Plan Review Details - Permit 22030762
Plan Review Stops For Permit 22030762
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-05-23 Cont ID  
Sent By pvalenti Date 2022-05-23 Time 10:59 Rev Time 0.00
Received By pvalenti Date 2022-05-23 Time 10:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-16 Cont ID  
Sent By jbrooks Date 2022-05-16 Time 08:58 Rev Time 0.00
Received By jbrooks Date 2022-05-16 Time 08:55 Sent To  
Notes
2022-05-16 08:58:481ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. PREVIOUS COMMENTS NOT ADDRESSED.
 2. PLEASE PROVIDE FLOOR PLAN SHOWING EACH OF THE
 OPENINGS. 107.3FBC
 3. IF THE SHUTTERS ARE BEING REMOVED THE PROPOSED
 WINDOW SHALL BE IMPACT PROTECTED. 107.3FBC
 4. PLEASE PROVIDE WIND LOAD CALCULATIONS. 1609FBC
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-26 Cont ID  
Sent By pvalenti Date 2022-04-26 Time 08:00 Rev Time 0.00
Received By pvalenti Date 2022-04-26 Time 07:40 Sent To  
Notes
2022-04-26 08:20:41PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1:
  
 1.) PROVIDE THE COVER SHEETS FOR THE CORRECT PRODUCT
 APPROVAL.
 2.) THE WINDOW SCHEDULE STATES THE MODEL OF WINDOWS
 WILL BE THE 2500 SERIES BUT THE PORTION OF SUBMITTED
 PRODUCT APPROVAL IS NOT FOR THE 2500 SERIES.
 3.) THE SUBMITTED INFORMATION IS FOR NON-IMPACT
 WINDOWS, PLEASE PROVIDE INFORMATION FOR STORM
 PROTECTION (SUCH AS STORM SHUTTER INFORMATION).

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-05-10 Cont ID  
Sent By fmittner Date 2022-05-10 Time 10:17 Rev Time 0.00
Received By fmittner Date 2022-05-10 Time 10:17 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-04-20 Cont ID  
Sent By amhamilt Date 2022-04-20 Time 15:36 Rev Time 0.00
Received By amhamilt Date 2022-04-20 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-16 Cont ID  
Sent By jbrooks Date 2022-05-16 Time 08:58 Rev Time 0.00
Received By jbrooks Date 2022-04-27 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-26 Cont ID  
Sent By pvalenti Date 2022-04-26 Time 08:20 Rev Time 0.00
Received By pvalenti Date 2022-04-07 Time 15:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-04-26 Cont ID  
Sent By pvalenti Date 2022-04-26 Time 08:00 Rev Time 0.00
Received By pvalenti Date 2022-04-26 Time 07:40 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy