Plan Review Details - Permit 22030787
Plan Review Stops For Permit 22030787
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-12 Cont ID  
Sent By pvalenti Date 2022-05-12 Time 16:14 Rev Time 0.00
Received By pvalenti Date 2022-05-12 Time 16:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-18 Cont ID  
Sent By pvalenti Date 2022-04-18 Time 07:17 Rev Time 0.00
Received By pvalenti Date 2022-04-18 Time 06:30 Sent To  
Notes
2022-04-18 07:19:28PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 PLEASE PROVIDE THE FLOORING SPECIFICATIONS.
  
 NOTE: THE AREA OF WORK COVERS 832 S.F. AS PER
 APPLICATION. UNDERLAYMENT TEST REPORTS HAVE BEEN ADDED
 TO PROJECT DOX.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-25 Cont ID  
Sent By pleduc Date 2022-04-25 Time   Rev Time 0.00
Received By pleduc Date 2022-04-25 Time 13:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-17 Cont ID  
Sent By pleduc Date 2022-03-17 Time   Rev Time 0.00
Received By pleduc Date 2022-03-17 Time 14:03 Sent To  
Notes
2022-03-17 14:05:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL
 PROPOSED VINYL FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS OF THE PROPOSED FINISHED
 VINYL FLOORING INDICATING THE FIRE BEHAVIOR RATING PER
 THE ABOVE CODE.
  
 2) THERE IS NO FLOOR PLAN SUBMITTED INDICATING THE
 AREAS OF PROPOSED FLOORING.
  
 1.14 PLAN REVIEW.
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 FOR THE OFFICIAL RECORD AND CLARIFICATION, PLEASE
 PROVIDE THE UNIT FLOOR PLAN WITH INDICATIONS OF WHERE
 THE FLOORING IS LOCATED
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-12 Cont ID  
Sent By pvalenti Date 2022-05-12 Time 16:14 Rev Time 0.00
Received By pvalenti Date 2022-04-22 Time 07:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-18 Cont ID  
Sent By pvalenti Date 2022-04-18 Time 07:17 Rev Time 0.00
Received By pvalenti Date 2022-03-16 Time 06:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-04-18 Cont ID  
Sent By pvalenti Date 2022-04-18 Time 07:17 Rev Time 0.00
Received By pvalenti Date 2022-04-18 Time 06:30 Sent To  
Notes
***NONE***