| 2022-03-29 10:48:40 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL16709-R8 HAS BEEN REVISED TO FL16709-R9. |
| | PLEASE PROVIDE A COMPLETE SET OF PRODUCT APPROVALS. |
| | INCLUDE COVER PAGE, EVALUATION REPORT PAGES 1-4 AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL16709-R8 SELECTED SYSTEM NO W-5; EXPOSURE |
| | (B); ENCLOSURE (OPEN); ROOF HEIGHT (H < 15); ULTIMATE |
| | WIND SPEED 180 IS NOT CORRECT. THE CORRECT EXPOSURE |
| | CATEGORY FOR THE LISTED ADDRESS IS EXPOSURE C, PAPA |
| | LIST THIS AREA AS ENCLOSED AND THE CORRECT WIND SPEED |
| | IS 170 MPH. SELECT THE CORRECT OPTIONS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |