| 2022-04-08 10:31:07 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL16709-R9 COVERS MULTIPLE ROOF SYSTEM TYPES |
| | A-2 THROUGH E, NO. W-1 THRU W-5. PLEASE SELECT SYSTEM |
| | NO.; EXPOSURE; ENCLOSURE; ROOF HEIGHT; ZONE AND |
| | ULTIMATE WIND SPEED. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING |
| | 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL27499-R3 |
| | HAS BEEN REVISED TO FL27499-R4 PROVIDE A COMPLETE SET; |
| | IT COVERS MULTIPLE INSTALLATION OPTIONS TO MEET DESIGN |
| | UPLIFT PRESSURES. PLEASE SELECT CORRECT INSTALLATION |
| | OPTION FROM PAGE #2 OF THE EVALUATION REPORT THAT MEET |
| | OR EXCEED THE MINIMUM DESIGN PRESSURE REQUIREMENT FOR |
| | ZONE 3 EXPOSURE CATEGORY C AREAS. (-108.17). ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT (TU |
| | PLUS) TO BE USED. INCLUDE COVER PAGE, EVALUATION |
| | REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED. |
| | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |