| Plan Review Stops For Permit 22031166 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-03-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-03-31 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-03-31 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2022-03-31 12:00:47 | ADDRESS HAD PREVIOUSLY BEEN ASSIGNED TO THIS BUILDING | | | AS 221 PERSHING WAY, UPDATED PERMIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-05-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-05-23 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-05-23 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2022-05-23 13:34:42 | BUILDING REVIEW APPROVED WITH PROVISO | | | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO | | | INSTALLATION/INSPECTIONS TO AVOID CONFLICTS/DELAYS): | | | | | | 1- PROVIDE COMPLETE FRAMING DETAILS/SPECS FOR ELEVATOR | | | SHAFT. SPECIFY ALL FRAMING MEMBERS/CONNECTORS, | | | INCLUDING BRACING TO SUPPORT THE ELEVATOR. (MAIN HOUSE) | | | 2- PROVIDE COMPLETE DETAILS/SPECS FOR BALCONIES CLAY | | | TILE RAILING. SPECIFY ALL FRAMING MEMBERS/CONNECTORS | | | AND CLAY TILE INSTALLATION.(MAIN HOUSE) | | | 3- PROVIDE COMPLETE DETAILS/SPECS FOR CANOPIES. SPECIFY | | | ALL FRAMING MEMBERS/CONNECTORS. | | | 4- PROVIDE COMPLETE FRAMING DETAILS/SPECS FOR TRELLIS | | | PERGOLA. SPECIFY ALL FRAMING MEMBERS/CONNECTORS. (MAIN | | | HOUSE) | | | 5- DESIGNER OF RECORD TO DEPICT THE BUILDING THERMAL | | | ENVELOPE. SPECIFY INSULATION R-VALUES. SEC. R103.2 | | | FBC-ENERGY CONSERVATION. | | | 6- REVISE ENERGY CALCULATIONS MAIN HOUSE. | | | A)PROVIDE INFORMATION: OWNER, BUILDER, PERMIT OFFICE & | | | JURISDICTION (JURISDICTION 604700).SEC. R101.5.1.1.2 | | | FBC- ENERGY CONSERVATION. | | | B)WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH | | | PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC- | | | ENERGY CONSERVATION. | | | C)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL | | | (EPL) DISPLAY CARD FOR EACH BUILDING. SEC. R405.4.3 | | | FBC-ENERGY CONSERVATION. | | | 7- REVISE ENERGY CALCULATIONS GUEST HOUSE. | | | A)PROVIDE INFORMATION: OWNER, BUILDER, PERMIT OFFICE & | | | JURISDICTION (JURISDICTION 604700).SEC. R101.5.1.1.2 | | | FBC- ENERGY CONSERVATION. B)REVISE FLOOR TYPES | | | INFORMATION. THE RAISED FLOOR IS THE GUEST SUITE. | | | REVISE AS REQUIRED. FLOOR AREAS ABOVE UNCONDITIONED | | | SPACE NEED TO HAVE INSULATION. SEC. R101.5.1.1.2 FBC- | | | ENERGY CONSERVATION. | | | C)REVISE SPACES INFORMATION. THERE IS NOT KITCHEN IN | | | THE GUEST SUITE. | | | D)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL | | | (EPL) DISPLAY CARD FOR EACH BUILDING. SEC. R405.4.3 | | | FBC-ENERGY CONSERVATION. | | | 8- REVISE LOT DRAINAGE PLAN: DETAIL SECTIONS A-A, B-B | | | AND C-C SHOW WATER RUNNING TO THE NEIGHBOR'S PROPERTY. | | | ALSO, PROVIDE INFORMATION SHOWING DRAINAGE ON THE EAST | | | SIDE OF POOL DECK. | | | 9- PROVIDE SURVEY SHOWING PROPOSED BUILDINGS AND | | | SETBACKS. | | | 10- PROVIDE PRODUCT APPROVAL FOR: A)ALL EXTERIOR DOORS. | | | B)WINDOWS. C)WINDOW MULLIONS (NOTE: SPECIFY MULLION | | | SIZE) D)ROOF CLAY TILE. E)CLAY TILE ADHESIVE AND MARK | | | PADDY SIZE. F)CLAY TILE FOR GUARDRAIL SYSTEM SHOWN ON | | | ELEVATIONS. G)SPRAY FOAM INSULATION SPECIFIED ON | | | PLANS.(NOTE:PROVIDE ICC EVALUATION REPORT). | | | 11- ENGINEER OF RECORD TO REVIEW/APPROVE ALL PRODUCT | | | APPROVALS. | | | 12- PROVIDE COMPLETE DETAILS/SPECS FOR FUTURE CUSTOM | | | GLASS WINE ROOM ON A SEPARATE PERMIT. | | | 13- FUTURE ELEVATOR WILL BE ON A SEPARATE PERMIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-05-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-05-23 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-05-23 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2022-05-23 10:54:24 | GARAGE/GUEST SUITE ADDITION(R3), SECOND BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #22031166. | | | | | | NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR | | | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME | | | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT | | | ISSUANCE. | | | | | | ORIGINAL COMMENT: | | | 1-DESIGNER OF RECORD TO NEEDS TO DEPICT THE BUILDING | | | THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND | | | THEIR R-VALUES. DESIGNER OF RECORD TO SPECIFY THE | | | R-VALUE FOR CEILING, WALLS, FLOOR/CEILING ASSEMBLY | | | BETWEEN GARAGE AND GUEST SUITE ABOVE. SEC. R103.2 | | | FBC-ENERGY CONSERVATION. | | | NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | RESPONSE. | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 2-ENERGY CALCULATIONS SUBMITTED GUEST HOUSE: | | | A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, | | | INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE | | | AND JURISDICTION (THIS JURISDICTION IS 604700). SEC. | | | R101.5.1.1.2 FBC- ENERGY CONSERVATION. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | B)FLOOR TYPES INFORMATION IS INCORRECT. I BELIEVE THE | | | RAISED FLOOR AREA IS THE GUEST SUITE. THEN, THE SQUARE | | | FOOTAGE AREA OF THE GUEST SUITE IS INCORRECT. REVISE AS | | | REQUIRED. | | | NOTE: CLARIFY WHAT IS BEING CONSIDERED AS THE FLOOR | | | OVER THE GARAGE AREA AND RAISED FLOOR AREA?. ALSO, KEEP | | | IN MIND THAT FLOOR AREAS ABOVE UNCONDITIONED SPACE NEED | | | TO HAVE INSULATION. REVISE FLOOR TYPES INFORMATION TO | | | MATCH PLANS TO AVOID CONFLICTS/DELAYS. | | | SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. | | | | | | C)SPACES INFORMATION ON PAGE 2 IS INCORRECT. THERE IS | | | NOT KITCHEN IN THE GUEST SUITE. REVISE AS REQUIRED. | | | SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. | | | | | | D)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL | | | (EPL) DISPLAY CARD FOR EACH BUILDING. SEC. R405.4.3 | | | FBC-ENERGY CONSERVATION. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | 3- LOT DRAINAGE | | | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | | FOLLOWING: | | | R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS. | | | SEC. 110.9 CITY AMENDMENTS. | | | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED | | | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM | | | ADJACENT PROPERTIES. | | | | | | RESPONSE: | | | DETAIL SECTIONS A-A, B-B AND C-C ON SITE ENGINEERING | | | PLAN SUBMITTED SHOW WATER RUNNING TO THE NEIGHBOR'S | | | PROPERTY. THE WATER NEEDS TO BE CONTAINED WITHIN THE | | | LOT AND/OR DIVERTED TO AN APPROVED POINT OF COLLECTION | | | OR TOWARDS THE STREET. ALSO, THE PROPOSED POOL DECK IS | | | TOO CLOSE TO THE NEIGHBOR'S PROPERTY AND THERE IS NOT | | | INFORMATION SHOWING HOW THE WATER WILL REMAIN WITHIN | | | THIS LOT IN THIS AREA. REVISE AS REQUIRED. ALSO, | | | MISSING SECTION FOR FRONT OF THE LOT. | | | SEC. 110 CITY AMENDMENTS. | | | | | | ORIGINAL COMMENT: | | | 4-PROVIDE SURVEY SHOWING PROPOSED BUILDINGS AND | | | SETBACKS. | | | SEC. 107.2.5 CITY AMENDMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | DEFERRED SUBMITTAL: | | | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | A)ALL EXTERIOR DOORS. | | | B)WINDOWS. | | | C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE | | | TO AVOID DELAYS/CONFLICTS). | | | D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | E)CLAY TILE ROOF (3:12 PITCH). | | | F)CLAY TILE ADHESIVE (IF SPECIFIED ON PLANS) AND MARK | | | PADDY SIZE. | | | G)SPRAY FOAM INSULATION SPECIFIED ON | | | PLANS.(NOTE:PROVIDE ICC EVALUATION REPORT). | | | | | | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-04-06 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-04-06 |
Time |
18:02 |
Sent To |
|
|
| Notes |
| 2022-04-06 18:24:11 | GARAGE/GUEST SUITE ADDITION(R3), BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #22031166. | | | | | | 1-DESIGNER OF RECORD TO NEEDS TO DEPICT THE BUILDING | | | THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND | | | THEIR R-VALUES. DESIGNER OF RECORD TO SPECIFY THE | | | R-VALUE FOR CEILING, WALLS, FLOOR/CEILING ASSEMBLY | | | BETWEEN GARAGE AND GUEST SUITE ABOVE. SEC. R103.2 | | | FBC-ENERGY CONSERVATION. | | | NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | 2-ENERGY CALCULATIONS SUBMITTED: | | | A)CALCULATIONS NEED THE ORIGINAL SEAL AND SIGNATURE OF | | | THE ENGINEER AS REQUIRED BY CHAPTER 471 FLORIDA | | | STATUTES WHEN SUBMITTING DOCUMENTS/PLANS FOR PUBLIC | | | RECORDS. | | | NOTE: SUBMIT CALCULATIONS ELECTRONICALLY WITH | | | ENGINEER'S DIGITAL SIGNATURE OR PROVIDE HARD COPY | | | CALCULATIONS WITH ENGINEER'S ORIGINAL SEAL AND | | | SIGNATURE. | | | | | | B)SEPARATE ENERGY CALCULATIONS IS REQUIRED FOR EACH | | | BUILDING. MAIN HOUSE AND ACCESSORY STRUCTURE. SEC. | | | R101.3 FBC-ENERGY CONSERVATION. | | | | | | C)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, | | | INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE | | | AND JURISDICTION (THIS JURISDICTION IS 604700). SEC. | | | R101.5.1.1.2 FBC- ENERGY CONSERVATION. | | | | | | D)NUMBER OF BEDROOMS, CONDITIONED FLOOR AREA, WINDOWS | | | INFORMATION, FLOOR TYPES INFORMATION, WALL TYPES | | | INFORMATION, CEILING TYPES INFORMATION AND ALL | | | INFORMATION ON SUBSEQUENT PAGES NEED TO BE COORDINATED | | | WITH EACH BUILDING. SEE PLANS FOR INFORMATION ON EACH | | | BUILDING AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 | | | FBC-RESIDENTIAL. | | | NOTE: COORDINATE WITH ITEM 5(B) ABOVE. SEPARATE | | | BUILDINGS. | | | | | | E)WINDOWS OVERHANG DEPTH AND SEPARATION ON PAGE 3 DON'T | | | MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED TO MATCH | | | PLANS. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. | | | NOTE: COORDINATE WITH ITEM 5(B) ABOVE. SEPARATE | | | BUILDINGS. | | | | | | F)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL | | | (EPL) DISPLAY CARD FOR EACH BUILDING. SEC. R405.4.3 | | | FBC-ENERGY CONSERVATION. | | | | | | 3- LOT DRAINAGE | | | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | | FOLLOWING: | | | R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS. | | | SEC. 110.9 CITY AMENDMENTS. | | | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED | | | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM | | | ADJACENT PROPERTIES. | | | | | | NOTE: THIS IS NOT A DEFERRED SUBMITTAL. THIS | | | INFORMATION IS REQUIRED NOW BECAUSE IT AFFECTS THE | | | CONSTRUCTION OF THE HOUSE. | | | NOTE: PROVIDE DRAINAGE PLAN. SHOW HOW THE EXISTING AND | | | PROPOSED GRADE ELEVATIONS WILL KEEP WATER AWAY FROM | | | ADJACENT PROPERTIES. | | | | | | 4-PROVIDE SURVEY SHOWING PROPOSED BUILDINGS AND | | | SETBACKS. | | | SEC. 107.2.5 CITY AMENDMENTS. | | | | | | DEFERRED SUBMITTAL: | | | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | A)ALL EXTERIOR DOORS. | | | B)WINDOWS. | | | C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE | | | TO AVOID DELAYS/CONFLICTS). | | | D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | E)CLAY TILE ROOF (3:12 PITCH). | | | F)CLAY TILE ADHESIVE (IF SPECIFIED ON PLANS) AND MARK | | | PADDY SIZE. | | | G)SPRAY FOAM INSULATION SPECIFIED ON | | | PLANS.(NOTE:PROVIDE ICC EVALUATION REPORT). | | | | | | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-06-13 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-13 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-13 |
Time |
15:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-05-18 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-05-18 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2022-05-18 15:56:33 | NOT ABLE TO STAMP PLAN BECAUSE TWO UNITS ARE TOGETHER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-04-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-04-07 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-04-07 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2022-04-07 15:01:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NO RISER DIAGRAM SHOWN 215.5 | | | | | | 2) NO LOAD CALCULATION SUBMITTED. 215.5 | | | | | | 3) MASTRE BATH HAS PENDANT FIXTURE OVER TUB, NOT | | | ALLOWED 410.10(D) | | | | | | (D) BATHTUB AND SHOWER AREAS. NO PARTS OF | | | CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR | | | CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR | | | CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN | | | A ZONE MEASURED 900 MM (3 FT) HORIZONTALLY AND 2.5 M (8 | | | FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR | | | SHOWER STALL THRESHOLD. THIS ZONE IS ALL ENCOMPASSING | | | AND INCLUDES THE SPACE DIRECTLY OVER THE TUB OR SHOWER | | | STALL. LUMINAIRES LOCATED WITHIN THE ACTUAL OUTSIDE | | | DIMENSION OF THE BATHTUB OR SHOWER TO A HEIGHT OF 2.5 M | | | (8 FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR | | | SHOWER THRESHOLD SHALL BE MARKED FOR DAMP LOCATIONS, OR | | | MARKED FOR WET LOCATIONS WHERE SUBJECT TO SHOWER SPRAY. | | | | | | 4) PANEL SCHEDULE(S) REQUIRED TO VERUFY LOADS IN LOAD | | | CALCLUATION 215.5 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2022-05-31 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-05-31 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-05-31 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2022-05-31 11:13:21 | PLANS LOCATED AT 21060227 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-04-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-04-07 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-04-07 |
Time |
09:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-06-13 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-13 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-27 |
Time |
16:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-05-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-05-23 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-05-23 |
Time |
13:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-05-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-05-23 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-05-04 |
Time |
19:00 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-04-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-04-07 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-03-30 |
Time |
14:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-05-18 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-05-18 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2022-05-18 13:11:10 | IMPACT REVIEW DONE IN PERMIT 21060227. | | | QUESTIONAIRE, EXISTING USE AND PLANS FOR MAIN HOUSE AND | | | GARAGE ARE TOGETHER UNDER 21060227. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-04-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-04-06 |
Time |
18:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-04-06 |
Time |
18:28 |
Sent To |
|
|
| Notes |
| 2022-04-06 18:28:43 | IMPACT FEES | | | PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR | | | IMPACT FEE ASSESSMENT. | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2022-05-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-31 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-31 |
Time |
11:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-18 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-18 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2022-05-18 14:11:11 | MECHANICAL REVIEW COMPLETED UNDER PERMIT #21060227. ME |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-05-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-13 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-13 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2022-05-13 11:25:50 | PROVIDE THE MECHANICAL DRAWINGS FOR THIS PROJECT. FBC | | | 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-07 |
Time |
05:57 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-07 |
Time |
05:57 |
Sent To |
|
|
| Notes |
| 2022-04-07 06:04:16 | 1) THE GARAGE AND THE LIVING SPACE ABOVE IS UNDER | | | PERMIT NUMBER 22031166. THE ENERGY CALCULATION | | | SUBMITTED FOR PERMIT NUMBER 21060227 INCLUDES THE | | | GARAGE AND LIVING SPACE ABOVE. THERE MUST BE A SEPARATE | | | ENERGY CALCULATION FOR THE GARAGE AND LIVING SPACE. | | | PLEASE PROVIDE A SEPARATE ENERGY CALCULATION FOR BOTH | | | THE MAIN HOUSE AND THE GARAGE WITH LIVING SPACE ABOVE. | | | | | | 2) 3RD TIME FOR THE FOLLOWING COMMENTS. | | | | | | PLEASE PROVIDE MECHANICAL DRAWINGS FOR THIS PROJECT. | | | FBC 107.2.1 | | | A MECHANICAL PLANS REVIEW COULD NOT BE STARTED WITH | | | THIS SUBMITTAL AS NO MECHANICAL DRAWINGS WERE | | | SUBMITTED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-05-31 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-05-31 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-05-31 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2022-05-31 11:14:03 | PLANS LOCATED AT 21060227 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-05-18 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-05-18 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2022-05-18 14:02:27 | PLANS REVIEWED ON 21060227 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-05-09 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-05-09 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-05-09 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2022-05-09 15:35:26 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. NOT ADDRESSED --- 2017 WPB AMEND - 107.3.5.3 (12.) | | | -- PLEASE SUBMIT A PLUMBING RISER. PLEASE INCLUDE THE | | | SIGNATURE OF THE PERSON WHO DESIGNED THE ISOMETRIC AS A | | | REQUIREMENT OF 107.2.1. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-04-05 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-04-05 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-04-05 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2022-04-05 15:31:14 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND - 107.3.5.3 (12.) -- PLEASE SUBMIT A | | | PLUMBING RISER. PLEASE INCLUDE THE SIGNATURE OF THE | | | PERSON WHO DESIGNED THE ISOMETRIC AS A REQUIREMENT OF | | | 107.2.1. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2022-07-01 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-07-01 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-07-01 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2022-07-01 15:56:13 | PRIVATE PROVIDER INSPECTIONS. | | | PP DOCUMENTS UNDER MAIN PERMIT 21060227 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-04-06 |
Time |
18:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-04-06 |
Time |
18:26 |
Sent To |
|
|
| Notes |
| 2022-04-06 18:27:29 | NEED TO PROVIDE COMPLETE ROOFING INFORMATION FOR REVIEW | | | PRIOR TO ISSUING THE ROOFING SUB-PERMIT. | | | | | | 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | A))CLAY TILE ROOF (3:12 PITCH). AND CLEARLY MARK | | | FASTENING METHOD. | | | B)CLAY TILE ADHESIVE (IF SPECIFIED ON CLAY TILE PRODUCT | | | APPROVAL) AND MARK PADDY SIZE. | | | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
N |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-05-18 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-05-18 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2022-05-18 13:16:38 | PLANS FOR GARAGE ARE WITH THE MAIN HOUSE 21060227 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-04-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-04-07 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-04-07 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2022-04-07 09:46:11 | SIGNATURE REVIEW: | | | | | | 1- DRAWINGS DON'T HAVE ORIGINAL DIGITAL SEAL/SIGNATURE | | | BY THE ARCHITECT AND ENGINEER OF RECORD. ALL DRAWINGS | | | NEED TO HAVE ORIGINAL DIGITAL L SEAL/SIGNATURE AS | | | REQUIRED BY CHAPTER 481 F.S. AND CHAPTER 471 F.S. WHEN | | | SUBMITTING FOR PUBLIC RECORDS. | | | | | | NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH | | | ARCHITECT'S/ENGINEER'S DIGITAL SIGNATURE OR PROVIDE | | | HARD COPY PLANS WITH ARCHITECT'S ORIGINAL SEAL AND | | | SIGNATURE. | | | | | | 2- ENERGY CALCULATIONS AND EQUIPMENT SIZING | | | CALCULATIONS DON'T HAVE ENGINEER'S ORIGINAL DIGITAL | | | SEAL/SIGNATURE. NEED TO HAVE ORIGINAL DIGITAL L | | | SEAL/SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN | | | SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS. | | | | | | | | | ENGINEERS | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | ARCHITECTS | | | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2022-04-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-04-07 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-04-07 |
Time |
09:15 |
Sent To |
|
|
| Notes |
|
|