Plan Review Details - Permit 22030597
Plan Review Stops For Permit 22030597
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By rmcphers Date 2022-04-27 Time 15:26 Rev Time 0.00
Received By rmcphers Date 2022-04-27 Time 15:25 Sent To  
Notes
2022-04-27 15:40:19ADD OVERHEAD DOOR -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF
 THE NEW DOOR.
  
 2) PLEASE SHOW THE TIEBEAM OR LINTEL FOR THE MASONRY
 ABOVE THE NEW DOOR OPENING - FBC 1403.3 STRUCTURAL.
 EXTERIOR WALLS, AND THE ASSOCIATED OPENINGS, SHALL BE
 DESIGNED AND CONSTRUCTED TO RESIST SAFELY THE
 SUPERIMPOSED LOADS REQUIRED BY CHAPTER 16. - FBC 1609.1
 APPLICATIONS.
 BUILDINGS, STRUCTURES AND PARTS THEREOF SHALL BE
 DESIGNED TO WITHSTAND THE MINIMUM WIND LOADS PRESCRIBED
 HEREIN. DECREASES IN WIND LOADS SHALL NOT BE MADE FOR
 THE EFFECT OF SHIELDING BY OTHER STRUCTURES. ALL
 EXTERIOR WALL COVERINGS AND SOFFITS SHALL BE CAPABLE OF
 RESISTING THE DESIGN PRESSURES SPECIFIED FOR WALLS FOR
 COMPONENTS AND CLADDING LOADS IN ACCORDANCE WITH
 SECTION 1609.1.1.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-18 Cont ID  
Sent By pleduc Date 2022-03-18 Time   Rev Time 0.00
Received By pleduc Date 2022-03-18 Time 12:18 Sent To  
Notes
2022-03-18 12:25:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS IS INSUFFICIENT INFORMATION PROVIDED TO
 CONDUCT A LIFE SAFETY REVIEW OF THE PROPOSED WORK.
  
 1.7.11 PLANS AND SPECIFICATIONS.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.11.2 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 CONSTRUCTION UNLESS OTHERWISE PERMITTED BY 1.7.11.4.
  
 1.7.11.3 THE CONSTRUCTION DOCUMENTS FOR EACH PHASE
 SHALL BE COMPLETE IN THEMSELVES, SO THAT REVIEW AND
 INSPECTION CAN PROPERLY BE MADE. PRELIMINARY PLANS OF
 THE TOTAL BUILDING SHALL BE SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS, AND WITH SUFFICIENT DETAIL, SO
 THAT PROPER EVALUATION CAN BE MADE. AREAS AND ITEMS NOT
 INCLUDED IN THE PHASE TO BE PERMITTED SHALL BE SHOWN AS
 NOT INCLUDED
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A SITE PLAN
 SHOWING THE EXACT LOCATION OF THE PROPOSED WORK.
  
  
 2) THERE ARE NO INDICATIONS OF FIRE SPRINKLER
 PROTECTION AND AREA SPRINKLER HEADS THAT MAY BE
 OBSTRUCTED WHEN THE GARAGE DOOR IS OPENED.
  
 1.7.11.3 THE CONSTRUCTION DOCUMENTS FOR EACH PHASE
 SHALL BE COMPLETE IN THEMSELVES, SO THAT REVIEW AND
 INSPECTION CAN PROPERLY BE MADE. PRELIMINARY PLANS OF
 THE TOTAL BUILDING SHALL BE SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS, AND WITH SUFFICIENT DETAIL, SO
 THAT PROPER EVALUATION CAN BE MADE. AREAS AND ITEMS NOT
 INCLUDED IN THE PHASE TO BE PERMITTED SHALL BE SHOWN AS
 NOT INCLUDED
  
 PLEASE PROVIDE SPRINKLER HEAD LOCATION DETAIL.
  
  
 2A) THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-27 Cont ID  
Sent By rmcphers Date 2022-04-27 Time 16:02 Rev Time 0.00
Received By rmcphers Date 2022-03-17 Time 10:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By rmcphers Date 2022-04-27 Time 15:41 Rev Time 0.00
Received By rmcphers Date 2022-04-27 Time 15:41 Sent To  
Notes
2022-04-27 16:02:01SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) PROVIDED SIGNED AND SEALED DRAWING DOES NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-25 Cont ID  
Sent By ckimmerl Date 2022-03-25 Time 11:08 Rev Time 0.00
Received By ckimmerl Date 2022-03-25 Time 11:08 Sent To  
Notes
2022-03-25 11:08:19PERMIT SAYS IT IS FOR NEW GARAGE DOOR INSTALL. PLEASE
 PROVIDE ADDITIONAL DIMENSIONED DRAWINGS DETAILING THE
 FULL SCOPE OF WORK. ONLY THE GARAGE BUCK DETAIL DRAWING
 WAS INCLUDED WITH SUBMITTAL:
  
 PLEASE SHOW:
 1. GENERAL SITE PLAN SHOWCASING PROPOSED GARAGE DOOR
 LOCATION ON BUILDING/STRUCTURE.
 2. AREAS OF DEMOLITION/CINDERBLOCK SECTIONS OF
 BUILDING/STRUCTURE BEING REMOVED.
 3. FACADE/FRONTAGE ELEVATIONS.
  