Plan Review Details - Permit 22031012
Plan Review Stops For Permit 22031012
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-04-28 Cont ID  
Sent By rmcphers Date 2022-04-28 Time 16:17 Rev Time 0.00
Received By rmcphers Date 2022-04-28 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-10 Cont ID  
Sent By rmcphers Date 2022-05-10 Time 11:12 Rev Time 0.00
Received By rmcphers Date 2022-05-10 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-04-28 Cont ID  
Sent By rmcphers Date 2022-04-28 Time 16:17 Rev Time 0.00
Received By rmcphers Date 2022-04-28 Time 16:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-19 Cont ID  
Sent By fgiaquin Date 2022-05-19 Time 19:41 Rev Time 0.00
Received By fgiaquin Date 2022-05-19 Time 18:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-13 Cont ID  
Sent By fgiaquin Date 2022-04-13 Time 22:14 Rev Time 0.00
Received By fgiaquin Date 2022-04-13 Time 20:57 Sent To  
Notes
2022-04-13 22:14:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL NOTE #1 IS INCORRECT. FLORIDA STATUTE
 471.003 (2) (H) (1 AND 2A) READS AS FOLLOWS:
  
 (H)?ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR
 MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE
 DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY,
 WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED
 UNDER CHAPTER 489, UNDER FORMER PART I OF CHAPTER 553,
 FLORIDA STATUTES 2001, OR UNDER ANY SPECIAL ACT OR
 ORDINANCE WHEN WORKING ON ANY CONSTRUCTION PROJECT
 WHICH:
 1.?REQUIRES AN ELECTRICAL OR PLUMBING OR
 AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE
 OF $125,000 OR LESS; AND
 2.A.?REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600
 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL
 SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A
 COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM
  
 THEY ARE NOT REQUIRED TO TAKE RESPONSIBILTY FOR THE
 DESIGN, THEY ARE EXEMPT FROM NEEDING A DESIGN
 PROFESSIONAL TO DESIGN THE DRAWINGS IF THEY CHOOSE.
 PLEASE PROVIDE CORRECTION IF YOU WISH TO KEEP NOTE ON
 PLAN.
  
 2. ELECTRICAL NOTE #19 IS INCORRECT. IT IS 90% OF LIGHT
 FIXTURES IN THE CURRENT ADOPTED ENERGY CODE FBC-EC 2020
 7TH EDITION FBC-EC R404.1 PLEASE PROVIDE CORRECTION.
  
 3.RECEPTACLE REQUIRED ON BALCONY PER NEC 210.52E3
 PLEASE PROVIDE CORRECTION.
  
 4. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-06 Cont ID  
Sent By pleduc Date 2022-05-06 Time   Rev Time 0.00
Received By pleduc Date 2022-05-06 Time 10:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-23 Cont ID  
Sent By pleduc Date 2022-03-23 Time   Rev Time 0.00
Received By pleduc Date 2022-03-23 Time 12:09 Sent To  
Notes
2022-03-23 12:32:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT
 NAME FOR THE ACTUAL PROPOSED TILE FLOORING.
  
 PER SHEET PROP COND UNDER FLOOR FINISH IT INDICATES
 WITHIN THE MODEL NAME/NUMBER COLUMN FLOOR FINISH T.B.D.
 AND UNDER THE FIRE PERFORMANCE COLUMN INDICATES A
 CRITICAL RADIANT FLUX BUT ALSO A FIRE RESISTIVE WALL,
 WHICH IS NOT APPLICABLE.
  
 TILE FLOORING MAY HAVE DIFFERENT TYPE
 MEANINGS/DEFINITIONS AND IS MANUFACTURED AROUND THE
 WORLD AND NOT ALL ARE TESTED AND MEETING LISTED AND
 NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 PRODUCT NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED FLOORING INDICATING THE FIRE BEHAVIOR
 RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 2) THERE ARE INDICATIONS OF BATHROOM TUB WORK IN TH
 MASTER BATH THAT MAY AFFECT THE FIRE RATED
 TENANT/CORRIDOR SEPARATION WALLS,
  
 ENSURE FIRE RATED TENANT SEPARATION WALLS ARE REPAIRED
 TO THE EXISTING FIRE RATED SEPARATION.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
  
 3) THERE ARE INDICATIONS OF REMOVING A WALL IN THE
 KITCHEN/LIVING AREA.
  
 REMOVAL OF WALLS REQUIRES A CODE COMPLIANT SPRINKLER
 HEAD COVERAGE REVIEW BY A FIRE SPRINKLER CONTRACTOR.
  
 ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT ON THE FLOOR PLAN.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-19 Cont ID  
Sent By fgiaquin Date 2022-05-19 Time 19:42 Rev Time 0.00
Received By fgiaquin Date 2022-05-05 Time 17:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-29 Cont ID  
Sent By shill Date 2022-04-29 Time 14:34 Rev Time 0.00
Received By shill Date 2022-03-22 Time 09:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-04-06 Cont ID  
Sent By medwards Date 2022-04-06 Time 15:22 Rev Time 0.00
Received By medwards Date 2022-04-06 Time 15:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-09 Cont ID  
Sent By rwbrown Date 2022-05-09 Time 15:56 Rev Time 0.00
Received By rwbrown Date 2022-05-09 Time 15:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-04-01 Cont ID  
Sent By lcrespo Date 2022-04-01 Time 15:07 Rev Time 0.00
Received By lcrespo Date 2022-04-01 Time 15:03 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-05-04 Cont ID  
Sent By rgathrig Date 2022-05-04 Time 17:04 Rev Time 0.00
Received By rgathrig Date 2022-05-04 Time 17:04 Sent To  
Notes
2022-05-04 17:05:07PRIVATE PROVIDER INSPECTIONS ONLY APPROVED
 TEW & TAYLOR
  
  
 RICHARD GATHRIGHT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-10 Cont ID  
Sent By rmcphers Date 2022-05-10 Time 11:15 Rev Time 0.00
Received By rmcphers Date 2022-05-10 Time 11:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-28 Cont ID  
Sent By rmcphers Date 2022-04-28 Time 16:19 Rev Time 0.00
Received By rmcphers Date 2022-04-28 Time 16:19 Sent To  
Notes
2022-04-28 16:23:13SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 DESIGNER - FBC WPB 107.2
  
 2) ALL DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON