| Plan Review Stops For Permit 22030579 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-01-10 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-10 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-11-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-23 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-23 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-05 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-05 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2022-10-05 12:14:04 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: ADDITION REMOVED FROM SOW. CHANGED PERMIT TYPE | | | FROM RES-ADD TO RES-REMOD. | | | | | | NEW COMMENTS: | | | | | | 1. NOTE ON FLOOR PLAN STATES: TOP OF NEW SLAB TO BE + | | | 5.8". PLEASE CLARIFY? | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE DEMENSIONS TO PROPERTY LINES ON SITE PLAN. | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | | AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE | | | AND INCLUDED BOUNDARY LINE SURVEY. | | | | | | 3. PROVIDE CEILING AND WALL INSULATION R VALUE ON FLOOR | | | PLAN. 2ND REQUEST. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 4. CORRECT WINDOW AND DOOR SCHEDULE TO REFLECT NOA'S | | | SUBMITTED FOR REVIEW. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 5. PROVIDE CURRENT PRODUCT APPROVALS OR NOA FOR | | | PROPOSED OVERHEAD DOOR. (OHD) | | | PRODUCT APPROVALS INCLUDE THE COVER SHEET, EVALUATION | | | REPORT AND INSTALLATION INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | NOTICE: ADJUSTED VALUE, BASED ON THE REDUCED SOW, | | | REMOVES THE SUBSTANTIAL IMPROVEMENT (S/I) REQUIREMENT | | | UNDER FEMA'S 50% RULE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-27 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-26 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2022-04-27 10:42:31 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | | | | 2. PROVIDE A SOILS REPORT. | | | R401.4 SOIL TESTS. | | | WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL | | | SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, | | | SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE | | | LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL | | | DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE | | | THE SOILS CHARACTERISTICS AT A PARTICULAR LOCATION. | | | THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN | | | APPROVED METHOD. | | | | | | 3. PROVIDE AN ENERGY SUBMITTAL ? RESIDENTIAL (RE) | | | R401.2COMPLIANCE. | | | PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING: | | | 1. 1.SECTIONS R401 THROUGH R404. | | | 2. 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401 | | | THROUGH R404 LABELED ?MANDATORY.? | | | | | | 4. PLACE WALL INSULATION TYPE AND R-VALUE ON PLANS. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 5. PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT | | | APPROVAL OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 | | | FBC, FOR THE PROPOSED WINDOWS AND DOORS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 6. PROVIDE A STRUCTURAL DETAIL OF THE ARCHED OPENINGS | | | ON PROPOSED ADDITION. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 7.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE | | | R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES | | | R301.2.1.1WIND DESIGN REQUIRED. | | | | | | 8.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER | | | CALCULATED DESIGN PRESSURES. | | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | NOTICE: PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA (SFHA). THE VALUE OF WORK ($350,000.00) EXCEEDS | | | 50% OF THE IMPROVEMENT VALUE ($295,328.00) AS STATED ON | | | THE PROPERTY APPRAISERS WEB-SITE. WORK IS CONSIDERED A | | | SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758. | | | | | | PLEASE REFERENCE COMMENTS UNDER THE NFIP REVIEW: SEE | | | BELOW. | | | | | | SUBSTANTIAL IMPROVEMENT PER FEMA P-758, 50% RULE. | | | | | | NOTICE: | | | | | | PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH A BASE | | | FLOOD ELEVATION OF 6.0 FEET NAVD. BASED ON THE VALUE OF | | | THIS SUBMITTAL, THE WORK ON THE PROPERTY IS CONSIDERED | | | A SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758. | | | | | | 2020 FBC EXISTING BUILDING | | | 1201.3FLOOD HAZARD AREAS. | | | IN FLOOD HAZARD AREAS, IF ALL PROPOSED WORK, INCLUDING | | | REPAIRS, WORK REQUIRED BECAUSE OF A CHANGE OF | | | OCCUPANCY, AND ALTERATIONS, CONSTITUTES SUBSTANTIAL | | | IMPROVEMENT, THEN THE BUILDING SHALL COMPLY WITH | | | SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING, OR | | | SECTION R322 OF THE FLORIDA BUILDING CODE, RESIDENTIAL, | | | AS APPLICABLE. | | | | | | CITY ORDINANCE NO. 4658-16 | | | | | | CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16 | | | AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT | | | AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE | | | MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD | | | HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM | | | BEACH, FL. | | | | | | ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON | | | NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM | | | BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A | | | TWO-FOOT FREEBOARD ABOVE THE (BFE). | | | FINISHED FLOOR ELEVATIONS SHALL BE PLACED ON FOUNDATION | | | PLAN AND/OR FLOOR PLAN. | | | | | | 1. PROVIDE AN ELEVATION CERTIFICATE WITH AN ACCURATELY | | | COMPLETED BOUNDY LINE SURVEY. | | | | | | | | | NOTICE: 3 EC S ARE REQUIRED | | | | | | 1. A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | | | | 2.A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE | | | IS REQUIRED AT PLACEMENT OF 1ST FLOOR. | | | | | | 3.A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL | | | GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE | | | BUILDING. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-01-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-06 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-01-06 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-09-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-09-22 |
Time |
02:06 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-09-22 |
Time |
01:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-04-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-04-09 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-04-07 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2022-04-09 07:59:48 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) OUTLETS AT FRONT AND REAR OF BUILDING MISSING 210.52 | | | | | | 2) OUTLET SPACING IN SEVERAL ROOMS DOES NOT MEET 210.52 | | | | | | 3) BATHROOM OUTLETS MISSING 201.52 | | | | | | 210.52(A)(2) WALL SPACE. AS USED IN THIS SECTION, A | | | WALL SPACE SHALL INCLUDE THE FOLLOWING: | | | (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH | | | (INCLUDINGSPACE MEASURED AROUND CORNERS) AND UNBROKEN | | | ALONG THE | | | FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS, | | | FIREPLACES, AND FIXED CABINETS THAT DO NOT HAVE | | | COUNTERTOPS OR SIMILAR | | | WORK SURFACES | | | | | | 210.52(D) BATHROOMS. AT LEAST ONE RECEPTACLE OUTLET | | | SHALL BE INSTALLED IN BATHROOMS WITHIN 900 MM (3 FT) OF | | | THE OUTSIDE EDGE OF | | | EACH BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A | | | WALL OR PARTITION THAT IS ADJACENT TO THE BASIN OR | | | BASIN COUNTERTOP, LOCA? | | | TED ON THE COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE | | | OF THE BASIN CABINET. IN NO CASE SHALL THE RECEPTACLE | | | BE LOCATED MORE | | | THAN 300 MM (12 IN.) BELOW THE TOP OF THE BASIN OR | | | BASIN COUNTERTOP. RECEPTACLE OUTLET ASSEMBLIES LISTED | | | FOR USE IN COUNTERTOPS | | | SHALL BE PERMITTED TO BE INSTALLED IN THE COUNTERTOP. | | | | | | 210.52(E)(1) ONE-FAMILY AND TWO-FAMILY DWELLINGS. FOR A | | | ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY | | | DWELLING THAT IS AT GRADE | | | LEVEL, AT LEAST ONE RECEPTACLE OUTLET READILY | | | ACCESSIBLE FROM GRADE AND NOT MORE THAN 2.0 M (6 1?2 | | | FT) ABOVE GRADE LEVEL SHALL | | | BE INSTALLED AT THE FRONT AND BACK OF THE DWELLING. | | | | | | FBC R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE | | | BUILDING OR AN ADDITION TO AN EXISTING BUILDING FOR | | | WHICH A PERMIT | | | FOR NEW CONSTRUCTION IS ISSUED AND HAVING A | | | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, | | | AN ATTACHED GARAGE, OR | | | OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON | | | MONOXIDE AS BYPRODUCT OF COMBUSTION SHALL HAVE AN | | | OPERATIONAL CARBON | | | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM | | | USED FOR SLEEPING PURPOSES. | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2022-12-27 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-12-27 |
Time |
07:14 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2022-10-29 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-29 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-29 09:03:29 | 3RD GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2413.3 - FOR SIZING THE GAS LINE, YOU NEED | | | TO PROVIDE THE LINE PRESSURES THAT YOU ARE USING FOR | | | SIZING. INCLUDE THE REFERENCE FOR THE TABLE FROM THE | | | FUEL GAS CODE. | | | | | | FYI - RANGES DO NOT REQUIRE SEDIMENT TRAPS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-01 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-09-01 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2022-09-01 09:39:44 | 2ND GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2413.3 - FOR SIZING THE GAS LINE, YOU NEED | | | TO PROVIDE THE LINE PRESSURES THAT YOU ARE USING FOR | | | SIZING. INCLUDE THE REFERENCE FOR THE TABLE FROM THE | | | FUEL GAS CODE. | | | | | | FYI - RANGES DO NOT REQUIRE SEDIMENT TRAPS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-03-15 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-03-15 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2022-03-15 15:40:06 | 03/15/22 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. WOULD YOU PLEASE SUBMIT THE ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE | | | PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. INCLUDE | | | PIPE LENGTHS, BTU LOADS, AND DISTANCES TO THE | | | APPLIANCES THAT WERE USED TO CALCULATE MINIMUM PIPE | | | SIZES USING THE SIZING TABLES FROM THE 2020 FGC 402/FBC | | | RES G2413. (INCLUDE REFERENCES TO THE TABLE(S) USED) | | | | | | 2. THIS TANKLESS UNIT CALL FOR A 10.5? WATER COLUMN, | | | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN | | | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE | | | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S | | | SPECIFICATIONS FOR THE PRESSURE REGULATORS IF | | | APPLICABLE. REGULATORS INSTALLED ON THE EXTERIOR OF THE | | | BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER | | | THE 2020 FBC RES. SEC. G2421.1 OR 410.1. | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS | | | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC | | | FG SEC. 402.4.1 OR 2020 FBC RES. SEC. G2413.4.1. | | | | | | | | | 4. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR | | | NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 5. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE | | | PLAN PER THE 2020 FBC FG SEC. 402.2 OR 2020 FBC RES. | | | SEC. G2413.2. | | | | | | 6. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS | | | FOR GAS TANKLESS, GRILL BBQ, RANGE, FIREPLACE, AND GAS | | | LIGHTS EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC | | | RES. SEC. G2408.1. GAS APPLIANCES SHALL BE LISTED AND | | | LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION PER THE 2020 FBC RES. SEC. G2413.2 AND | | | G2404.3. | | | | | | 7. IF UTILITIES PROVIDE A REGULATOR, NO SPECIFICATIONS | | | ARE REQUIRED BUT SUBMIT THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE PRESSURE REGULATORS INSTALLED AT | | | TANKLESS OR ANY OTHER LOCATION. REGULATORS INSTALLED ON | | | THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR | | | OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC. | | | G2421.1. A REGULATOR IS REQUIRED TO BRING THE SYSTEM | | | DOWN TO 10.5 WC ON THE HEART, BUT THE FPU REGULATOR MAY | | | STEP DOWN FOR THIS SYSTEM. | | | | | | 8. WOULD YOU PLEASE SHOW ON THE HOUSE PLAN THE LOCATION | | | OF THE TANK-LESS WATER HEATER AND THE LOCATION AND | | | DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION | | | TO THE WATER HEATER? THE LOCATION OF THE WATER HEATER | | | SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE | | | WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | 9. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE | | | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE | | | 403.5.3. WOULD YOU PLEASE NOTE ON PLANS. IF APPLICABLE. | | | | | | 10. CONDENSATE FOR TANKLESS NEEDS TO BE 1' AWAY FROM | | | THE STRUCTURE PER THE 2020 FBC SEC. R318.5. IF | | | APPLICABLE. WOULD YOU PLEASE NOTE ON PLANS. IF | | | APPLICABLE. | | | | | | 11. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVES | | | AND DRIP LEGS ON GAS ISOMERIC PER THE 2020 FBC RES. | | | SEC. G2420.5. | | | | | | 12. WOULD YOU PLEASE SHOW COMPLIANCE FOR ELECTRICAL | | | BONDING PER 2020 FGC 310/FBC RES G2411. | | | | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON | | | REQUEST. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-01-10 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-12-21 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-11-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-11-23 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-27 |
Time |
15:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-05 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-30 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-27 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-14 |
Time |
05:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-27 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-27 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2022-04-27 09:53:25 | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2022-12-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-22 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-22 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2022-12-22 14:46:41 | PLEASE ADDRESS THE COMMENT FROM THE PREVIOUS REVIEW | | | CYCLE BELOW: | | | | | | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS PROJECT OR PROVIDE A COMPLETED LIKE FOR LIKE | | | CHANGE OUT FORM FOR THE AHU. FEC R403.7.1 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-11-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-04 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-04 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2022-11-04 10:03:50 | 2ND REVIEW FMC | | | PERMIT: 22030579 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-8: NOTE 1 APPEARS TO BE MISSING FROM THE | | | KEYNOTES. PROVIDE A PLAN THAT INCLUDES THIS NOTE. FBC | | | 107.3.5 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS PROJECT. FEC R403.7.1 | | | | | | 3) PROVIDE THE NEW BATH EXHAUST FAN CFM???S AND SHOW | | | THE BATH EXHAUST FAN ON THE DRAWING ALONG WITH THE | | | TERMINATION LOCATION. FRC R303.3 | | | | | | 4) SHOW THE RETURN AIR PATH FROM ALL ROOMS WITH DOORS | | | BACK TO THE AHU. FRC M1602.3 | | | | | | 5) IT APPEARS THE NEW AHU IS LOCATED IN THE MIDDLE OF | | | THE FLOOR IN THE GARAGE, IS THIS STILL TO BE A CAR | | | GARAGE? WILL THE AHU BE PROTECTED? | | | | | | 6) THERE AE DUCTS AND DIFFUSERS THAT APPEAR TO BE | | | INSTALLED IN WALLS, PLEASE SHOW THESE IN THE ROOMS THAT | | | THEY ARE MEANT TO BE INSTALLED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-02 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-02 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2022-09-02 12:04:46 | THE SCOPE OF WORK FOR THE MECHANICAL DESIGN IS STATED | | | ON SHEET A-8. NOTE 1 STATES THAT THE MECHANICAL WORK | | | INVOLVES THE ADDITION OR 2 MINI SPLIT UNITS TO AUGMENT | | | EXISTING. IS THIS THE ENTIRE SCOPE OF WORK? THE DRAWING | | | INDICATES DUCTWORK, IS THIS EXISTING DUCT WORK OR NEW | | | DUCTWORK? CLEARLY IDENTIFY ON THIS DRAWING THE LOCATION | | | OF THE INTERIOR UNIT FOR THE MINI SPLIT SYSTEM. CLEARLY | | | LOCATION THE CONDENSING UNIT FOR THE NEW MINI SPLIT | | | SYSTEMS. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-28 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-28 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2022-03-28 15:49:26 | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS PROJECT. FEC R403.7 | | | | | | PLEASE SHOW THE DUCT SIZES FOR TH DUCTWORK BEING MOVED. | | | FBC 107.2.1 | | | | | | PLEASE SHOW THE NEW MECHANICAL UNITS ON THE MECHANICAL | | | DRAWING, THIS SHOULD INCLUDE THE CONCENSING UNITS AND | | | CONDENSATE DRAINAGE LOCATION. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
N |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-06 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-06 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2022-10-06 15:07:16 | 3RD NFIP REVIEW: | | | ADJUSTED VALUE, BASED ON THE REDUCED SOW, REMOVES THE | | | SUBSTANTIAL IMPROVEMENT (S/I) REQUIREMENT UNDER FEMA'S | | | 50% RULE. CT |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-05 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-05 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2022-10-05 12:26:10 | NFIP REVIEW | | | | | | 2ND REQUEST | | | | | | SUBSTANTIAL IMPROVEMENT PER FEMA P-758, 50% RULE. | | | NOTICE: PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA (SFHA). THE VALUE OF WORK ($350,000.00) EXCEEDS | | | 50% OF THE IMPROVEMENT VALUE ($295,328.00) AS STATED ON | | | THE PROPERTY APPRAISERS WEB-SITE. WORK IS CONSIDERED A | | | SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758. | | | | | | | | | NOTICE: | | | | | | PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH A BASE | | | FLOOD ELEVATION OF 6.0 FEET NAVD. BASED ON THE VALUE OF | | | THIS SUBMITTAL, THE WORK ON THE PROPERTY IS CONSIDERED | | | A SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758. | | | | | | 2020 FBC EXISTING BUILDING | | | 1201.3FLOOD HAZARD AREAS. | | | IN FLOOD HAZARD AREAS, IF ALL PROPOSED WORK, INCLUDING | | | REPAIRS, WORK REQUIRED BECAUSE OF A CHANGE OF | | | OCCUPANCY, AND ALTERATIONS, CONSTITUTES SUBSTANTIAL | | | IMPROVEMENT, THEN THE BUILDING SHALL COMPLY WITH | | | SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING, OR | | | SECTION R322 OF THE FLORIDA BUILDING CODE, RESIDENTIAL, | | | AS APPLICABLE. | | | | | | CITY ORDINANCE NO. 4658-16 | | | | | | CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16 | | | AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT | | | AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE | | | MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD | | | HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM | | | BEACH, FL. | | | | | | ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON | | | NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM | | | BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A | | | TWO-FOOT FREEBOARD ABOVE THE (BFE). | | | FINISHED FLOOR ELEVATIONS SHALL BE PLACED ON FOUNDATION | | | PLAN AND/OR FLOOR PLAN. | | | | | | 1. PROVIDE AN ELEVATION CERTIFICATE WITH AN ACCURATELY | | | COMPLETED BOUNDY LINE SURVEY. (2ND REQUEST) | | | | | | NOTICE: 3 EC S ARE REQUIRED | | | | | | 1. A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | | | | 2.A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE | | | IS REQUIRED AT PLACEMENT OF 1ST FLOOR. | | | | | | 3.A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL | | | GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE | | | BUILDING. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-27 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-27 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2022-04-27 10:13:10 | SUBSTANTIAL IMPROVEMENT PER FEMA P-758, 50% RULE. | | | | | | NOTICE: | | | | | | PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH A BASE | | | FLOOD ELEVATION OF 6.0 FEET NAVD. BASED ON THE VALUE OF | | | THIS SUBMITTAL, THE WORK ON THE PROPERTY IS CONSIDERED | | | A SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758. | | | | | | 2020 FBC EXISTING BUILDING | | | 1201.3FLOOD HAZARD AREAS. | | | IN FLOOD HAZARD AREAS, IF ALL PROPOSED WORK, INCLUDING | | | REPAIRS, WORK REQUIRED BECAUSE OF A CHANGE OF | | | OCCUPANCY, AND ALTERATIONS, CONSTITUTES SUBSTANTIAL | | | IMPROVEMENT, THEN THE BUILDING SHALL COMPLY WITH | | | SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING, OR | | | SECTION R322 OF THE FLORIDA BUILDING CODE, RESIDENTIAL, | | | AS APPLICABLE. | | | | | | CITY ORDINANCE NO. 4658-16 | | | | | | CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16 | | | AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT | | | AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE | | | MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD | | | HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM | | | BEACH, FL. | | | | | | ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON | | | NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM | | | BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A | | | TWO-FOOT FREEBOARD ABOVE THE (BFE). | | | FINISHED FLOOR ELEVATIONS SHALL BE PLACED ON FOUNDATION | | | PLAN AND/OR FLOOR PLAN. | | | | | | 1. PROVIDE AN ELEVATION CERTIFICATE WITH AN ACCURATELY | | | COMPLETED BOUNDY LINE SURVEY. | | | | | | | | | NOTICE: 3 EC S ARE REQUIRED | | | | | | 1. A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | | | | 2.A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE | | | IS REQUIRED AT PLACEMENT OF 1ST FLOOR. | | | | | | 3.A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL | | | GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE | | | BUILDING. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-12-27 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-12-27 |
Time |
07:14 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2022-10-29 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-29 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-29 08:59:31 | 3RD PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - YOUR DIAGRAM FOR THE | | | DWV IS NOT IN ISOMETRIC FORM. PLEASE RECONFIGURE THE | | | DRAWING TO BE IN A TYPICAL ISOMETRIC CONFIGURATION. THE | | | ISOMETRIC SHOULD INCLUDE PIPE SIZES WHERE NEEDED. THE | | | ISOMETRIC SHOULD INDICATE DIRECTIONAL FLOW. | | | | | | 2. 2020 FRC P3108.1 - THE CONFIGURATION OF THE FIXTURE | | | DRAIN CONNECTIONS DO NOT COMPLY WITH THE CODE. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-01 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-09-01 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2022-09-01 09:31:37 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - YOUR DIAGRAM FOR THE | | | DWV IS NOT IN ISOMETRIC FORM. PLEASE RECONFIGURE THE | | | DRAWING TO BE IN A TYPICAL ISOMETRIC CONFIGURATION. THE | | | ISOMETRIC SHOULD INCLUDE PIPE SIZES WHERE NEEDED. THE | | | ISOMETRIC SHOULD INDICATE DIRECTIONAL FLOW. | | | | | | 2. 2020 FRC P3108.1 - THE CONFIGURATION OF THE FIXTURE | | | DRAIN CONNECTIONS DO NOT COMPLY WITH THE CODE. TWO | | | TRAPS ON THE HIGH SIDE OF THE VENTED FIXTURE CONNECTION | | | IS NOT ALLOWED. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-03-15 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-03-15 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2022-03-15 15:13:18 | 03/15/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED | | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | | TO THE FBC SEC. 105.1. | | | | | | 2. ON SHEET A-8; | | | | | | A. THE SANITARY ISOMETRIC DIAGRAM IS HARD TO READ AS IT | | | DOES NOT MATCH THE FLOOR PLAN. WOULD YOU PLEASE CORRECT | | | TO MATCH PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. | | | 107.3.5.3 (12) RESIDENTIAL PLUMBING? | | | | | | B. IT DOES NOT SHOW THE WASHING MACHINE ON THE FLAT | | | PLANS, BUT YOU HAVE IT SHOWN ON ISOMETRIC, AND THERE IS | | | A SHOWER THAT IS NOT VENTED CORRECTLY. WOULD YOU PLEASE | | | SHOW AND LABEL PER THE WPB AMENDMENTS TO THE FBC SEC. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENT? | | | | | | C. THE ORIENTATION OF THE LAVS AND OTHER FIXTURES IS | | | CHALLENGING TO MATCH. WOULD YOU PLEASE CORRECT PER THE | | | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | D. THE WASHING MACHINE AND LAUNDRY ARE NOT VENTED | | | CORRECTLY. WOULD YOU PLEASE CORRECT PER THE WPB | | | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | E. THE RESTROOM WITH THE THREE LAVS LOOKS LIKE THE | | | WATER CLOSET HAS A DRY VENT ON A WET VENT PER THE FBC | | | 2020 R P3108.2.1 HORIZONTAL WET VENT. | | | | | | F. WOULD YOU PLEASE LABEL ALL BATHROOMS PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | G. WOULD YOU PLEASE PROVIDE A SCOPE OF WORK ON WHAT THE | | | PLUMBING WORK CONSISTS OF PER THE WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | H. PIPES SIZES ARE MISSING ON THE ISOMETRIC. WOULD YOU | | | PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE FBC | | | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | I. ON SHEET A-3, IT DOES NOT MATCH THE FLOOR PLAN A-8 | | | IN THE LAUNDRY ROOM. WOULD YOU PLEASE CORRECT PER THE | | | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON | | | REQUEST. | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-27 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-26 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2022-04-27 09:52:28 | PROVISO ON PLAN PAGE A6: A SEPERATE ROOFING PERMIT IS | | | REQUIRED. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-12-30 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-30 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-12-30 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2022-12-30 08:50:35 | 12/30/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS | | | PASSED AND ROUTED TO STORAGE.MP |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-11-03 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-03 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-03 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2022-11-03 12:31:02 | 11/3/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS | | | PASSED AND ROUTED TO STORAGE.MP |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-05 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-05 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2022-10-05 12:23:20 | SIGNATURE REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 CFM | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC2017 | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | | SIGNATURE. | | | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR | | | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH | | | 61G1-16 AND 61G15, F.A.C. | | | | | | | | | 2. UPLOAD DOCUMENTS WITH VALID DIGITAL SIGNATURES. | | | INCLUDE SURVEY. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-27 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-26 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2022-04-27 09:54:13 | SIGNATURE REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 CFM | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC2017 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | | SIGNATURE. | | | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR | | | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH | | | 61G1-16 AND 61G15, F.A.C. | | | | | | SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
N |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-11-17 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-11-17 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2022-11-17 16:35:07 | ADDITION REMOVED FROM SCOPE OF WORK. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-09-08 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-09-08 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-09-08 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2022-09-08 10:50:41 | 9/8/2022 FAILED | | | | | | THE SIDE SETBACKS DO NOT MEET THE REQUIRMENT PER THE | | | ZONING LAND REGUALTIONS CODE SECTION 94-72 (A)(2): | | | | | | MINIMUM SETBACKS FOR PRINCIPAL BUILDING. | | | FRONT: 25 FEET; | | | CORNER: 12.5 FEET; | | | REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER IS | | | LESS; | | | SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | MAXIMUM BUILDING HEIGHT: 30 FEET. | | | | | | | | | PLEASE SHOW THE LENGTH OF THE STRCTURE ON THE EXISITING | | | FLOOR PLAN SHEET 002 A-2 | | | | | | IT IS UNCLEAR IF PROJECT INCLUDES EXTENSIONS OF THE | | | STRUCTURE, PLEASE EMAIL ME WITH A RESPONSE OR PROVIDE A | | | WRITTEN RESPONSE UPLOADED WITH THE PERMIT | | | | | | **** REVIEWD BY **** | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2022-03-30 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-03-30 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-03-18 |
Time |
11:49 |
Sent To |
|
|
| Notes |
|
|