Plan Review Details - Permit 22030857
Plan Review Stops For Permit 22030857
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-04-18 Cont ID  
Sent By jgomez Date 2022-04-18 Time 11:23 Rev Time 0.00
Received By jgomez Date 2022-04-18 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-04-08 Cont ID  
Sent By jbrooks Date 2022-04-08 Time 10:30 Rev Time 0.00
Received By jbrooks Date 2022-04-08 Time 07:42 Sent To  
Notes
2022-04-08 10:31:07JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R9 COVERS MULTIPLE ROOF SYSTEM TYPES
 A-2 THROUGH E, NO. W-1 THRU W-5. PLEASE SELECT SYSTEM
 NO.; EXPOSURE; ENCLOSURE; ROOF HEIGHT; ZONE AND
 ULTIMATE WIND SPEED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING
 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL27499-R3
 HAS BEEN REVISED TO FL27499-R4 PROVIDE A COMPLETE SET;
 IT COVERS MULTIPLE INSTALLATION OPTIONS TO MEET DESIGN
 UPLIFT PRESSURES. PLEASE SELECT CORRECT INSTALLATION
 OPTION FROM PAGE #2 OF THE EVALUATION REPORT THAT MEET
 OR EXCEED THE MINIMUM DESIGN PRESSURE REQUIREMENT FOR
 ZONE 3 EXPOSURE CATEGORY C AREAS. (-108.17). ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT (TU
 PLUS) TO BE USED. INCLUDE COVER PAGE, EVALUATION
 REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-31 Cont ID  
Sent By jbrooks Date 2022-03-31 Time 10:32 Rev Time 0.00
Received By jbrooks Date 2022-03-31 Time 07:53 Sent To  
Notes
2022-03-31 10:32:58JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R9 SELECTED SYSTEM NO W-1; EXPOSURE
 (B); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H < 15);
 ULTIMATE WIND SPEED (170), IS NOT CORRECT. THE CORRECT
 EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE C. PLEASE
 SELECT THE CORRECT OPTIONS.
 2. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL11651-R3 IS THE 2017 CODE VERSION AND IS NO
 LONGER VALID. PLEASE PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA?S FOR THE PROPOSED
 METAL ROOFING SYSTEM TO BE USED. INCLUDE COVER PAGE,
 EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED.
 3. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL
 SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH
 NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS.
 PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT
 INDICATE ON ROOF DRAWING/SKETCH).
 4. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-18 Cont ID  
Sent By jgomez Date 2022-04-18 Time 11:23 Rev Time 0.00
Received By jgomez Date 2022-04-14 Time 07:01 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-08 Cont ID  
Sent By jbrooks Date 2022-04-08 Time 10:31 Rev Time 0.00
Received By jbrooks Date 2022-04-05 Time 07:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-31 Cont ID  
Sent By jbrooks Date 2022-03-31 Time 10:33 Rev Time 0.00
Received By jbrooks Date 2022-03-30 Time 09:37 Sent To  
Notes
***NONE***