| 2022-04-15 15:52:01 | 1ST REVIEW FMC |
| | PERMIT: 22031507 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE REVISE THE VALUE OF WORK ON THE REVISION |
| | REQUEST FORM AS THIS WORK WAS NOT INCLUDED UNDER THE |
| | MAIN PERMIT. |
| | |
| | 2) THE RETURN AIR SHALL NOT BE FROM A CLOSET. |
| | |
| | FRC M1602.2 RETURN AIR OPENINGS. RETURN AIR OPENINGS |
| | FOR HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS |
| | SHALL COMPLY WITH ALL OF THE FOLLOWING: 4. RETURN AIR |
| | SHALL NOT BE TAKEN FROM A CLOSET, BATHROOM, |
| | TOILET ROOM, KITCHEN, GARAGE, MECHANICAL ROOM, BOILER |
| | ROOM, FURNACE ROOM OR UNCONDITIONED ATTIC. |
| | |
| | 3) SHOW THE ANCHORAGE DETAIL OF THE OUTDOOR CONDENSING |
| | UNIT. |
| | M1307.2 ANCHORAGE OF APPLIANCES. APPLIANCES DESIGNED TO |
| | BE FIXED IN POSITION SHALL BE FASTENED OR ANCHORED IN |
| | AN APPROVED MANNER. IN SEISMIC DESIGN CATEGORIES D0, D1 |
| | AND D2, AND IN TOWNHOUSES IN SEISMIC DESIGN CATEGORY C, |
| | WATER HEATERS AND THERMAL STORAGE UNITS SHALL BE |
| | ANCHORED OR STRAPPED TO RESIST HORIZONTAL DISPLACEMENT |
| | CAUSED BY EARTHQUAKE MOTION IN ACCORDANCE WITH ONE OF |
| | THE FOLLOWING: |
| | 1. ANCHORAGE AND STRAPPING SHALL BE DESIGNED TO RESIST |
| | A HORIZONTAL FORCE EQUAL TO ONE-THIRD OF THE OPERATING |
| | WEIGHT OF THE WATER HEATER STORAGE TANK, ACTING IN ANY |
| | HORIZONTAL DIRECTION. STRAPPING SHALL BE AT POINTS |
| | WITHIN THE UPPER ONE-THIRD AND LOVER ONE-THIRD OF THE |
| | APPLIANCE?S VERTICAL DIMENSIONS. AT THE LOWER POINT, |
| | THE STRAPPING SHALL MAINTAIN A MINIMUM DISTANCE OF 4 |
| | INCHES (102 MM) ABOVE THE CONTROLS. |
| | 2. THE ANCHORAGE STRAPPING SHALL BE IN ACCORDANCE WITH |
| | THE APPLIANCE MANUFACTURER?S RECOMMENDATIONS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |