| 2022-04-12 11:47:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22030798 4500 S DIXIE HWY |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.RE: A-4.10 |
| | ***A) DIMENSION SHALL BE TO THE BOTTOM EDGE OF |
| | "REFLECTING SURFACE" PER FBC ACC 603.3. |
| | ***B) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL |
| | AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL PER |
| | FBC ACC 604.5.1. PLEASE NOTE THE OVERALL DIMENSION OF |
| | 54 INCHES MINIMUM FROM THE REAR WALL. |
| | ***C) PER WPB FBC 107.2.1, PLEASE NOTE DIMENSIONS OF |
| | CLEARANCE AROUND THE WATER CLOSET(S); SHALL BE 60 |
| | INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER |
| | CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED |
| | WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL |
| | PER FBC ACC 604.3.1 AND 604.8.1.1. |
| | ***D) URINALS SHALL BE 13 1/2 INCHES DEEP MINIMUM |
| | MEASURED FROM THE OUTER FACE OF THE URINAL RIM TO THE |
| | BACK OF THE FIXTURE PER FBC ACC 605.2 |
| | |
| | 2.PLAN SHEET P-4: |
| | ***A) PER WPB FBC 107.2.1, PLEASE LOCATE AND IDENTIFY |
| | ON THE PLAN, THE EXISTING WATER HEATER. |
| | ***B) ADD TO KEY NOTES THE FOLLOWING STATEMENT; "IF THE |
| | DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, FROM |
| | THE SOURCE OF HOT WATER TO THE FIXTURES THAT REQUIRE |
| | HOT OR TEMPERED WATER, EXCEEDS 50 FEET, A RECIRCULATING |
| | SYSTEM OR HEAT-TRACED SYSTEM SHALL BE INSTALLED TO |
| | PROVIDE COMPLIANCE WITH THE FLORIDA PLUMBING CODE |
| | SECTION 607.2." |
| | ***C) ADD TO THE KEY NOTES THE FOLLOWING STATEMENT: |
| | "PER THE WEST PALM BEACH AMENDMENTS SECTION 107.4, IF A |
| | NEW WATER HEATER AND/OR A NEW HOT WATER RECIRCULATING |
| | OR HEAT-TRACE SYSTEM IS REQUIRED, A PLAN REVISION SHALL |
| | BE SUBMITTED THE BUILDING DEPARTMENT FOR APPROVAL. |
| | APPROVED REVISION SHALL BE ON SITE FOR FINAL |
| | INSPECTION." |
| | |
| | 3.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE |
| | SAME. |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH |
| | A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN |
| | ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 5. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON |
| | THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| | THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW |
| | SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT |
| | AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR |
| | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS |
| | WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR FINAL INSPECTION. WPB FBC 105.11 |
| | |
| | 6. P301 AND P601: THE FOUR NEW SANITARY DRAINS EXITING |
| | THE BUILDING EACH CONSTITUTE AN INDIVIDUAL BUILDING |
| | DRAIN AS DEFINED IN FBC PL CHAPTER 2, SECTION 202. PER |
| | FBC PL 708.1.3, PROVIDE A CLEANOUT ON EACH BUILDING |
| | DRAIN TO SERVICE THE JUNCTION OF THE BUILDING DRAIN AND |
| | BUILDING SEWER. |
| | |
| | 7.P801: PER WPB FBC 107.2.1, PROVIDE A FIXTURE |
| | SCHEDULE/SPECIFICATION LISTING MANUFACTURER, MODEL |
| | NUMBER, TRIM. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |