Plan Review Details - Permit 22030685
Plan Review Stops For Permit 22030685
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2022-05-12 Cont ID  
Sent By cpuell Date 2022-05-12 Time 16:27 Rev Time 0.00
Received By cpuell Date 2022-05-12 Time 16:27 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-04-14 Cont ID  
Sent By shill Date 2022-04-14 Time 17:23 Rev Time 0.00
Received By shill Date 2022-04-14 Time 17:23 Sent To  
Notes
2022-04-14 17:26:36THIS FLOOR APPEARS TO HAVE AN EXPIRED PERMIT. PLEASE
 RESOLVE. IF WORK WAS NOT DONE, SEND A CANCELLATION
 REQUEST TO [email protected]. IF WORK WAS DONE, EMAIL
 [email protected] TO INQUIRE AS TO HOW TO REOPEN
 THE PERMIT.
  
 12050046 PRINTED COM-REMOD 1700 PALM BEACH LAKES BLVD
 FL G & I IV SOUTHTRUST CENTER LLC 10TH FLOOR REMOVE
 EXISTING DOOR INSTALL NEW
  
 WAS ANY WORK DONE UNDER 12050046 SHOWN AS "EXISTING" IN
 THIS APPLICATION? WE DO NOT CONSIDER IT "EXISTING"
 UNLESS THE PERMIT WAS ISSUED, INSPECTED, CLOSED. THIS
 WILL BE EVALUATED AT TIME OF BUILDING DIVISION AUDIT IF
 12050046 IS STILL IN EXPIRED STATUS.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 15:05 Rev Time 0.00
Received By rmcphers Date 2022-05-02 Time 15:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 15:04 Rev Time 0.00
Received By rmcphers Date 2022-05-02 Time 15:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-05-03 Cont ID  
Sent By mpeterso Date 2022-05-03 Time 10:59 Rev Time 0.00
Received By mpeterso Date 2022-05-03 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-16 Cont ID  
Sent By   Date 2022-05-16 Time   Rev Time 0.00
Received By bdolan Date 2022-05-16 Time 12:06 Sent To  
Notes
2022-05-16 12:06:23THIS PLAN WAS REVIEWED AND APPROVED BY LT. BRIAN DOLAN,
 DIVISION OF FIRE PREVENTION, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL REMAIN
 ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-31 Cont ID  
Sent By   Date 2022-03-31 Time   Rev Time 0.00
Received By bdolan Date 2022-03-31 Time 14:17 Sent To  
Notes
2022-03-31 14:23:05THIS PLAN WAS REVIEWED AND APPROVED BY LT. BRIAN DOLAN,
 DIVISION OF FIRE PREVENTION, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL REMAIN
 ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2022-05-27 Time   Rev Time 0.00
Received By lmarchan Date 2022-05-23 Time 10:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-05-18 Cont ID  
Sent By shill Date 2022-05-18 Time 19:16 Rev Time 0.00
Received By shill Date 2022-05-12 Time 07:24 Sent To  
Notes
2022-05-13 13:11:48NEW PARTITION PLAN, NEEDS FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-09 Cont ID  
Sent By shill Date 2022-05-09 Time 08:43 Rev Time 0.00
Received By shill Date 2022-05-07 Time 10:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-05-03 Time   Rev Time 0.00
Received By lmarchan Date 2022-04-22 Time 15:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-15 Cont ID  
Sent By lmarchan Date 2022-04-15 Time 16:44 Rev Time 0.00
Received By lmarchan Date 2022-03-25 Time 12:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-03-26 Cont ID  
Sent By shill Date 2022-03-26 Time 12:10 Rev Time 0.00
Received By shill Date 2022-03-26 Time 12:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-27 Cont ID  
Sent By medwards Date 2022-05-27 Time 13:13 Rev Time 0.00
Received By medwards Date 2022-05-27 Time 13:13 Sent To  
Notes
2022-05-27 13:13:48MECHANICAL AUDIT ONLY. APPROVED ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-03 Cont ID  
Sent By medwards Date 2022-05-03 Time 10:37 Rev Time 0.00
Received By medwards Date 2022-05-03 Time 10:37 Sent To  
Notes
2022-05-03 10:37:201ST REVIEW FMC
 PERMIT: 22030685
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OUTSIDE AIR CALCULATIONS NOTE 1 INDICATES THE
 CALCULATIONS ARE BASED ON ESTIMATED MAX. OCCUPANCY
 RATES PER ARCHITECTURAL PLANS AND MECHANICAL FBC 2020
 CH-4; VENTILATION RATES PER MECHANICAL FBC 2017 CH-4.
 SOME OF THE AREAS HAVE A LOW OUTDOOR AIR CALCULATION.
 PLEASE CHANGE THE REFERENCE TO THE 2017 CODE AS WE ARE
 CURRENTLY IN THE 2020 FMC. ALSO REMOVE AND DO NOT USE
 THE ARCHITECTURAL ESTIMATED MAX. OCCUPANCY AS THE 2020
 FMC 403.3.1.1 3RD SENTENCE STATES: THE OCCUPANT LOAD
 UTILIZED FOR DESIGN OF THE VENTILATION SYSTEM SHALL BE
 NOT LESS THAN THE NUMBER DETERMINED FROM THE ESTIMATED
 MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE
 403.3.1.1.
  
 2) SHEET M2.1: WHERE IS THE DETAIL SHOWING WHAT KEYNOTE
 1 IS ASKING FOR? IS THIS NEW DUCTWORK IN A SHAFT? FBC
 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-27 Cont ID  
Sent By ccole Date 2022-05-27 Time 14:25 Rev Time 0.00
Received By ccole Date 2022-05-27 Time 14:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-03 Cont ID  
Sent By ccole Date 2022-05-03 Time 15:57 Rev Time 0.00
Received By ccole Date 2022-05-03 Time 15:39 Sent To  
Notes
2022-05-03 15:58:58PLUMBING AUDIT
 PERMIT- 22030685
 5/3/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IA110, IA-801 OR P2.1: CLEAR FLOOR SPACE DIAGRAMS W/
 DIMENSIONS AT THE ACCESSIBLE SINK, DISHWASHER, AND
 REFRIGERATOR NOT PROVIDED- SEC. 606.2 & 804.6 FBC ACC.
  
 2) IA-801: PANTRY EQUIPMENT ITEM #8 NOT SHOWN IN THE
 SCHEDULE- SEC. 107.2.1 WPB.
  
 2) P0.1: LOCATION OF THE REQUIRED DEDICATED SHUT OFF
 VALVE FOR THE IWH UNDER THE SINK NOT SHOWN- SEC 503.1
 FBC P.
  
 3) P0.1: PUBLIC LAVATORY LABELING AT THE SINK DETAIL
 INCORRECT. ACCORDING TO THE PLANS THE SINK IS IN THE
 PANTRY- SEC. 107.2.1 WPB.
  
 4) P0.1: HOT WATER, NOT TEMPERED WATER IS REQUIRED AT
 THE PANTRY SINK. REMOVE THE TEMPERED WATER MIXING VALVE
 AND ALL REFERENCES TO TEMPERED WATER- SECS 419.5 AND
 607.1.2 FBC. PROVIDE A MIXING VALVE THAT WILL LIMIT THE
 HOT WATER TEMPERATURE IN ACCORDANCE WITH SEC. 607.1.1.
  
 5) P2.1: INSTALLATION OF THE NEW DRAINS WILL REQUIRE
 THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
  
 6) P2.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING
 SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR
 SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND
 APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN-
 SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 6 Status F Date 2022-06-07 Cont ID  
Sent By shill Date 2022-06-07 Time 14:44 Rev Time 0.00
Received By shill Date 2022-06-07 Time 14:44 Sent To  
Notes
2022-06-07 14:45:51FS553.791, ELECTRICAL IS NOT WITHIN THE SCOPE OF THE
 BUILDING PLANS EXAMINER'S LICENSE. SHEET IA-310 IS AN
 ELECTRICAL PAGE. PROVIDE AN AFFIDAVIT FROM SOMEONE
 LICENSED FOR THIS SCOPE, CHECK ALL PAGES.
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status P Date 2022-05-25 Cont ID  
Sent By shill Date 2022-05-25 Time 08:29 Rev Time 0.00
Received By shill Date 2022-05-25 Time 08:29 Sent To  
Notes
2022-05-25 08:29:30AFFIDAVITS OK
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status F Date   Cont ID  
Sent By   Date 2022-05-18 Time   Rev Time 0.00
Received By   Date 2022-05-18 Time   Sent To  
Notes
2022-05-18 09:29:21PRIVATE PROVIDER PLAN COMPLIANCE AFFIDAVIT
  
 THE MECHANICAL AND ELECTRICAL AFFIDAVITS ARE MISSING
 THE PLAN DATE OR PLAN REVISION DATE (NEED THE DATE
 SHOWN TO VERIFY THE CORRECT DRAWING HAS BEEN REVIEWED
 AND UP LOADED TO PROJECTDOX)

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2022-05-09 Time   Rev Time 0.00
Received By   Date 2022-05-09 Time   Sent To  
Notes
2022-05-09 08:43:42FS553.791, THE OWNER HAS ELECTED TO USE A PRIVATE
 PROVIDER FOR PLAN REVIEW SERVICES. THE PRIVATE PROVIDER
 IS TO REVIEW THE PLAN AND PROVIDE ACCURATE AFFIDAVITS
 PRIOR TO BUILDING DIVISION AUDIT. PLANS WERE REVISED
 BUT NEW AFFIDAVITS WERE NOT SUBMITTED.
  
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2022-04-27 Cont ID  
Sent By dbattles Date 2022-04-27 Time 08:56 Rev Time 0.00
Received By dbattles Date 2022-04-27 Time 08:56 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-04-15 Cont ID  
Sent By rgathrig Date 2022-04-15 Time 10:52 Rev Time 0.00
Received By rgathrig Date 2022-04-15 Time 10:52 Sent To  
Notes
2022-04-15 10:53:2422030685 1700 PALM BEACH LAKES BLVD FL 10 FLOOR
 PRIVATE PROVIDER REVIEW FAILED.
 THE NOTICE TO BUILDING OFFICIAL LIST ROOP KHIRSUKHANI
 P.E.42242 AS THE PRIVATE PROVIDER AND MTCI PRIVATE
 PROVIDER SERVICES AS THE FIRM.
 THE CERTIFICATE OF INSURANCE PROVIDED LACKS THE
 REQUIRED LANGUAGE FOUND IN 553.791 (4)(B) THAT A
 CERTIFICATE OF INSURANCE MUST DEMONSTRATE THAT
 PROFESSIONAL LIABILITY INSURANCE COVERAGE IS IN PLACE
 FOR THE PRIVATE PROVIDER?S FIRM, THE PRIVATE PROVIDER,
 AND ANY DULY AUTHORIZED REPRESENTATIVE IN THE AMOUNTS
 REQUIRED BY THIS SECTION. IT IS CUSTOMARY TO SEE THIS
 LANGUAGE IN THE ?DESCRIPTION OF OPERATIONS? SECTION ON
 THE CERTIFICATE OF INSURANCE
  
 THERE ARE FOUR PLAN COMPLIANCE AFFIDAVITS SUBMITTED FOR
 THIS PROJECT. THE BUILDING PLAN COMPLIANT AFFIDAVIT IS
 PREPARED BY THE LISTED PRIVATE PROVIDER ON THE NOTICE
 TO BUILDING OFFICIAL. THE THREE OTHER PLAN COMPLIANCE
 AFFIDAVITS ARE SUBMITTED BY TWO OTHER PRIVATE PROVIDERS
 NOT LISTED ON THE NOTICE TO BUILDING OFFICIAL.
 THE BUILDING COMPLIANCE AFFIDAVIT SIGNED BY ROOP
 KHIRSUKHANI DOCUMENTS THE PLAN REVIEW WAS PERFORMED BY
 RYAN ALEXANDER PX1265. SIGN BY ROOP KHIRSUKHANI AS THE
 PRIVATE PROVIDER AS A PROFESSIONAL ENGINEER.
 THE PLUMBING AND MECHANICAL PLAN COMPLIANCE AFFIDAVITS
 ARE SIGNED BY JULIO E. GONZALEZ P.E 37275. MICHAEL
 OGDEN PX 2096 DID THE PLUMBING REVIEW AND MR. GONZALEZ
 DID THE MECHANICAL REVIEW. BOTH AFFIDAVITS SIGNED BY
 MR. GONZALEZ AS A PRIVATE PROVIDER/PROFESSIONAL
 ENGINEER
 THE ELECTRICAL PLAN COMPLIANCE AFFIDAVIT IS SIGNED BY
 CARLOS RODRIGUEZ P.E 65687. KIM WATKINS PX 3232 DID THE
 ELECTRICAL REVIEW. THE AFFIDAVIT IS SIGNED BY MR.
 RODRIGUEZ AS A PRIVATE PROVIDER/PROFESSIONAL ENGINEER
 PLEASE PROVIDE A CORRECTED NOTICE TO BUILDING OFFICIAL
 LISTING ALL THE PRIVATE PROVIDERS PERFORMING PLAN
 REVIEW AND INSPECTION SERVICES, OR YOU COULD HAVE MR.
 ROOP KHIRSUKHANI SIGN ALL THE AFFIDAVITS AS THE PRIVATE
 PROVIDER AS PRESENTED IN THE NOTICE TO BUILDING
 OFFICIAL SUBMITTED.
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-27 Cont ID  
Sent By medwards Date 2022-05-27 Time 13:17 Rev Time 0.00
Received By medwards Date 2022-05-27 Time 13:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-27 Cont ID  
Sent By dbattles Date 2022-04-27 Time 09:09 Rev Time 0.00
Received By dbattles Date 2022-04-27 Time 09:09 Sent To  
Notes
2022-04-27 09:10:10ANY ADDITIONAL SHEETS SUBMITTED AFTER 3/16/22 UPLOAD
 NEED SIGNATURE REVIEW.