 17:22:38RESIDENTIAL (R3)ALTERATION SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22031580
 849 ARDMORE RD
  
 ORIGINAL COMMENT:
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 AND ENGINEERS OF RECORD. ALL DRAWINGS NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER
 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 RESPONSE:
 NEED DRAWINGS WITH VERIFIABLE DIGITAL SIGNATURE. SEE
 SIGNATURE REVIEW COMMENTS.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2- OK.
 3- OK.
  
 ORIGINAL COMMENT:
 4- REFLECTED CEILING PLAN ON SHEET A103 SHOWS PROPOSED
 BEDROOM #1 WITH A CEILING HEIGHT OF 6'8". THIS ROOM
 DOESN'T COMPLY WITH THE MINIMUM CEILING HEIGHT OF 7'-0"
 REQUIRED FOR HABITABLE ROOMS. THEREFORE, THIS ROOM
 CANNOT BE USED AS A HABITABLE ROOM. SEC. R305.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 CEILING HEIGHT DIMENSIONS ON SHEET A103 ARE NOT CLEAR.
 A CEILING HEIGHT IS TAKEN FROM FINISH FLOOR TO CEILING.
 CEILING HEIGHT AT HEADER AND CEILING HEIGHT AT HEAD
 HEIGHT DON'T SPECIFY THE ACTUAL CEILING HEIGHT OF THE
 ROOM. BASED ON DRAWING SUBMITTED AND PICTURES ON THE
 WEBSITE WHEN THE HOUSE WAS FOR SALE, THIS IS A
 CONTINUOUS CEILING. BASED ON THE PICTURES, IT LOOKS
 LIKE THE SLOPED CEILING IS TOO SLOW TO BE CONSIDERED A
 HABITABLE ROOM. ONLY THE AREAS COMPLYING WITH THE
 MINIMUM CEILING HEIGHT AND HORIZONTAL DIMENSIONS ARE
 CONSIDERED FOR THE ROOM TO BE CONSIDERED AS BEDROOM.
 PROVIDE COMPLETE CROSS SECTION OF THIS BEDROOM WITH
 DIMENSIONS SHOWING COMPLIANCE WITH THE MINIMUM AREAS OF
 SEC. R304.1, SEC. R304.2 AND R304.3 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 5- NONE OF THE WINDOWS OF PROPOSED BEDROOM #1 COMPLY
 WITH THE BEDROOMS EMERGENCY ESCAPE SEC. R310.2.1
 FBC-RESIDENTIAL (NOTE: COORDINATE WITH ITEM #4 ABOVE).
 ALSO, SPECIFY TYPE AND SIZE OF EXISTING WINDOWS TO BE
 REPLACED ON PROPOSED BEDROOM #2 AND TYPE AND SIZE OF
 PROPOSED WINDOWS TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH EGRESS REQUIREMENTS. SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 RESPONSE:
 SINGLE HUNG WINDOW W5 (4'-2" X 5'-0") DOESN'T SEEM TO
 COMPLY WITH THE MINIMUM CLEAR HEIGHT OPENING
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. REVISE
 AS REQUIRED OR PROVIDE MANUFACTURER'S SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE EGRESS HEIGHT REQUIREMENTS.
 NOTE: TYPICALLY, 63" HIGH SINGLE HUNG WINDOWS ARE THE
 ONES THAT PROVIDE THE 24" CLEAR HEIGHT OPENING. VERIFY
 WITH MANUFACTURER.
  
 ORIGINAL COMMENT:
 6- SHEET S1: SPECIFY PROTECTION AGAINST WOOD DECAY FOR
 THE FLOOR JOISTS OF THE COVERED DECK AS REQUIRED BY
 SEC. R37 FBC-RESIDENTIAL.
  
 RESPONSE:
 PARTIALLY DONE. ENGINEER IS SPECIFYING PRESSURE TREATED
 WOOD JOISTS FOR PERIMETER BEAMS BUT THERE ARE NO
 SPECIFICATIONS FOR THE INTERIOR FLOOR JOISTS OF THE
 DECK.
  
 7- SHEET S3:
 A) OK.
  
 ORIGINAL COMMENT:
 B)COMPONENTS AND CLADDING DESIGN PRESSURES ARE TOO LOW
 BASED ON SPECIFIED BUILDING EXPOSURE AND HEIGHT, DOORS
 AND WINDOWS ARE LOW. REVISE AS REQUIRED OR PROVIDE
 ACTUAL CALCULATIONS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 DESIGN PRESSURES SHOWN ON SHEET S1 ARE TOO LOW FOR
 WINDOWS LOCATED IN THE END ZONE. ENGINEER TO REVIEW
 REVISED DRAWING A102 FOR CORRECT WINDOW SIZES. ALSO,
 THE HEIGHT FOR THIS BUILDING IS NOT 10 FEET. SEE
 ELEVATIONS AND REVISE CALCULATIONS AS REQUIRED.
 NOTE: THERE ARE THREE WINDOWS IN THE BAY AREA OF
 BEDROOM #1, NOT JUST ONE WINDOW.
  
 8- OK.
 9- OK.
 10-OK.
 11-OK.
  
 ORIGINAL COMMENT:
 12- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES THAT DRAWING A102
 WAS REVISED TO SHOW OUTSWING DOOR. DRAWING A102 WAS NOT
 REVISED. CLARIFY IF USING SAME NOA 19-0918.03 FOR ENTRY
 DOOR AND COVERED DECK DOORS.
  
 B)FRENCH DOORS.
 RESPONSE: OK IF USING SAME NOA 19-0918.03.
  
 C)OK.
 D)OK.
  
 E)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 RESPONSE:
 MULLION SIZE WAS NOT SPECIFIED AND NOA 20-1118.13
 SUBMITTED DOESN'T SHOW MULLION FOR BAY WINDOWS ON
 BEDROOM #1. PROVIDE PRODUCT APPROVAL FOR CORNER
 MULLIONS OR PROVIDE COMPLETE STRUCTURAL MULLION
 DETAIL/SPECIFICATIONS FOR THE BAY WINDOWS AS SHOWN ON
 PLANS.
  
 F)OK.
 G)OK.
  
 H) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 NOA 18-0919.12 DOESN'T SPECIFY WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED AND NEED TO PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA.
 NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CANNOT BE
 USED. SEE GENERAL LIMITATION #9 ON LAST PAGE OF NOA.
  
 NEW PRODUCT APPROVAL REQUIRED:
 I) HORIZONTAL SLIDER WINDOW SPECIFIED ON REVISED PLANS.
  
 ORIGINAL COMMENT:
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 A)FLAT ROOF PRODUCT APPROVAL WAS NOT REVIEWED/APPROVED.
  
 B)GUARDRAIL ICC EVALUATION REPORT ESR-4945 SUBMITTED
 WAS NOT REVIEWED/APPROVED.
  
 ORIGINAL COMMENT:
 14- HANDRAILS AND HANDRAILS: DESIGNER OF RECORD NEEDS
 TO PROVIDE THE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE HANDRAILS AND GUARDRAILS AS
 REQUIRED BY TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 RESPONSE:
 THE FIBERON INSTALLATION INSTRUCTIONS SUBMITTED DON'T
 CORRESPOND TO FIBERON ICC EVALUATION REPORT ESR-4945
 SUBMITTED. THESE ARE TWO DIFFERENT RAILINGS SYSTEMS.
 SUBMIT ONLY THE ICC EVALUATION REPORT AND DESIGNER OF
 RECORD TO REVIEW/APPROVE IT.
  
 15-OK.
 16-OK.
  
 17- HARD COPY OF STRUCTURAL CALCULATIONS SUBMITTED HAVE
 A COPY OF THE ENGINEER'S DIGITAL SIGNATURE. DIGITAL
 SIGNATURES ARE NOT ALLOWED TO BE PRINTED. ALL DOCUMENTS
 PREPARED BY A LICENSED ENGINEER NEED TO HAVE THE
 ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF RECORD
 AS REQUIRED BY SEC. 61G15-23.004 FAC AND CHAPTER 471
 F.S.
 NOTE: SUBMIT CALCULATIONS ELECTRONICALLY WITH DIGITAL
 SIGNATURE
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By jgomez Date 2022-07-22 Time 17:12 Rev Time 0.00
Received By jgomez Date 2022-07-22 Time 13:17 Sent To  
Notes
2022-07-22 17:12:16RESIDENTIAL (R3)ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22031580 849 ARDMORE RD
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 AND ENGINEERS OF RECORD. ALL DRAWINGS NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER
 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE
  
 2- ALL PLANS UPLOADED TO PROJECTDOX FOR REVIEW ARE NOT
 LEGIBLE. NEED TO UPLOAD LEGIBLE DRAWINGS. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 3- BASED ON PLANS SUBMITTED, THIS IS ALTERATION LEVEL 3
 NOT LEVEL 2. ARCHITECT TO REVISE DESCRIPTION OF WORK ON
 SHEET G001. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE.
 SEC. 604 FBC-EXISTING BUILDING.
  
 4- REFLECTED CEILING PLAN ON SHEET A103 SHOWS PROPOSED
 BEDROOM #1 WITH A CEILING HEIGHT OF 6'8". THIS ROOM
 DOESN'T COMPLY WITH THE MINIMUM CEILING HEIGHT OF 7'-0"
 REQUIRED FOR HABITABLE ROOMS. THEREFORE, THIS ROOM CAN
 NOT BE USED AS A HABITABLE ROOM. SEC. R305.1
 FBC-RESIDENTIAL.
  
 5- NONE OF THE WINDOWS OF PROPOSED BEDROOM #1 COMPLY
 WITH THE BEDROOMS EMERGENCY ESCAPE SEC. R310.2.1
 FBC-RESIDENTIAL (NOTE: COORDINATE WITH ITEM #4 ABOVE).
 ALSO, SPECIFY TYPE AND SIZE OF EXISTING WINDOWS TO BE
 REPLACED ON PROPOSED BEDROOM #2 AND TYPE AND SIZE OF
 PROPOSED WINDOWS TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH EGRESS REQUIREMENTS. SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 6- SHEET S1: SPECIFY PROTECTION AGAINST WOOD DECAY FOR
 THE FLOOR JOISTS OF THE COVERED DECK AS REQUIRED BY
 SEC. R37 FBC-RESIDENTIAL.
  
 7- SHEET S3:
 A)REVISE "PROJECT SPECIFIC CODES USED", GRAVITY LOADING
 AND WIND LOADING. . CURRENT CODE IS THE 2020
 FBC-RESIDENTIAL NOT 2017. REVISE ALL THE INFORMATION
 ACCORDINGLY, INCLUDING CURRENT ASCE.
 SEC. 553 FLORIDA STATUTES.
  
 B)COMPONENTS AND CLADDING DESIGN PRESSURES ARE TOO LOW
 BASED ON SPECIFIED BUILDING EXPOSURE AND HEIGHT, DOORS
 AND WINDOWS ARE LOW. REVISE AS REQUIRED OR PROVIDE
 ACTUAL CALCULATIONS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 8- DETAIL 15/S2: WIND PRESSURES ARE TOO LOW BASED ON
 SPECIFIED BUILDING EXPOSURE AND HEIGHT. REVISE AS
 REQUIRED OR PROVIDE ACTUAL CALCULATIONS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 9- SPECIFY ROOF SHEATHING NAILING SPECIFICATIONS
 SHOWING COMPLIANCE WITH NEW 2020 FBC-RESIDENTIAL
 SPECIFICATIONS. SPECIFY NAIL TYPE, SIZE AND SPACING.
 NEED TO USE RING SHANK NAILS.
 SEC. R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH SPECIFICATIONS SHOWN ON EXTERIOR
 ELEVATIONS SHEET A201, A202, A203 AND SECTION A ON
 SHEETS A301 TO AVOID CONFLICTS.
  
 10- WALL SECTIONS: NEED TO SPECIFY TWO WATER RESISTIVE
 BARRIERS WHEN STUCCO IS APPLIED TO WOOD AS REQUIRED BY
 SEC. R703.7.3 FBC-RESIDENTIAL.
  
 11- ROOFING UNDERLAYMENT
 PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE
 NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT.
 SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001
  
 12- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
 B)FRENCH DOORS.
 C)SINGLE HUNG WINDOWS.
 D)FIXED WINDOWS AS SPECIFIED ON WINDOW SCHEDULE. (NOTE:
 CLARIFY WHY ELEVATIONS DON'T SHOW FIXED WINDOWS).
 E)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 F)ROOF SHINGLES.
 G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 H) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- HANDRAILS AND HANDRAILS: DESIGNER OF RECORD NEEDS
 TO PROVIDE THE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE HANDRAILS AND GUARDRAILS AS
 REQUIRED BY TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 15-REVISE WINDOWS AND DOORS STRUCTURAL BUCK DETAILS
 SHOWN ON SHEET A501.
 STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO THE
 DOOR/WINDOW FRAME AND NEED TO EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME AS REQUIRED
 BY SEC. R609.7.2.1 FBC-RESIDENTIAL. ALSO, BEVELED BUCKS
 ARE NOT ALLOWED ANYMORE.
  
 16- VALUATION WAS REVISED TO REFLECT VALUE STATED ON
 THE COPY OF THE CONTRACT SUBMITTED ($172,868.75).
 DEDUCTED THE PERMIT FEE OF $6,800 FROM CONTRACT VALUE.
 TOTAL VALUE USED $166,068). THE PERMIT FEE BALANCE IS
 $3503.81.
 SEC. 109.3 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-12-15 Cont ID  
Sent By fgiaquin Date 2022-12-15 Time 19:11 Rev Time 0.00
Received By fgiaquin Date 2022-12-15 Time 19:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-21 Cont ID  
Sent By fgiaquin Date 2022-10-21 Time 19:29 Rev Time 0.00
Received By fgiaquin Date 2022-10-20 Time 23:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-02 Cont ID  
Sent By fgiaquin Date 2022-06-02 Time 21:55 Rev Time 0.00
Received By fgiaquin Date 2022-06-02 Time 20:40 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-03-24 Cont ID  
Sent By amhamilt Date 2023-03-24 Time 14:49 Rev Time 0.00
Received By amhamilt Date 2023-03-24 Time 14:49 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2022-11-22 Cont ID  
Sent By amhamilt Date 2022-11-22 Time 15:51 Rev Time 0.00
Received By amhamilt Date 2022-11-22 Time 15:53 Sent To  
Notes
2022-11-22 15:55:24THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PROPOSED HORIZONTAL SLIDER WINDOW NOT APPROPRIATE FOR
 HISTORIC DISTRICT, PLEASE REVISE TO EITHER SINGLE HUNG
 OR CASEMENT WINDOWS
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-06-03 Cont ID  
Sent By amhamilt Date 2022-06-03 Time 11:18 Rev Time 0.00
Received By amhamilt Date 2022-06-03 Time 11:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-02-27 Cont ID  
Sent By dbattles Date 2023-02-27 Time 10:28 Rev Time 0.00
Received By dbattles Date 2023-02-27 Time 10:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-16 Cont ID  
Sent By jgomez Date 2022-12-16 Time 09:01 Rev Time 0.00
Received By jgomez Date 2022-11-21 Time 11:12 Sent To I
Notes
2022-12-13 11:19:3112/13/22 OPENED INCOMING STOP BECAUSE NEW DRAWINGS WERE
 UPLOADED TO PROJECTDOX ON 11/21/22 AND WERE NOT
 REVIEWED BY BUILDING, ELECTRICAL, MECHANICAL AND
 PLUMBING. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-28 Cont ID  
Sent By lmarchan Date 2022-11-28 Time 09:21 Rev Time 0.00
Received By lmarchan Date 2022-10-18 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-22 Cont ID  
Sent By jgomez Date 2022-07-22 Time 17:22 Rev Time 0.00
Received By jgomez Date 2022-05-17 Time 08:26 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2023-02-06 Cont ID  
Sent By dbattles Date 2023-02-06 Time 14:20 Rev Time 0.00
Received By dbattles Date 2023-02-06 Time 14:20 Sent To  
Notes
2023-02-06 14:21:38THIS PERMIT IS REMODEL AND COVERED PATIO.
 NO IMPACT REVIEW REQUIRED.
  
 THE OTHER STRUCTURE WAS SENT TO IMPACT REVIEW UNDER
 PERMIT 22010353

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-12-16 Cont ID  
Sent By jgomez Date 2022-12-16 Time 08:55 Rev Time 0.00
Received By jgomez Date 2022-12-16 Time 08:54 Sent To  
Notes
2022-12-16 08:55:18IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-11-16 Cont ID  
Sent By jgomez Date 2022-11-16 Time 14:58 Rev Time 0.00
Received By jgomez Date 2022-11-16 Time 14:55 Sent To  
Notes
2022-11-16 14:58:29IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-12-14 Cont ID  
Sent By medwards Date 2022-12-14 Time 07:21 Rev Time 0.00
Received By medwards Date 2022-12-14 Time 07:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-10-31 Cont ID  
Sent By medwards Date 2022-10-31 Time 08:19 Rev Time 0.00
Received By medwards Date 2022-10-31 Time 08:19 Sent To  
Notes
2022-10-31 08:20:24THE DESIGNER OF SHEET M101 MUST PRINT AND SIGN THEIR
 NAME ON THE DRAWING. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-24 Cont ID  
Sent By medwards Date 2022-05-24 Time 09:21 Rev Time 0.00
Received By medwards Date 2022-05-24 Time 09:20 Sent To  
Notes
2022-05-24 09:26:14THE CONTRACT STATES A VALUE $100,0000,00. HIGHER THAN
 THE VALUE LISTED ON THE APPLICATION. SUBMIT A NEW
 APPLICATION WITH THE CORRECTED VALUE. $172,868.75
  
 THE DRAWINGS ARE VERY BLURRY WHEN MAGNIFIED TO SEE,
 PLEASE SUBMIT ORIGINAL SIGNED AND SEALED DOCUMENTS. FBC
 107.2.1
  
 PROVIDE A COMPLETE DESIGN FOR THE MECHANICAL SYSTEMS
 FOR THIS PROJECT INCLUDING DRAWINGS, ENERGY
 CALCULATIONS, MECHANICAL SIZING CALCULATIONS. FBC
 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-12-14 Cont ID  
Sent By rwbrown Date 2022-12-14 Time 07:33 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-10-19 Cont ID  
Sent By rwbrown Date 2022-10-19 Time 14:22 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-05-21 Cont ID  
Sent By rwbrown Date 2022-05-21 Time 08:47 Rev Time 0.00
Received By rwbrown Date 2022-05-21 Time 08:34 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2023-03-24 Cont ID  
Sent By dbattles Date 2023-03-24 Time 13:34 Rev Time 0.00
Received By dbattles Date 2023-03-24 Time 13:34 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2022-12-16 Cont ID  
Sent By jgomez Date 2022-12-16 Time 08:55 Rev Time 0.00
Received By jgomez Date 2022-12-16 Time 08:55 Sent To  
Notes
2022-12-16 08:55:57ROOFING REVIEW
  
 ORIGINAL COMMENT:
 1) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 FASTENING OPTION #2 SELECTED ON PAGE 53 NOA 18-0919.12
 CANNOT BE USED. THIS ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9. THIS LIMITATION DOESN'T ALLOW NAIL
 ENHANCEMENT. SEE GENERAL LIMITATION #9 ON LAST PAGE OF
 NOA.
  
 NOTE: ENGINEER NEEDS TO REVISE RAS 117 CALCULATIONS.
 SEE COMMENT ABOVE.
 AND NEEDS TO REFERENCE THE SPECIFIC FASTENING OPTION
 FROM NOA 18-0919.12.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-11-16 Cont ID  
Sent By jgomez Date 2022-11-16 Time 14:26 Rev Time 0.00
Received By jgomez Date 2022-11-16 Time 14:25 Sent To  
Notes
2022-11-16 14:26:04ROOFING REVIEW
  
 ORIGINAL COMMENT:
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A) OK.
 B) OK.
  
 C)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 NOA 18-0919.12 DOESN'T SPECIFY WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED AND NEED TO PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA.
 NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CANNOT BE
 USED. SEE GENERAL LIMITATION #9 ON LAST PAGE OF NOA.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By jgomez Date 2022-07-22 Time 17:24 Rev Time 0.00
Received By jgomez Date 2022-07-22 Time 17:23 Sent To  
Notes
2022-07-22 17:25:36ROOFING REVIEW
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES.
 B)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 C) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 2-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-16 Cont ID  
Sent By jgomez Date 2022-12-16 Time 09:01 Rev Time 0.00
Received By jgomez Date 2022-12-16 Time 09:01 Sent To  
Notes
2022-12-14 07:22:34MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-10-18 Cont ID  
Sent By mpeterso Date 2022-10-18 Time 13:45 Rev Time 0.00
Received By mpeterso Date 2022-10-18 Time 13:45 Sent To  
Notes
2022-10-18 13:48:20SIGNATURE REVIEW OF PAPER PLANS FAILED 22031580
 1) MECHANICAL SHEET M101 DOES NOT DETAIL THE REQUIRED
 SEAL AND SIGNATURE
 2) STRUCTURAL, ELECTRICAL, AND PLUMBING SHEETS APPEAR
 TO BE COPIES OF AN ENGINEERS DIGITAL SIGNATURE
 3) G AND A SHEETS HAVE THE CORRECT WET SIGNATURE AND
 SEAL
  
 PLEASE CORRECT AS OUTLINED BELOW
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
  
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 06:58 Rev Time 0.00
Received By shill Date 2022-07-18 Time 06:58 Sent To  
Notes
2022-07-18 07:00:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. FS481, THE PAGES UPLOADED ARE NOT DIGITALLY
 SIGNED.
  
 IF THE ARCHITECT DOES NOT HAVE A DIGITAL SIGNATURE,
 PLEASE ASK HIM TO EMAIL [email protected] FOR ASSISTANCE.
  
 PLEASE UPLOAD INDIVIDUALLY DIGITALLY SIGNED PAGES.
  
 2. FBC 107, SOMEONE UPLOADED A SINGLE MULTIPAGE PDF TO
 THE SIGNATURE FOLDER. THIS DOCUMENT IS FOR STAFF USE
 ONLY, AND THIS DOCUMENT IS NOT DIGITALLY SIGNED. THIS
 DOCUMENT WILL BE DELETED.
  
 3. FBC 107, IT APPEARS THAT SCANNED DOCUMENTS WERE
 UPLOADED. PLEASE UPLOAD DIGITALLY SIGNED PDFS DIRECTLY
 FROM THE ARCHITECT AS THIS AFFECTS OUR ABILITY TO
 PERFORM AN EFFICIENT PLAN REVIEW, DIGITALLY VERSION
 RESUBMITTALS AND REVISIONS.
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2023-03-24 Cont ID  
Sent By amhamilt Date 2023-03-24 Time 14:44 Rev Time 0.00
Received By amhamilt Date 2023-03-24 Time 14:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-11-22 Cont ID  
Sent By amhamilt Date 2022-11-22 Time 15:46 Rev Time 0.00
Received By amhamilt Date 2022-11-22 Time 15:46 Sent To  
Notes
2022-11-22 15:46:44THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 THE VALUE OF CONSTRUCTION EXCEEDS 50% OF THE
 IMPROVEMENT VALUE OF THE STRUCTURE, THEREFORE A
 SEPERATE LANDSCAPE PERMIT IS REQUIRED AND MUST BE
 SUBMITTED FOR ZONING APPROVAL TO MOVE FORWARD
  
 SEC 94-441 (B)
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-06-03 Cont ID  
Sent By ahamilto Date 2022-06-03 Time 11:18 Rev Time 0.00
Received By amhamilt Date 2022-06-03 Time 11:18 Sent To  
Notes
***NONE***