Plan Review Details - Permit 22030591
Plan Review Stops For Permit 22030591
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-07-07 Cont ID  
Sent By jleahy Date 2022-07-07 Time 17:12 Rev Time 0.00
Received By jleahy Date 2022-07-07 Time 17:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-16 Cont ID  
Sent By pleduc Date 2022-06-16 Time   Rev Time 0.00
Received By pleduc Date 2022-06-16 Time 10:48 Sent To  
Notes
2022-06-16 11:58:59FIRE COMMENT:
  
 PER NFPA 90A
  
 6.4 SMOKE DETECTION FOR AUTOMATIC CONTROL
  
 6.4.2 LOCATION
  
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
  
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY OF GREATER THAT 944 L/SEC(2000FT3/MIN.)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OF FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVE A CAPACITY
 GREATER THAN 7080L/SEC(15.000FT3/MIN) AND SERVING MORE
 THAN ONE STORY.
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4 INSTALLATION
  
 6.4.4.1 SMOKE DETECTORS SHALL BE INSTALLED, TESTED, AND
 MAINTAINED IN ACCORDANCE WITH NFPA 72.
  
 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING
 DAMPERS OR FOR HEATING, VENTILATING, AND
 AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED
 TO ACTIVATE THE BUILDING EVACUATION ALARM.
  
 PER NFPA 72, 2016 ED
  
 CHAPTER 21 EMERGENCY CONTROL FUNCTION INTERFACES
 21.7 HEATING, VENTILATING AND AIR-CONDITIONING (HVAC)
 SYSTEMS.
 21.7.1 THE PROVISIONS OF SECTION SHALL APPLY TO THE
 BASIC METHOD BY WHICH A FIRE ALARM SYSTEM INTERFACES
 WITH THE HEATING, VENTILATING, AND AIR-CONDITIONING
 (HVAC) SYSTEM
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-07 Cont ID  
Sent By jleahy Date 2022-07-07 Time 17:12 Rev Time 0.00
Received By jleahy Date 2022-06-15 Time 11:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-06-24 Cont ID  
Sent By medwards Date 2022-06-24 Time 09:34 Rev Time 0.00
Received By medwards Date 2022-06-24 Time 09:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-24 Cont ID  
Sent By medwards Date 2022-06-24 Time 09:34 Rev Time 0.00
Received By medwards Date 2022-06-24 Time 09:34 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved