| 2022-03-21 11:37:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE INDICATIONS OF HALLWAY CEILING REPAIR. |
| | |
| | FORE THE OFFICIAL RECORD, IS IT A REPAIR OR A DEMO AND |
| | REPLACEMENT? |
| | |
| | PLEASE PROVIDE SECIFIC DETAILS. |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF A REPAIR OF A CEILING IN A |
| | HALLWAY. |
| | |
| | THERE IS NO LISTED/SPECIFICATION CALLOUT OF THE |
| | REQUIRED FIRE RATING OF THIS HALLWAY THAT THE REPAIR IS |
| | REQUIRED TO MEET. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE ORIGINAL |
| | FIRE RATING OF THIS HALLWAY AND LISTED REPAIR THAT THE |
| | REPAIR IS REQUIRED TO MEET. |
| | |
| | |
| | 3) THE CEILING WORK MAY INVOLVE THE FIRE SPRINKLER |
| | HEADS IN SOME WAY. |
| | |
| | ANY WORK ON THE FIRE SPRINKLER HEADS/SYTEM EQUIPMENT, |
| | INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE PERMIT & |
| | SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 4) THE CEILING WORK MAY INVOLVE THE FIRE ALARM |
| | EQUIPMENT IN SOME WAY. |
| | |
| | ANY WORK ON THE FIRE ALARM EQUIPMENT, INCLUDING DEMO, |
| | SHALL BE DONE UNDER SEPARATE PERMIT & SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 5) THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE |
| | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |