Plan Review Details - Permit 22031166
Plan Review Stops For Permit 22031166
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-03-31 Cont ID  
Sent By cpuell Date 2022-03-31 Time 12:00 Rev Time 0.00
Received By cpuell Date 2022-03-31 Time 12:00 Sent To  
Notes
2022-03-31 12:00:47ADDRESS HAD PREVIOUSLY BEEN ASSIGNED TO THIS BUILDING
 AS 221 PERSHING WAY, UPDATED PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-05-23 Cont ID  
Sent By jgomez Date 2022-05-23 Time 13:33 Rev Time 0.00
Received By jgomez Date 2022-05-23 Time 13:33 Sent To  
Notes
2022-05-23 13:34:42BUILDING REVIEW APPROVED WITH PROVISO
 (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION/INSPECTIONS TO AVOID CONFLICTS/DELAYS):
  
 1- PROVIDE COMPLETE FRAMING DETAILS/SPECS FOR ELEVATOR
 SHAFT. SPECIFY ALL FRAMING MEMBERS/CONNECTORS,
 INCLUDING BRACING TO SUPPORT THE ELEVATOR. (MAIN HOUSE)
 2- PROVIDE COMPLETE DETAILS/SPECS FOR BALCONIES CLAY
 TILE RAILING. SPECIFY ALL FRAMING MEMBERS/CONNECTORS
 AND CLAY TILE INSTALLATION.(MAIN HOUSE)
 3- PROVIDE COMPLETE DETAILS/SPECS FOR CANOPIES. SPECIFY
 ALL FRAMING MEMBERS/CONNECTORS.
 4- PROVIDE COMPLETE FRAMING DETAILS/SPECS FOR TRELLIS
 PERGOLA. SPECIFY ALL FRAMING MEMBERS/CONNECTORS. (MAIN
 HOUSE)
 5- DESIGNER OF RECORD TO DEPICT THE BUILDING THERMAL
 ENVELOPE. SPECIFY INSULATION R-VALUES. SEC. R103.2
 FBC-ENERGY CONSERVATION.
 6- REVISE ENERGY CALCULATIONS MAIN HOUSE.
 A)PROVIDE INFORMATION: OWNER, BUILDER, PERMIT OFFICE &
 JURISDICTION (JURISDICTION 604700).SEC. R101.5.1.1.2
 FBC- ENERGY CONSERVATION.
 B)WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH
 PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
 C)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD FOR EACH BUILDING. SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
 7- REVISE ENERGY CALCULATIONS GUEST HOUSE.
 A)PROVIDE INFORMATION: OWNER, BUILDER, PERMIT OFFICE &
 JURISDICTION (JURISDICTION 604700).SEC. R101.5.1.1.2
 FBC- ENERGY CONSERVATION. B)REVISE FLOOR TYPES
 INFORMATION. THE RAISED FLOOR IS THE GUEST SUITE.
 REVISE AS REQUIRED. FLOOR AREAS ABOVE UNCONDITIONED
 SPACE NEED TO HAVE INSULATION. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
 C)REVISE SPACES INFORMATION. THERE IS NOT KITCHEN IN
 THE GUEST SUITE.
 D)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD FOR EACH BUILDING. SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
 8- REVISE LOT DRAINAGE PLAN: DETAIL SECTIONS A-A, B-B
 AND C-C SHOW WATER RUNNING TO THE NEIGHBOR'S PROPERTY.
 ALSO, PROVIDE INFORMATION SHOWING DRAINAGE ON THE EAST
 SIDE OF POOL DECK.
 9- PROVIDE SURVEY SHOWING PROPOSED BUILDINGS AND
 SETBACKS.
 10- PROVIDE PRODUCT APPROVAL FOR: A)ALL EXTERIOR DOORS.
 B)WINDOWS. C)WINDOW MULLIONS (NOTE: SPECIFY MULLION
 SIZE) D)ROOF CLAY TILE. E)CLAY TILE ADHESIVE AND MARK
 PADDY SIZE. F)CLAY TILE FOR GUARDRAIL SYSTEM SHOWN ON
 ELEVATIONS. G)SPRAY FOAM INSULATION SPECIFIED ON
 PLANS.(NOTE:PROVIDE ICC EVALUATION REPORT).
 11- ENGINEER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS.
 12- PROVIDE COMPLETE DETAILS/SPECS FOR FUTURE CUSTOM
 GLASS WINE ROOM ON A SEPARATE PERMIT.
 13- FUTURE ELEVATOR WILL BE ON A SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-23 Cont ID  
Sent By jgomez Date 2022-05-23 Time 10:53 Rev Time 0.00
Received By jgomez Date 2022-05-23 Time 09:15 Sent To  
Notes
2022-05-23 10:54:24GARAGE/GUEST SUITE ADDITION(R3), SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22031166.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ORIGINAL COMMENT:
 1-DESIGNER OF RECORD TO NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND
 THEIR R-VALUES. DESIGNER OF RECORD TO SPECIFY THE
 R-VALUE FOR CEILING, WALLS, FLOOR/CEILING ASSEMBLY
 BETWEEN GARAGE AND GUEST SUITE ABOVE. SEC. R103.2
 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE.
 REPEAT COMMENT. NOT ADDRESSED.
  
 2-ENERGY CALCULATIONS SUBMITTED GUEST HOUSE:
 A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION (THIS JURISDICTION IS 604700). SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B)FLOOR TYPES INFORMATION IS INCORRECT. I BELIEVE THE
 RAISED FLOOR AREA IS THE GUEST SUITE. THEN, THE SQUARE
 FOOTAGE AREA OF THE GUEST SUITE IS INCORRECT. REVISE AS
 REQUIRED.
 NOTE: CLARIFY WHAT IS BEING CONSIDERED AS THE FLOOR
 OVER THE GARAGE AREA AND RAISED FLOOR AREA?. ALSO, KEEP
 IN MIND THAT FLOOR AREAS ABOVE UNCONDITIONED SPACE NEED
 TO HAVE INSULATION. REVISE FLOOR TYPES INFORMATION TO
 MATCH PLANS TO AVOID CONFLICTS/DELAYS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 C)SPACES INFORMATION ON PAGE 2 IS INCORRECT. THERE IS
 NOT KITCHEN IN THE GUEST SUITE. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD FOR EACH BUILDING. SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 3- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 DETAIL SECTIONS A-A, B-B AND C-C ON SITE ENGINEERING
 PLAN SUBMITTED SHOW WATER RUNNING TO THE NEIGHBOR'S
 PROPERTY. THE WATER NEEDS TO BE CONTAINED WITHIN THE
 LOT AND/OR DIVERTED TO AN APPROVED POINT OF COLLECTION
 OR TOWARDS THE STREET. ALSO, THE PROPOSED POOL DECK IS
 TOO CLOSE TO THE NEIGHBOR'S PROPERTY AND THERE IS NOT
 INFORMATION SHOWING HOW THE WATER WILL REMAIN WITHIN
 THIS LOT IN THIS AREA. REVISE AS REQUIRED. ALSO,
 MISSING SECTION FOR FRONT OF THE LOT.
 SEC. 110 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 4-PROVIDE SURVEY SHOWING PROPOSED BUILDINGS AND
 SETBACKS.
 SEC. 107.2.5 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 DEFERRED SUBMITTAL:
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
 A)ALL EXTERIOR DOORS.
 B)WINDOWS.
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
 D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)CLAY TILE ROOF (3:12 PITCH).
 F)CLAY TILE ADHESIVE (IF SPECIFIED ON PLANS) AND MARK
 PADDY SIZE.
 G)SPRAY FOAM INSULATION SPECIFIED ON
 PLANS.(NOTE:PROVIDE ICC EVALUATION REPORT).
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-06 Cont ID  
Sent By jgomez Date 2022-04-06 Time 18:23 Rev Time 0.00
Received By jgomez Date 2022-04-06 Time 18:02 Sent To  
Notes
2022-04-06 18:24:11GARAGE/GUEST SUITE ADDITION(R3), BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22031166.
  
 1-DESIGNER OF RECORD TO NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND
 THEIR R-VALUES. DESIGNER OF RECORD TO SPECIFY THE
 R-VALUE FOR CEILING, WALLS, FLOOR/CEILING ASSEMBLY
 BETWEEN GARAGE AND GUEST SUITE ABOVE. SEC. R103.2
 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 2-ENERGY CALCULATIONS SUBMITTED:
 A)CALCULATIONS NEED THE ORIGINAL SEAL AND SIGNATURE OF
 THE ENGINEER AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES WHEN SUBMITTING DOCUMENTS/PLANS FOR PUBLIC
 RECORDS.
 NOTE: SUBMIT CALCULATIONS ELECTRONICALLY WITH
 ENGINEER'S DIGITAL SIGNATURE OR PROVIDE HARD COPY
 CALCULATIONS WITH ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE.
  
 B)SEPARATE ENERGY CALCULATIONS IS REQUIRED FOR EACH
 BUILDING. MAIN HOUSE AND ACCESSORY STRUCTURE. SEC.
 R101.3 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION (THIS JURISDICTION IS 604700). SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)NUMBER OF BEDROOMS, CONDITIONED FLOOR AREA, WINDOWS
 INFORMATION, FLOOR TYPES INFORMATION, WALL TYPES
 INFORMATION, CEILING TYPES INFORMATION AND ALL
 INFORMATION ON SUBSEQUENT PAGES NEED TO BE COORDINATED
 WITH EACH BUILDING. SEE PLANS FOR INFORMATION ON EACH
 BUILDING AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH ITEM 5(B) ABOVE. SEPARATE
 BUILDINGS.
  
 E)WINDOWS OVERHANG DEPTH AND SEPARATION ON PAGE 3 DON'T
 MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
 NOTE: COORDINATE WITH ITEM 5(B) ABOVE. SEPARATE
 BUILDINGS.
  
 F)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD FOR EACH BUILDING. SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
  
 3- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 NOTE: THIS IS NOT A DEFERRED SUBMITTAL. THIS
 INFORMATION IS REQUIRED NOW BECAUSE IT AFFECTS THE
 CONSTRUCTION OF THE HOUSE.
 NOTE: PROVIDE DRAINAGE PLAN. SHOW HOW THE EXISTING AND
 PROPOSED GRADE ELEVATIONS WILL KEEP WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 4-PROVIDE SURVEY SHOWING PROPOSED BUILDINGS AND
 SETBACKS.
 SEC. 107.2.5 CITY AMENDMENTS.
  
 DEFERRED SUBMITTAL:
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
 A)ALL EXTERIOR DOORS.
 B)WINDOWS.
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
 D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)CLAY TILE ROOF (3:12 PITCH).
 F)CLAY TILE ADHESIVE (IF SPECIFIED ON PLANS) AND MARK
 PADDY SIZE.
 G)SPRAY FOAM INSULATION SPECIFIED ON
 PLANS.(NOTE:PROVIDE ICC EVALUATION REPORT).
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-06-13 Cont ID  
Sent By mpeterso Date 2022-06-13 Time 15:23 Rev Time 0.00
Received By mpeterso Date 2022-06-13 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By jleahy Date 2022-05-18 Time 15:56 Rev Time 0.00
Received By jleahy Date 2022-05-18 Time 15:55 Sent To  
Notes
2022-05-18 15:56:33NOT ABLE TO STAMP PLAN BECAUSE TWO UNITS ARE TOGETHER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-07 Cont ID  
Sent By jleahy Date 2022-04-07 Time 15:01 Rev Time 0.00
Received By jleahy Date 2022-04-07 Time 14:43 Sent To  
Notes
2022-04-07 15:01:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO RISER DIAGRAM SHOWN 215.5
  
 2) NO LOAD CALCULATION SUBMITTED. 215.5
  
 3) MASTRE BATH HAS PENDANT FIXTURE OVER TUB, NOT
 ALLOWED 410.10(D)
  
 (D) BATHTUB AND SHOWER AREAS. NO PARTS OF
 CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR
 CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR
 CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN
 A ZONE MEASURED 900 MM (3 FT) HORIZONTALLY AND 2.5 M (8
 FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR
 SHOWER STALL THRESHOLD. THIS ZONE IS ALL ENCOMPASSING
 AND INCLUDES THE SPACE DIRECTLY OVER THE TUB OR SHOWER
 STALL. LUMINAIRES LOCATED WITHIN THE ACTUAL OUTSIDE
 DIMENSION OF THE BATHTUB OR SHOWER TO A HEIGHT OF 2.5 M
 (8 FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR
 SHOWER THRESHOLD SHALL BE MARKED FOR DAMP LOCATIONS, OR
 MARKED FOR WET LOCATIONS WHERE SUBJECT TO SHOWER SPRAY.
  
 4) PANEL SCHEDULE(S) REQUIRED TO VERUFY LOADS IN LOAD
 CALCLUATION 215.5
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-05-31 Cont ID  
Sent By rwbrown Date 2022-05-31 Time 11:11 Rev Time 0.00
Received By rwbrown Date 2022-05-31 Time 11:11 Sent To  
Notes
2022-05-31 11:13:21PLANS LOCATED AT 21060227

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-04-07 Cont ID  
Sent By fmittner Date 2022-04-07 Time 09:15 Rev Time 0.00
Received By fmittner Date 2022-04-07 Time 09:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-06-13 Cont ID  
Sent By mpeterso Date 2022-06-13 Time 15:23 Rev Time 0.00
Received By mpeterso Date 2022-05-27 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-23 Cont ID  
Sent By jgomez Date 2022-05-23 Time 13:37 Rev Time 0.00
Received By jgomez Date 2022-05-23 Time 13:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-23 Cont ID  
Sent By jgomez Date 2022-05-23 Time 10:55 Rev Time 0.00
Received By jgomez Date 2022-05-04 Time 19:00 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-07 Cont ID  
Sent By jleahy Date 2022-04-07 Time 15:02 Rev Time 0.00
Received By jleahy Date 2022-03-30 Time 14:45 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2022-05-18 Cont ID  
Sent By dbattles Date 2022-05-18 Time 13:08 Rev Time 0.00
Received By dbattles Date 2022-05-18 Time 13:08 Sent To  
Notes
2022-05-18 13:11:10IMPACT REVIEW DONE IN PERMIT 21060227.
 QUESTIONAIRE, EXISTING USE AND PLANS FOR MAIN HOUSE AND
 GARAGE ARE TOGETHER UNDER 21060227.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-04-06 Cont ID  
Sent By jgomez Date 2022-04-06 Time 18:28 Rev Time 0.00
Received By jgomez Date 2022-04-06 Time 18:28 Sent To  
Notes
2022-04-06 18:28:43IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-05-31 Cont ID  
Sent By medwards Date 2022-05-31 Time 11:17 Rev Time 0.00
Received By medwards Date 2022-05-31 Time 11:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-05-18 Cont ID  
Sent By medwards Date 2022-05-18 Time 14:10 Rev Time 0.00
Received By medwards Date 2022-05-18 Time 14:10 Sent To  
Notes
2022-05-18 14:11:11MECHANICAL REVIEW COMPLETED UNDER PERMIT #21060227. ME

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-05-13 Cont ID  
Sent By medwards Date 2022-05-13 Time 11:25 Rev Time 0.00
Received By medwards Date 2022-05-13 Time 11:25 Sent To  
Notes
2022-05-13 11:25:50PROVIDE THE MECHANICAL DRAWINGS FOR THIS PROJECT. FBC
 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-07 Cont ID  
Sent By medwards Date 2022-04-07 Time 05:57 Rev Time 0.00
Received By medwards Date 2022-04-07 Time 05:57 Sent To  
Notes
2022-04-07 06:04:161) THE GARAGE AND THE LIVING SPACE ABOVE IS UNDER
 PERMIT NUMBER 22031166. THE ENERGY CALCULATION
 SUBMITTED FOR PERMIT NUMBER 21060227 INCLUDES THE
 GARAGE AND LIVING SPACE ABOVE. THERE MUST BE A SEPARATE
 ENERGY CALCULATION FOR THE GARAGE AND LIVING SPACE.
 PLEASE PROVIDE A SEPARATE ENERGY CALCULATION FOR BOTH
 THE MAIN HOUSE AND THE GARAGE WITH LIVING SPACE ABOVE.
  
 2) 3RD TIME FOR THE FOLLOWING COMMENTS.
  
 PLEASE PROVIDE MECHANICAL DRAWINGS FOR THIS PROJECT.
 FBC 107.2.1
 A MECHANICAL PLANS REVIEW COULD NOT BE STARTED WITH
 THIS SUBMITTAL AS NO MECHANICAL DRAWINGS WERE
 SUBMITTED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-05-31 Cont ID  
Sent By rwbrown Date 2022-05-31 Time 11:13 Rev Time 0.00
Received By rwbrown Date 2022-05-31 Time 11:13 Sent To  
Notes
2022-05-31 11:14:03PLANS LOCATED AT 21060227

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-05-18 Cont ID  
Sent By rwbrown Date 2022-05-18 Time 14:02 Rev Time 0.00
Received By rwbrown Date 2022-05-18 Time 14:02 Sent To  
Notes
2022-05-18 14:02:27PLANS REVIEWED ON 21060227

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-09 Cont ID  
Sent By rwbrown Date 2022-05-09 Time 15:35 Rev Time 0.00
Received By rwbrown Date 2022-05-09 Time 15:21 Sent To  
Notes
2022-05-09 15:35:262ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. NOT ADDRESSED --- 2017 WPB AMEND - 107.3.5.3 (12.)
 -- PLEASE SUBMIT A PLUMBING RISER. PLEASE INCLUDE THE
 SIGNATURE OF THE PERSON WHO DESIGNED THE ISOMETRIC AS A
 REQUIREMENT OF 107.2.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-05 Cont ID  
Sent By rwbrown Date 2022-04-05 Time 15:29 Rev Time 0.00
Received By rwbrown Date 2022-04-05 Time 14:18 Sent To  
Notes
2022-04-05 15:31:141ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 107.3.5.3 (12.) -- PLEASE SUBMIT A
 PLUMBING RISER. PLEASE INCLUDE THE SIGNATURE OF THE
 PERSON WHO DESIGNED THE ISOMETRIC AS A REQUIREMENT OF
 107.2.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-07-01 Cont ID  
Sent By dbattles Date 2022-07-01 Time 15:55 Rev Time 0.00
Received By dbattles Date 2022-07-01 Time 15:55 Sent To  
Notes
2022-07-01 15:56:13PRIVATE PROVIDER INSPECTIONS.
 PP DOCUMENTS UNDER MAIN PERMIT 21060227

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-05-18 Cont ID  
Sent By jgomez Date 2022-04-06 Time 18:26 Rev Time 0.00
Received By jgomez Date 2022-04-06 Time 18:26 Sent To  
Notes
2022-04-06 18:27:29NEED TO PROVIDE COMPLETE ROOFING INFORMATION FOR REVIEW
 PRIOR TO ISSUING THE ROOFING SUB-PERMIT.
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
 A))CLAY TILE ROOF (3:12 PITCH). AND CLEARLY MARK
 FASTENING METHOD.
 B)CLAY TILE ADHESIVE (IF SPECIFIED ON CLAY TILE PRODUCT
 APPROVAL) AND MARK PADDY SIZE.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-05-18 Cont ID  
Sent By dbattles Date 2022-05-18 Time 13:13 Rev Time 0.00
Received By dbattles Date 2022-05-18 Time 13:13 Sent To  
Notes
2022-05-18 13:16:38PLANS FOR GARAGE ARE WITH THE MAIN HOUSE 21060227

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-07 Cont ID  
Sent By jgomez Date 2022-04-07 Time 09:45 Rev Time 0.00
Received By jgomez Date 2022-04-07 Time 09:45 Sent To  
Notes
2022-04-07 09:46:11SIGNATURE REVIEW:
  
 1- DRAWINGS DON'T HAVE ORIGINAL DIGITAL SEAL/SIGNATURE
 BY THE ARCHITECT AND ENGINEER OF RECORD. ALL DRAWINGS
 NEED TO HAVE ORIGINAL DIGITAL L SEAL/SIGNATURE AS
 REQUIRED BY CHAPTER 481 F.S. AND CHAPTER 471 F.S. WHEN
 SUBMITTING FOR PUBLIC RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH
 ARCHITECT'S/ENGINEER'S DIGITAL SIGNATURE OR PROVIDE
 HARD COPY PLANS WITH ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE.
  
 2- ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS DON'T HAVE ENGINEER'S ORIGINAL DIGITAL
 SEAL/SIGNATURE. NEED TO HAVE ORIGINAL DIGITAL L
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
  
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-04-07 Cont ID  
Sent By fmittner Date 2022-04-07 Time 09:15 Rev Time 0.00
Received By fmittner Date 2022-04-07 Time 09:15 Sent To  
Notes
***NONE***