| 2022-03-17 14:05:29 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE |
| | FLOOR UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL |
| | PROPOSED VINYL FLOORING. |
| | |
| | VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT |
| | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT |
| | SPEC SHEETS OF THE PROPOSED FINISHED |
| | VINYL FLOORING INDICATING THE FIRE BEHAVIOR RATING PER |
| | THE ABOVE CODE. |
| | |
| | 2) THERE IS NO FLOOR PLAN SUBMITTED INDICATING THE |
| | AREAS OF PROPOSED FLOORING. |
| | |
| | 1.14 PLAN REVIEW. |
| | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION |
| | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND |
| | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE |
| | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD |
| | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. |
| | |
| | FOR THE OFFICIAL RECORD AND CLARIFICATION, PLEASE |
| | PROVIDE THE UNIT FLOOR PLAN WITH INDICATIONS OF WHERE |
| | THE FLOORING IS LOCATED |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |