| Plan Review Stops For Permit 22030683 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-06 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-06 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2022-10-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-22 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-22 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2022-10-22 11:57:02 | 4TH BUILDING REVIEW | | | | | | CHRISTOPHER S. THROOP, CBO, BU, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | | PREVIOUS COMMENTS. | | | | | | NOTICE: | | | THERE ARE 38 PLAN PAGES IN THE DRAWINGS FOLDER. THE | | | ARCHITECTURAL AND STRUCTURAL DRAWINGS HAVE GENERIC | | | NAMES. PLEASE NAME EACH PLAN PAGE PER STANDARD NAMING | | | CONVENTION. | | | 13 PLAN SHEETS (017 THRU 029 ARE TITLED "SECTIONS". | | | PLEASE IDENTIFY WHAT IS ON EACH PLAN PAGE. | | | | | | 1. | | | | | | 2. | | | | | | 3. | | | | | | | | | 4. | | | | | | | | | 5. PROVIDE PRODUCT APPROVAL OR UL REPORT FOR THE BILCO | | | ACCESS HATCH. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 6. | | | | | | 7. | | | | | | 8. | | | | | | 9. | | | | | | NEW COMMENTS: | | | | | | 10. | | | | | | 11. | | | | | | 12. | | | | | | NEW COMMENTS: | | | | | | 13. PROVIDE A ROOF FRAMING PLAN. SHOW TRUSS LAYOUT AND | | | CONNECTOR SCHEDULE. IDENTIFY WHAT PLAN PAGE IT IS ON. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 14. PROVIDE THE PRODUCT APPROVALS FOR EXTERIOR DOOR | | | D-1. FL37182 PER DOOR SCHEDULE. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 15. FL14998.1 IS FOR NON-IMPACT RATED SLIDING GLASS | | | DOOR. | | | EITHER SUBMIT A CURRENT PRODUCT APPROVAL FOR IMPACT | | | RATED GLAZING OR PROVIDE A SCHEDULE OF OPENING | | | PROTECTIVE DEVICES AND OR ASSEMBLIES. INCLUDE THE | | | PRODUCT APPROVALS OF PROTECTIVE DEVICES USED. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-07-26 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-26 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2022-07-26 14:55:48 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 2ND REVIEW-CONTINUED (SERVER WENT DOWN) | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | | PREVIOUS COMMENTS. | | | | | | NOTICE: | | | THERE ARE 38 PLAN PAGES IN THE DRAWINGS FOLDER. THE | | | ARCHITECTURAL AND STRUCTURAL DRAWINGS HAVE GENERIC | | | NAMES. PLEASE NAME EACH PLAN PAGE PER STANDARD NAMING | | | CONVENTION. | | | | | | 1. | | | | | | 2. | | | | | | 3.PROVIDE ROOF DRAINAGE PLAN. PROVIDE NUMBER AND | | | LOCATION OF DRAINS AND SCUPPERS BASED ON THE ROOF AREA | | | TO BE DRAINED. (IDENTIFY WHAT PLAN PAGE THEY ARE ON) | | | | | | | | | 4.GUTTERS (IDENTIFY WHAT PLAN PAGE THEY ARE ON) | | | | | | | | | 5. THE HIGH ROOF FRAMING PLAN APPEARS TO BE A COPY OF | | | THE 2ND AND 3RD FLOOR FRAMING PLANS. (N0T ADDRESSED) | | | IDENTIFY ROOFTOP ACCESS. (IDENTIFY WHAT PLAN PAGE THEY | | | ARE ON) | | | PROVIDE PRODUCT APPROVAL OR UL REPORT FOR ACCESS HATCH. | | | (BILCO) (IDENTIFY WHAT PLAN PAGE THEY ARE ON) | | | PROVIDE DETAIL OF GUARDRAIL ATTACHMENT. (IDENTIFY WHAT | | | PLAN PAGE THEY ARE ON) | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 6. PRODUCT APPROVAL FL251-R32 HAS EXPIRED. (REMOVE FROM | | | SUBMITTAL) | | | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL | | | OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE | | | PROPOSED EXT. FIBERGLASS DOOR. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 7. ONLY THE EVALUATION REPORT WAS SUBMITTED FOR REVIEW | | | FOR THE EXTERIOR SWINGING DOOR. | | | PROVIDE THE FL PRODUCT APPROVAL COVER SHEETS FOR THE | | | PROPOSED EXT. DOOR. | | | THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE | | | VERSION, AND STATUS, FBC R 301. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 8. PROVIDE PRODUCT APPROVALS FOR THE PROPOSED WINDOWS. | | | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL | | | OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE | | | PROPOSED EXT. FIBERGLASS DOOR. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 9. IDENTIFY CEILING AND WALL INSULATION TYPE AND R | | | VALUE ON PLANS. (IDENTIFY WHAT PLAN PAGE THEY ARE ON) | | | | | | NEW COMMENTS: | | | | | | 10. THE PAGE OF WEB LINKS TO PRODUCT APPROVALS IS NOT | | | AN ACCEPTABLE DOCUMENT. | | | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL | | | OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE | | | PROPOSED WINDOWS AND DOORS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 11. FL14911-R12 (SH WINDOWS) IS FOR NON-IMPACT RATED | | | GLAZING. PROVIDE A SCHEDULE OF OPENING PROTECTIVE | | | DEVICES AND OR ASSEMBLIES. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 12. PRODUCT APPROVALS ON WINDOW AND DOOR SCHEDULE (PG | | | A105) HAVE NOT BEEN SUBMITTEDE FOR REVIEW. | | | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL | | | OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE | | | PROPOSED WINDOWS AND DOORS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-07-26 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-25 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2022-07-26 11:58:35 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | | PREVIOUS COMMENTS. | | | | | | | | | 1. | | | | | | 2. | | | | | | 3.PROVIDE ROOF DRAINAGE PLAN. PROVIDE NUMBER AND | | | LOCATION OF DRAINS AND SCUPPERS BASED ON THE ROOF AREA | | | TO BE DRAINED. | | | | | | 4.GUTTERS | | | | | | 5. THE HIGH ROOF FRAMING PLAN APPEARS TO BE A COPY OF | | | THE 2ND AND 3RD FLOOR FRAMING PLANS. | | | IDENTIFY ROOFTOP ACCESS. | | | PROVIDE PRODUCT APPROVAL OR UL REPORT FOR ACCESS HATCH. | | | (BILCO) | | | PROVIDE DETAIL OF GUARDRAIL ATTACHMENT. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 6. PRODUCT APPROVAL FL251-R32 HAS EXPIRED. | | | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL | | | OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE | | | PROPOSED EXT. FIBERGLASS DOOR. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 7. ONLY THE EVALUATION REPORT WAS SUBMITTED FOR REVIEW | | | FOR THE EXTERIOR SWINGING DOOR. | | | PROVIDE THE FL PRODUCT APPROVAL COVER SHEETS FOR THE | | | PROPOSED EXT. DOOR. | | | THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE | | | VERSION, AND STATUS, FBC R 301. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 8. PROVIDE PRODUCT APPROVALS FOR THE PROPOSED WINDOWS. | | | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL | | | OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE | | | PROPOSED EXT. FIBERGLASS DOOR. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 9. IDENTIFY CEILING AND WALL INSULATION TYPE AND R | | | VALUE ON PLANS. | | | R402.1 GENERAL (PRESCRIPTIVE). | | | THE BUILDING THERMAL ENVELOPE SHALL MEET THE | | | REQUIREMENTS OF SECTIONS R402.1.1 THROUGH R402.1.4. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-02 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-01 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2022-04-02 12:14:10 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: VALUE HAS BEEN INCREASED TO $302,799, PER THE | | | ICC BUILDING VALUATION DATA. | | | | | | 1. THE SOILS REPORT SUBMITTED FOR REVIEW IS FROM THE | | | 1-STORY STRUCTURE UNDER PERMIT 21030578. | | | PROVIDE A SOILS REPORT FOR THE PROPOSED 3-STORY | | | STRUCTURE. | | | R401.4 SOIL TESTS. | | | WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL | | | SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, | | | SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE | | | LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL | | | DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE | | | THE SOILS CHARACTERISTICS AT A PARTICULAR LOCATION. | | | THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN | | | APPROVED METHOD. | | | | | | 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | 2A) IDENTIFY THE LOCATION OF THE UNDERGROUND DRAIN | | | PIPES. | | | 2B) PROVIDE DETAIL OF TERMINAL DEVICES AT SIDEWALK. | | | | | | 3.PROVIDE ROOF DRAINAGE PLAN. PROVIDE NUMBER AND | | | LOCATION OF DRAINS AND SCUPPERS BASED ON THE ROOF AREA | | | TO BE DRAINED. | | | R903.4ROOF DRAINAGE. | | | UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF | | | DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE | | | ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL | | | BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR | | | PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY | | | THE ROOF SLOPE AND CONTRIBUTING ROOF AREA. | | | R903.4.1OVERFLOW DRAINS AND SCUPPERS. | | | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT | | | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR | | | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 | | | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND | | | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED | | | VERTICAL LEADERS OR DOWN-SPOUTS OR WALL AND PARAPET | | | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN | | | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. | | | OVERFLOW DRAINS SHALL DISCHARGE TO AN APPROVED LOCATION | | | AND SHALL NOT BE CONNECTED TO ROOF DRAIN LINES. | | | | | | 4.GUTTERS | | | R903.4.2ONE AND TWO-FAMILY DWELLINGS, AND PRIVATE | | | GARAGES. | | | WHEN GUTTERS AND LEADERS ARE PLACED ON THE OUTSIDE OF | | | BUILDINGS, THE GUTTERS AND LEADERS SHALL BE CONSTRUCTED | | | OF METAL OR APPROVED PLASTIC FOR OUTDOOR EXPOSURE WITH | | | LAPPED, SOLDERED OR CAULKED JOINTS AND SHALL BE | | | SECURELY FASTENED TO THE BUILDING WITH A CORROSION | | | RESISTANT FASTENING DEVICE OF SIMILAR OR COMPATIBLE | | | MATERIAL TO THE GUTTERS AND DOWNSPOUTS. | | | | | | 5. THE HIGH ROOF FRAMING PLAN APPEARS TO BE A COPY OF | | | THE 2ND AND 3RD FLOOR FRAMING PLANS. | | | IDENTIFY ROOFTOP ACCESS. | | | PROVIDE PRODUCT APPROVAL OR UL REPORT FOR ACCESS HATCH. | | | (BILCO) | | | PROVIDE DETAIL OF GUARDRAIL ATTACHMENT. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 6. PRODUCT APPROVAL FL251-R32 HAS EXPIRED. | | | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL | | | OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE | | | PROPOSED EXT. FIBERGLASS DOOR. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 7. ONLY THE EVALUATION REPORT WAS SUBMITTED FOR REVIEW | | | FOR THE EXTERIOR SWINGING DOOR. | | | PROVIDE THE FL PRODUCT APPROVAL COVER SHEETS FOR THE | | | PROPOSED EXT. DOOR. | | | THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE | | | VERSION, AND STATUS, FBC R 301. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 8. PROVIDE PRODUCT APPROVALS FOR THE PROPOSED WINDOWS. | | | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL | | | OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE | | | PROPOSED EXT. FIBERGLASS DOOR. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 9. IDENTIFY CEILING AND WALL INSULATION TYPE AND R | | | VALUE ON PLANS. | | | R402.1 GENERAL (PRESCRIPTIVE). | | | THE BUILDING THERMAL ENVELOPE SHALL MEET THE | | | REQUIREMENTS OF SECTIONS R402.1.1 THROUGH R402.1.4. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2023-01-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-27 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-01-27 |
Time |
08:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-11-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-11-03 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-11-03 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-06-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-06-10 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-06-10 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2022-06-10 08:37:06 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) LAYOUT CHANGED PLEASE PROVIDE A LOAD CALCULATION AND | | | PANRL SCHEDULE FOR UNIT 215.5 | | | | | | 2) KITCHEN COUNTER OUTLETS NOT PER 210.52 | | | | | | 3) OUTLETS AT FRONT AND REAR OF UNIT MISSING. 210.52 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-03-25 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-03-25 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-03-25 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2022-03-25 12:39:16 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | OUTLET SPACING TO MEET 210.52 FOR WALL SPACE. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2023-01-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-25 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-25 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2023-01-25 11:01:20 | SPEARATE PERMIT FOR GAS IS REQUESTED BY OWNER. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-10-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-10-24 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-10-24 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2022-10-24 10:03:10 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 22030683 | | | 10/24/22 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P101: GAS PIPING IS SPECIFIED IN THE PIPE | | | MATERIALS SCHEDULE. PLEASE PROVIDE GAS PLANS OR | | | INDICATE THAT GAS WILL BE INSTALLED UNDER A SEPARATE | | | PERMIT- SEC. 105.1 & 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2023-03-13 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2023-02-28 |
Time |
07:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-02-06 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-24 |
Time |
16:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-11-07 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-10-19 |
Time |
07:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-07-26 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-05-31 |
Time |
12:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-04-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
cdecoeur |
Date |
2022-03-17 |
Time |
07:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-03-21 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-14 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2023-03-21 12:17:57 | NO FEES DUE PER IMPACT. LEM | | 2023-03-14 07:56:49 | 3/14/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-04-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-02 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-02 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2022-04-02 11:17:02 | NOTICE: IMPACT FEE DOCUMENTS SUBMITTED FOR REVIEW ARE | | | FOR THE 1-STORY STRUCTURE UNDER PERMIT 21030578. | | | | | | IMPACT FEE QUESTIONNAIRE | | | | | | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2023-01-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-25 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-25 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-11-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-01 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-01 |
Time |
07:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-06-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-01 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-06-01 08:42:45 | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOWS 2100 | | | TOTAL SQUARE FOOTAGE FOR THIS BUILDING WITH A COOLING | | | BTUH OF 23,409. THIS IS FOR THE ENTIRE BUILDING BUT | | | M101 INDICATES THAT AC-1 IS A 1.5 TON UNIT AND YOU HAVE | | | ONE OF THESE INSTALLED PER FLOOR. PROVIDE MECHANICAL | | | UNITS THAT WOULD BE SIZED PER FLOOR ACCORDING TO THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS. THE | | | MECHANICAL SIZING CALCULATIONS CALL FOR A 2 TON SYSTEM | | | FOR THE ENTIRE ADDITION, WHAT IS SUBMITTED IS A 1.5 TON | | | FOR EACH FLOOR. THIS IS OVER SIZED. | | | | | | FEC R403.7.1.2.1 HEAT PUMPS. HEAT PUMP SIZING SHALL BE | | | BASED ON THE COOLING REQUIREMENTS AS CALCULATED | | | ACCORDING TO SECTION R403.7.1.1, AND THE HEAT PUMP | | | TOTAL COOLING CAPACITY SHALL NOT BE MORE THAN 1.15 | | | TIMES GREATER THAN THE DESIGN COOLING LOAD EVEN IF THE | | | DESIGN HEATING LOAD IS 1.15 TIMES GREATER THAN THE | | | DESIGN COOLING LOAD. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-25 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-25 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2022-03-25 10:53:47 | SHEET M101: THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS SHOW TOTAL HEATING BTUH FOR EACH FLOOR AS | | | 8,293, 4884 AND 5157. AC-1 UNIT DOES NOT SHOW THAT IT | | | HAS HEAT. PLEASE PROVIDE A UNIT THAT MEETS THE HEATING | | | REQUIREMENTS OF FBC RES R304.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-02 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-02 |
Time |
12:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2023-01-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-25 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-25 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2023-01-25 11:30:51 | FBC-2020 RES. PLUMBING | | | PERMIT- 22030683 | | | 1/25/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A102: 2ND REQUEST TO PROVIDE EMERGENCY ROOF | | | SCUPPER LOCATIONS AND OPENING DIMENSIONS- SEC. R903.4.1 | | | FBC RES. | | | | | | 2) SHEET P101 & P104: PLEASE REMOVE THE GREASE | | | INTERCEPTORS EQUIPMENT SCHEDULE AND LOCATION FROM THE | | | PLANS. THIS PROPOSED PROJECT IS AN ADDITION TO A | | | SINGLE-FAMILY RESIDENTIAL HOME (SEE SHEET C101) AND | | | GREASE INTERCEPTORS ARE NOT REQUIRED PER SEC. R101.2 | | | FBC RES. CODE & SEC. 90-125(7) WPB CODE OF ORDINANCES. | | | IF THE INTENTION IS TO CHANGE THE OCCUPANCY OF THE HOME | | | AT A LATER DATE AND INSTALL A GREASE INTERCEPTOR, THEN | | | BOTH THE CHANGE OF OCCUPANCY AND THE GREASE INTERCEPTOR | | | SHALL BE DONE UNDER SEPARATE PERMITS AND COMPLETE PLANS | | | AND SPECIFICATIONS SHALL BE PROVIDED FOR DEVELOPMENT | | | SERVICE DEPARTMENT REVIEW. PLEASE NOTE THE CURRENT PLAN | | | SHOWS THE SANITARY SEWER LINE FROM THE DOMESTIC | | | HOUSEHOLD FIXTURES DRAINING INTO THE GREASE INTERCEPTOR | | | WHICH IS PROHIBITED PER SEC. 1003.3.1 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2022-10-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-10-24 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-10-24 |
Time |
07:08 |
Sent To |
|
|
| Notes |
| 2022-10-24 08:40:49 | FBC-2020 RES. PLUMBING | | | PERMIT- 22030683 | | | 10/24/22 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A102 ROOF DRAINAGE- SEC. R903.4 FBC RES. | | | PLEASE PROVIDE ON THE PLAN: | | | A) RAINFALL RATE. | | | B) SQUARE FOOTAGE OF THE ROOF AND PARAPETS. | | | C) GPM FLOW AT EACH SCUPPER LOCATION. | | | D) SCUPPER DETAIL INCLUDING OPENING DIMENSIONS. | | | E) DOWNSPOUT SIZES. | | | F) EMERGENCY ROOF SCUPPER LOCATIONS AND OPENING | | | DIMENSIONS. | | | FOR FURTHER INFORMATION PLEASE REFER TO SECS. 1105 & | | | 1106 FBC P. | | | | | | 2) SHEETS P105 & SITE DRAWING #200: THE RISER DRAWING | | | ON P105 DOES NOT MATCH THE SITE PLAN SHOWING SEPARATE | | | BUILDING DRAINS FOR THE EXISTING RESIDENCE AND THE | | | 3-STORY ADDITION- SEC. 107.2.1 WPB. THE SITE PLAN | | | SHOULD BE SHOWING TWO-WAY CLEANOUTS AT THE JUNCTIONS OF | | | THE BUILDING DRAINS AND SEWER LINES AT EACH 3-STORY | | | HOUSE LOCATION- SEC. P3005.2.3 & P3005.2.8 FBC RES. | | | | | | 3) SITE DRAWING #200: PLEASE SHOW A HOSE BIB WITH | | | VACCUM BREAKER WILL BE INSTALLED AT THE EXTERIOR WATER | | | FAUCET LOCATION SHOWN ON THE PLAN- SECS. P2902.2 & | | | P2902.4.3 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | 2022-10-22 11:18:17 | COULD NOT VERIFY PLUMBING REVIEWERS STAMP. CT |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-06-01 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-06-01 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-06-01 |
Time |
09:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-03-23 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-03-23 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-03-23 |
Time |
11:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-07-26 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-25 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2022-07-26 11:52:38 | PROVISO ON PLAN PAGE A102: A SEPERATE ROOFING PERMIT IS | | | REQUIRED. CT |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-04-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-02 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-01 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2022-04-02 11:26:12 | ROOFING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: PLANS SPECIFY A FLAT ROOF WITH A TPO COVERING. | | | PRODUCT APPROVALS SUBMITTED FOR REVIEW ARE FOR ASPHALT | | | SHINGLES. | | | | | | 1. ROOFING PERMIT REQUIRED. | | | PERMITS - 105.1 REQUIRED. | | | | | | 2. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER | | | BARRIER PER FBC R905.1.1. | | | UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL | | | CONFORM TO THE APPLICABLE STANDARDS? AND SHALL BE | | | APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION | | | R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE. | | | | | | 3. PROVIDE PRODUCT APPROVALS FOR ROOF COVERINGS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-02 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-02 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-06 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-06 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-10-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-22 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-22 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2022-10-22 11:18:47 | ALL PLAN PAGES. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-07-26 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-25 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2022-06-10 08:38:44 | DIGITAL SIGNATURE APPROVED FOR ELECTRIC JLEAHY | | 2022-06-01 08:44:33 | DIGITAL SIGNATURE FOR MECHANICAL APPROVED ME | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-04-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-02 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-02 |
Time |
06:55 |
Sent To |
|
|
| Notes |
| 2022-03-25 10:55:12 | MECHANICAL DIGITAL SIGNATURES APPROVED. ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2023-03-13 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2023-03-13 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2023-03-13 16:53:36 | 3/12/23- APPROVED. SEPERATE LANDSCAPE AND DRIVEWAY | | | PERMIT REQIRED. | | | | | | ANGELLA VANN, AICP | | | [email protected] | | | 561-822-1441 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2023-02-01 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2023-02-01 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2023-02-01 12:30:07 | 2/1/23- FAILED. PLEASE CORRECT OR RESPOND TO THE | | | FOLLOWING: | | | 1, WHERE IS THE INTERNAL CONNECTION BETWEEN THE STARTER | | | HOUSE AND THE FIST FLOOR ADDITION? IT CAN NOT BE UNDER | | | THE STAIRS. | | | 3. WHAT IS INCLUDED AS PART OF THE WET BAR? REPEAT | | | COMMENT | | | 4. WHY IS A WAHSER AND DRYER IN THE LIVING ROOMS? | | | REPEAT COMMENT | | | 5. WHAT TYPE OF CLOSET IS BEING PROVIDED IN THE LIVING | | | ROOMS OF THE ADDITION? REPEAT COMMENT | | | 6. SPERATE LANDSCAPE PERMIT WILL BE REQUIRED. | | | | | | ANGELLA VANN, AICP | | | 561-822-1441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-10-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2022-10-26 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-26 16:51:54 | 10/26/22- FAILED. PLEASE CORRECT OR RESPOND TO THE | | | FOLLOWING: | | | 1, WHERE IS THE INTERNAL CONNECTION BETWEEN THE STARTER | | | HOUSE AND THE FIST FLOOR ADDITION? IT CAN NOT BE UNDER | | | THE STAIRS. | | | 3. WHAT IS INCLUDED AS PART OF THE WET BAR? REPEAT | | | COMMENT | | | 4. WHY IS A WAHSER AND DRYER IN THE LIVING ROOMS? | | | REPEAT COMMENT | | | 5. WHAT TYPE OF CLOSET IS BEING PROVIDED IN THE LIVING | | | ROOMS OF THE ADDITION? REPEAT COMMENT | | | 6. SPERATE LANDSCAPE PERMIT WILL BE REQUIRED. | | | | | | ANGELLA VANN, AICP | | | 561-822-1441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-06-14 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2022-06-14 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2022-06-14 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2022-06-14 10:24:17 | 6/14/22- FAILED. PLEASE CORRECT OR RESPOND TO THE | | | FOLLOWING: | | | 1, WHERE IS THE INTERNAL CONNECTION BETWEEN THE STARTER | | | HOUSE AND THE FIST FLOOR ADDITION? REPEAT COMMENT | | | 3. WHAT IS INCLUDED AS PART OF THE WET BAR? REPEAT | | | COMMENT | | | 4. WHY IS A WAHSER AND DRYER IN THE LIVING ROOMS? | | | REPEAT COMMENT | | | 5. WHAT TYPE OF CLOSET IS BEING PROVIDED IN THE LIVING | | | ROOMS OF THE ADDITION? REPEAT COMMENT | | | 6. SPERATE LANDSCAPE PERMIT WILL BE REQUIRED. | | | | | | ANGELLA VANN, AICP | | | 561-822-1441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-04-04 |
|
|
Cont ID |
|
| Sent By |
avann |
Date |
2022-04-04 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2022-04-04 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2022-04-04 16:24:56 | 4/4/22- FAILED. PLEASE CORRECT OR RESPOND TO THE | | | FOLLOWING: | | | 1. SHOW THE HEIGHT FROM THE FINISH GRADE OF THE | | | STRUCTURE. | | | 2, WHERE IS THE INTERNAL CONNECTION BETWEEN THE STARTER | | | HOUSE AND THE FIST FLOOR ADDITION? | | | 3. WHAT IS INCLUDED AS PART OF THE WET BAR? | | | 4. WHY IS A WAHSER AND DRYER IN THE LIVING ROOMS? | | | 5. WHAT TYPE OF CLOSET IS BEING PROVIDED IN THE LIVING | | | ROOMS OF THE ADDITION? | | | 6. SPERATE LANDSCAPE PERMIT WILL BE REQUIRED. | | | | | | ANGELLA VANN, AICP | | | 561-822-1441 | | | [email protected] |
|
|