Plan Review Details - Permit 22030585
Plan Review Stops For Permit 22030585
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-05-16 Cont ID  
Sent By rmcphers Date 2022-05-16 Time 14:09 Rev Time 0.00
Received By rmcphers Date 2022-05-16 Time 14:09 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2022-04-25 Time 17:16 Sent To  
Notes
2022-04-26 08:21:45PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 14:04 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 14:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-16 Cont ID  
Sent By rmcphers Date 2022-05-16 Time 14:07 Rev Time 0.00
Received By rmcphers Date 2022-05-16 Time 14:07 Sent To  
Notes
2022-05-16 14:08:54OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) MEETING ROOM #2 - DRAWINGS DO NOT SHOW AN EGRESS
 DOOR DESIGNATION NUMBER (WHAT IS THE DOOR SIZE?) FBC
 WPB 107.2.3
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2022-04-25 Time 17:16 Sent To  
Notes
2022-04-26 08:33:03OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) MEETING ROOM #2 - DRAWINGS DO NOT SHOW AN EGRESS
 DOOR. FBC WPB 107.2.3
  
 2) DRAWING S0.1 - PLEASE SHOW THE CORRECT ADDRESS. FBC
 WPB 107.2.1
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-11 Cont ID  
Sent By mpeterso Date 2022-04-11 Time 11:56 Rev Time 0.00
Received By mpeterso Date 2022-04-11 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-10-07 Cont ID  
Sent By mpeterso Date 2022-10-07 Time 11:20 Rev Time 0.00
Received By mpeterso Date 2022-10-07 Time 11:20 Sent To  
Notes
2022-10-07 11:22:37THIS WAS SUBMITTED AS AN ELECTRIC SUB NOW CHANGED BY JM
 TO LOW VOLT VOICE AND DATA # 22071296.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-11 Cont ID  
Sent By pleduc Date 2022-05-11 Time   Rev Time 0.00
Received By pleduc Date 2022-05-11 Time 13:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-21 Cont ID  
Sent By pleduc Date 2022-03-21 Time   Rev Time 0.00
Received By pleduc Date 2022-03-17 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2022-05-25 Time 08:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-20 Cont ID  
Sent By medwards Date 2022-05-20 Time 06:33 Rev Time 0.00
Received By medwards Date 2022-05-10 Time 11:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 08:38 Rev Time 0.00
Received By rmcphers Date 2022-03-16 Time 10:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 08:33 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 08:33 Sent To  
Notes
2022-04-26 08:33:43NO CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-20 Cont ID  
Sent By medwards Date 2022-05-20 Time 06:31 Rev Time 0.00
Received By medwards Date 2022-05-20 Time 06:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-01 Cont ID  
Sent By medwards Date 2022-04-01 Time 06:42 Rev Time 0.00
Received By medwards Date 2022-04-01 Time 06:42 Sent To  
Notes
2022-04-01 06:42:241ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22030585
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE IN THIS PROJECT. THERE IS A RECEPTION AREA,
 TEAM ROOMS WHICH APPEAR TO BE NO DIFFERENT THAN THE
 CONFERENCE ROOMS, CONFERENCE ROOMS, LOUNGE AREA,
 OFFICES, BREAK ROOM, COPY/PRINT ROOM, STORAGE ROOM.
 EACH SHOULD HAVE A CALCULATION BASED ON FMC 403.3.1.1
 AND TABLE 403.3.1.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-13 Cont ID  
Sent By ccole Date 2022-05-13 Time 15:04 Rev Time 0.00
Received By ccole Date 2022-05-13 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-24 Cont ID  
Sent By ccole Date 2022-03-24 Time 17:48 Rev Time 0.00
Received By ccole Date 2022-03-24 Time 17:01 Sent To  
Notes
2022-03-24 17:48:481ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22030585
 3/24/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-3.1, P-4.1, P-4.2: THE THERMOSTAT CONTROLS
 FOR THE WATER HEATERS SHALL NOT SERVE AS THE
 TEMPERATURE LIMITING MEANS FOR MAXIMUM ALLOWABLE HOT
 WATER DELIVERY TEMPERATURE AT THE SINKS AND DISHWASHER-
 SEC. 607.1.1 FBC P. PROVIDE MIXING VALVES.
  
 2) P-4.1: PROVIDE FULL OPEN SHUTOFF VALVES FOR THE COLD
 WATER SUPPLY LINES TO THE WATER HEATERS- SEC. 606.1(8)
 FBC P.
  
 3) P-4.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 DISHWASHER- SEC. 409.1 FBC P.
  
 4) P-1.1, P-3.1: WASTE RECEPTORS MAY BE REQUIRED TO
 CONVEY THE DRAINAGE FROM THE ICE MAKER AND SODA/WATER
 DISPENSERS TO THE SANITARY SYSTEM- SEC. 802.4 FBC P.
 PLEASE PROVIDE PRODUCT SUBMITTALS- SEC. 107.2.1 WPB.
  
 5) PROVIDE THE FOLLOWING DETAILS IN ACCORDANCE WITH THE
 FBC ACCESSIBILITY CODE.
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SINKS- SEC. 606.2, 804.4.
  
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 DISHWASHER, ICE MACHINE, AND DISPENSER- SEC. 804.6.1,
 804.6.3.
  
 C) REACH HEIGHTS TO APPLIANCE AND BEVERAGE DISPENSER
 CONTROLS- SEC. 308.1.
  
 D) SHOW OPERABLE CONTROL COMPLIANCE FOR APPLIANCES AND
 DISPENSER- SEC. 804.6.2.
  
 E) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 REFRIGERATOR/FREEZER- SEC. 804.6.6.
 COMBINATION REFRIGERATORS AND FREEZERS SHALL HAVE AT
 LEAST 50 PERCENT OF THE FREEZER SPACE 54 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. THE CLEAR FLOOR OR
 GROUND SPACE SHALL BE POSITIONED FOR A PARALLEL
 APPROACH TO THE SPACE DEDICATED TO A
 REFRIGERATOR/FREEZER WITH THE CENTERLINE OF THE CLEAR
 FLOOR OR GROUND SPACE OFFSET 24 INCHES MAXIMUM FROM THE
 CENTERLINE OF THE DEDICATED SPACE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 14:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-16 Cont ID  
Sent By rmcphers Date 2022-05-16 Time 14:16 Rev Time 0.00
Received By rmcphers Date 2022-05-16 Time 14:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 08:38 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 08:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2022-03-21 Cont ID  
Sent By ckimmerl Date 2022-03-21 Time 08:53 Rev Time 0.00
Received By ckimmerl Date 2022-03-21 Time 08:53 Sent To  
Notes
***NONE***