Plan Review Details - Permit 22031215
| Plan Review Stops For Permit 22031215 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-05-23 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-05-23 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-05-23 |
Time |
07:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-05-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-05-20 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-05-20 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2022-05-20 13:15:33 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, PLEASE PROVIDE A FLOOR PLAN OF INTERIOR | | | INDICATING WHICH AREAS ARE RECEIVING THE NEW FLOORING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-18 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-04-18 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-04-18 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2022-04-18 15:19:46 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, PROVIDE A FLOOR PLAN SKETCH SHOWING | | | THE AREAS FOR NEW FLOORING. | | | | | | 2.) PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-05-23 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-05-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2022-05-03 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-05-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-05-03 09:55:45 | FIRE REVIEW COMMENTS: | | | PROVIDE A FLOOR PLAN INDICATING THE AREA OF NEW | | | FLOORING TO BE INSTALLED. | | | NFPA 1, 1.14 | | | C. WALKER | | | 561-804-4762 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-03-31 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-03-31 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-03-31 14:09:21 | FIRE COMMENTS: | | | THE SUBMITTAL SHALL INCLUDE A FLOOR PLAN INDICATING THE | | | AREA AND SCOPE OF WORK TO BE PERFORMED. | | | NFPA 1, 1.14 | | | THE SUBMITTAL SHALL INCLUDE THE FIRE PERFORMANCE OF THE | | | PROPOSED NEW FLOOR TO BE INSTALLED INCLUDING THE | | | CRITICAL RADIANT FLUX OF THE MATERIAL. | | | NFPA 101, 10.2.7 | | | FIRE REVIEW PERFORMED BY: | | | C.R. WALKER, SENIOR FIRE INSPECTOR | | | 561-804-4762 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-05-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-05-24 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-05-22 |
Time |
10:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-05-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-05-20 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-05-02 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-04-18 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-04-18 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-03-30 |
Time |
09:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-04-18 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-04-18 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-04-18 |
Time |
15:03 |
Sent To |
|
|
| Notes |
|
|
|