Plan Review Details - Permit 22031330
Plan Review Stops For Permit 22031330
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-05-11 Cont ID  
Sent By rmcdouga Date 2022-05-11 Time 17:46 Rev Time 0.00
Received By rmcdouga Date 2022-05-11 Time 17:46 Sent To  
Notes
2022-05-11 17:49:15FBC-R4501.19 FINAL ELECTRICAL AND BARRIER CODE
 INSPECTION SHALL BE COMPLETED PRIOR TO FILLING THE POOL
 WITH WATER.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-26 Cont ID  
Sent By ppetty Date 2022-07-26 Time 08:27 Rev Time 0.00
Received By ppetty Date 2022-07-26 Time 08:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-25 Cont ID  
Sent By ppetty Date 2022-04-25 Time 08:33 Rev Time 0.00
Received By ppetty Date 2022-04-25 Time 08:24 Sent To  
Notes
2022-04-25 08:36:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-26 Cont ID  
Sent By ppetty Date 2022-07-26 Time 08:27 Rev Time 0.00
Received By ppetty Date 2022-07-14 Time 15:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-11 Cont ID  
Sent By rmcdouga Date 2022-05-11 Time 17:46 Rev Time 0.00
Received By rmcdouga Date 2022-03-31 Time 15:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-07-20 Cont ID  
Sent By ccole Date 2022-07-20 Time 10:15 Rev Time 0.00
Received By ccole Date 2022-07-20 Time 10:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-12 Cont ID  
Sent By ccole Date 2022-04-12 Time 09:32 Rev Time 0.00
Received By ccole Date 2022-04-12 Time 09:32 Sent To  
Notes
2022-04-12 09:41:461ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22031330
 4/12/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4/P-1: THE SUBMITTED PUMP SPECS FOR THE
 VSFLOPRO2.7 HP DO NOT MATCH THE PUMP SPECIFIED ON THE
 PLAN- VSFHP165JEP 1.65 THP. PLEASE SUBMIT THE CORRECT
 PUMP SPECS.
  
 2) SUBMIT THE AQUASTAR 32-INCH CHANNEL DRAIN SPECS-
 SEC. R4501.6.6 FBC RES.
  
 3) INDICATE HOW WATER WILL BE SUPPLIED TO THE POOL-
 SEC. R4501.9. PLEASE NOTE THAT BACKFLOW PREVENTION IS
 REQUIRED FOR WATER BEING SUPPLIED FROM THE MAIN HOUSE
 SYSTEM. A BACKFLOW ASSEMBLY IS ALSO REQUIRED AT THE
 WATER METER AND SHALL BE INSTALLED UNDER A SEPARATE
 PERMIT- SEC. 105.1 WPB.
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN
 SEPARATE PERMITS FOR INSTALLATION OF THE BACKFLOW
 PREVENTERS IN ACCORDANCE WITH SECTION 105.1WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICES SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-25 Cont ID  
Sent By ppetty Date 2022-04-25 Time 08:37 Rev Time 0.00
Received By ppetty Date 2022-04-25 Time 08:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-04-20 Cont ID  
Sent By asangele Date 2022-04-20 Time 10:21 Rev Time 0.00
Received By asangele Date 2022-04-20 Time 10:21 Sent To  
Notes
2022-04-20 10:23:144/20/2022
 POOL BARRIER REQUIRED