Plan Review Details - Permit 22030579
Plan Review Stops For Permit 22030579
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-01-10 Cont ID  
Sent By cthroop Date 2023-01-10 Time 15:59 Rev Time 0.00
Received By cthroop Date 2023-01-10 Time 15:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-11-23 Cont ID  
Sent By cthroop Date 2022-11-23 Time 16:31 Rev Time 0.00
Received By cthroop Date 2022-11-23 Time 15:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-05 Cont ID  
Sent By cthroop Date 2022-10-05 Time 11:20 Rev Time 0.00
Received By cthroop Date 2022-10-05 Time 09:33 Sent To  
Notes
2022-10-05 12:14:04PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: ADDITION REMOVED FROM SOW. CHANGED PERMIT TYPE
 FROM RES-ADD TO RES-REMOD.
  
 NEW COMMENTS:
  
 1. NOTE ON FLOOR PLAN STATES: TOP OF NEW SLAB TO BE +
 5.8". PLEASE CLARIFY?
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE DEMENSIONS TO PROPERTY LINES ON SITE PLAN.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE
 AND INCLUDED BOUNDARY LINE SURVEY.
  
 3. PROVIDE CEILING AND WALL INSULATION R VALUE ON FLOOR
 PLAN. 2ND REQUEST.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. CORRECT WINDOW AND DOOR SCHEDULE TO REFLECT NOA'S
 SUBMITTED FOR REVIEW.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 5. PROVIDE CURRENT PRODUCT APPROVALS OR NOA FOR
 PROPOSED OVERHEAD DOOR. (OHD)
 PRODUCT APPROVALS INCLUDE THE COVER SHEET, EVALUATION
 REPORT AND INSTALLATION INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
 NOTICE: ADJUSTED VALUE, BASED ON THE REDUCED SOW,
 REMOVES THE SUBSTANTIAL IMPROVEMENT (S/I) REQUIREMENT
 UNDER FEMA'S 50% RULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By cthroop Date 2022-04-27 Time 10:13 Rev Time 0.00
Received By cthroop Date 2022-04-26 Time 15:45 Sent To  
Notes
2022-04-27 10:42:31PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 2. PROVIDE A SOILS REPORT.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOILS CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 3. PROVIDE AN ENERGY SUBMITTAL ? RESIDENTIAL (RE)
 R401.2COMPLIANCE.
 PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. 1.SECTIONS R401 THROUGH R404.
 2. 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED ?MANDATORY.?
  
 4. PLACE WALL INSULATION TYPE AND R-VALUE ON PLANS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 5. PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA, APPROVED UNDER THE 2020
 FBC, FOR THE PROPOSED WINDOWS AND DOORS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 6. PROVIDE A STRUCTURAL DETAIL OF THE ARCHED OPENINGS
 ON PROPOSED ADDITION.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 7.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE
 R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES
 R301.2.1.1WIND DESIGN REQUIRED.
  
 8.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER
 CALCULATED DESIGN PRESSURES.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
 NOTICE: PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE VALUE OF WORK ($350,000.00) EXCEEDS
 50% OF THE IMPROVEMENT VALUE ($295,328.00) AS STATED ON
 THE PROPERTY APPRAISERS WEB-SITE. WORK IS CONSIDERED A
 SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758.
  
 PLEASE REFERENCE COMMENTS UNDER THE NFIP REVIEW: SEE
 BELOW.
  
 SUBSTANTIAL IMPROVEMENT PER FEMA P-758, 50% RULE.
  
 NOTICE:
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH A BASE
 FLOOD ELEVATION OF 6.0 FEET NAVD. BASED ON THE VALUE OF
 THIS SUBMITTAL, THE WORK ON THE PROPERTY IS CONSIDERED
 A SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758.
  
 2020 FBC EXISTING BUILDING
 1201.3FLOOD HAZARD AREAS.
 IN FLOOD HAZARD AREAS, IF ALL PROPOSED WORK, INCLUDING
 REPAIRS, WORK REQUIRED BECAUSE OF A CHANGE OF
 OCCUPANCY, AND ALTERATIONS, CONSTITUTES SUBSTANTIAL
 IMPROVEMENT, THEN THE BUILDING SHALL COMPLY WITH
 SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING, OR
 SECTION R322 OF THE FLORIDA BUILDING CODE, RESIDENTIAL,
 AS APPLICABLE.
  
 CITY ORDINANCE NO. 4658-16
  
 CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16
 AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT
 AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE
 MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD
 HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM
 BEACH, FL.
  
 ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON
 NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM
 BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A
 TWO-FOOT FREEBOARD ABOVE THE (BFE).
 FINISHED FLOOR ELEVATIONS SHALL BE PLACED ON FOUNDATION
 PLAN AND/OR FLOOR PLAN.
  
 1. PROVIDE AN ELEVATION CERTIFICATE WITH AN ACCURATELY
 COMPLETED BOUNDY LINE SURVEY.
  
  
 NOTICE: 3 EC S ARE REQUIRED
  
 1. A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 2.A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE
 IS REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 3.A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-01-06 Cont ID  
Sent By jleahy Date 2023-01-06 Time 10:01 Rev Time 0.00
Received By jleahy Date 2023-01-06 Time 09:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By jleahy Date 2022-09-22 Time 02:06 Rev Time 0.00
Received By jleahy Date 2022-09-22 Time 01:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-09 Cont ID  
Sent By jleahy Date 2022-04-09 Time 07:44 Rev Time 0.00
Received By jleahy Date 2022-04-07 Time 12:23 Sent To  
Notes
2022-04-09 07:59:48FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) OUTLETS AT FRONT AND REAR OF BUILDING MISSING 210.52
  
 2) OUTLET SPACING IN SEVERAL ROOMS DOES NOT MEET 210.52
  
 3) BATHROOM OUTLETS MISSING 201.52
  
 210.52(A)(2) WALL SPACE. AS USED IN THIS SECTION, A
 WALL SPACE SHALL INCLUDE THE FOLLOWING:
 (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH
 (INCLUDINGSPACE MEASURED AROUND CORNERS) AND UNBROKEN
 ALONG THE
 FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES, AND FIXED CABINETS THAT DO NOT HAVE
 COUNTERTOPS OR SIMILAR
 WORK SURFACES
  
 210.52(D) BATHROOMS. AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED IN BATHROOMS WITHIN 900 MM (3 FT) OF
 THE OUTSIDE EDGE OF
 EACH BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A
 WALL OR PARTITION THAT IS ADJACENT TO THE BASIN OR
 BASIN COUNTERTOP, LOCA?
 TED ON THE COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE
 OF THE BASIN CABINET. IN NO CASE SHALL THE RECEPTACLE
 BE LOCATED MORE
 THAN 300 MM (12 IN.) BELOW THE TOP OF THE BASIN OR
 BASIN COUNTERTOP. RECEPTACLE OUTLET ASSEMBLIES LISTED
 FOR USE IN COUNTERTOPS
 SHALL BE PERMITTED TO BE INSTALLED IN THE COUNTERTOP.
  
 210.52(E)(1) ONE-FAMILY AND TWO-FAMILY DWELLINGS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET READILY
 ACCESSIBLE FROM GRADE AND NOT MORE THAN 2.0 M (6 1?2
 FT) ABOVE GRADE LEVEL SHALL
 BE INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
  
 FBC R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE
 BUILDING OR AN ADDITION TO AN EXISTING BUILDING FOR
 WHICH A PERMIT
 FOR NEW CONSTRUCTION IS ISSUED AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 AN ATTACHED GARAGE, OR
 OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON
 MONOXIDE AS BYPRODUCT OF COMBUSTION SHALL HAVE AN
 OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2022-12-27 Cont ID  
Sent By rwbrown Date 2022-12-27 Time 07:14 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2022-10-29 Cont ID  
Sent By rwbrown Date 2022-10-29 Time 09:03 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-10-29 09:03:293RD GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2413.3 - FOR SIZING THE GAS LINE, YOU NEED
 TO PROVIDE THE LINE PRESSURES THAT YOU ARE USING FOR
 SIZING. INCLUDE THE REFERENCE FOR THE TABLE FROM THE
 FUEL GAS CODE.
  
 FYI - RANGES DO NOT REQUIRE SEDIMENT TRAPS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-09-01 Cont ID  
Sent By rwbrown Date 2022-09-01 Time 09:37 Rev Time 0.00
Received By rwbrown Date 2022-09-01 Time 09:37 Sent To  
Notes
2022-09-01 09:39:442ND GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2413.3 - FOR SIZING THE GAS LINE, YOU NEED
 TO PROVIDE THE LINE PRESSURES THAT YOU ARE USING FOR
 SIZING. INCLUDE THE REFERENCE FOR THE TABLE FROM THE
 FUEL GAS CODE.
  
 FYI - RANGES DO NOT REQUIRE SEDIMENT TRAPS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-03-15 Cont ID  
Sent By lcrespo Date 2022-03-15 Time 15:39 Rev Time 0.00
Received By lcrespo Date 2022-03-15 Time 15:39 Sent To  
Notes
2022-03-15 15:40:0603/15/22 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT THE ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. INCLUDE
 PIPE LENGTHS, BTU LOADS, AND DISTANCES TO THE
 APPLIANCES THAT WERE USED TO CALCULATE MINIMUM PIPE
 SIZES USING THE SIZING TABLES FROM THE 2020 FGC 402/FBC
 RES G2413. (INCLUDE REFERENCES TO THE TABLE(S) USED)
  
 2. THIS TANKLESS UNIT CALL FOR A 10.5? WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS IF
 APPLICABLE. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER
 THE 2020 FBC RES. SEC. G2421.1 OR 410.1.
  
 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 FG SEC. 402.4.1 OR 2020 FBC RES. SEC. G2413.4.1.
  
  
 4. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE
 PLAN PER THE 2020 FBC FG SEC. 402.2 OR 2020 FBC RES.
 SEC. G2413.2.
  
 6. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS
 FOR GAS TANKLESS, GRILL BBQ, RANGE, FIREPLACE, AND GAS
 LIGHTS EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC
 RES. SEC. G2408.1. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER THE 2020 FBC RES. SEC. G2413.2 AND
 G2404.3.
  
 7. IF UTILITIES PROVIDE A REGULATOR, NO SPECIFICATIONS
 ARE REQUIRED BUT SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS INSTALLED AT
 TANKLESS OR ANY OTHER LOCATION. REGULATORS INSTALLED ON
 THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
 OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC.
 G2421.1. A REGULATOR IS REQUIRED TO BRING THE SYSTEM
 DOWN TO 10.5 WC ON THE HEART, BUT THE FPU REGULATOR MAY
 STEP DOWN FOR THIS SYSTEM.
  
 8. WOULD YOU PLEASE SHOW ON THE HOUSE PLAN THE LOCATION
 OF THE TANK-LESS WATER HEATER AND THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER? THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 9. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. WOULD YOU PLEASE NOTE ON PLANS. IF APPLICABLE.
  
 10. CONDENSATE FOR TANKLESS NEEDS TO BE 1' AWAY FROM
 THE STRUCTURE PER THE 2020 FBC SEC. R318.5. IF
 APPLICABLE. WOULD YOU PLEASE NOTE ON PLANS. IF
 APPLICABLE.
  
 11. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVES
 AND DRIP LEGS ON GAS ISOMERIC PER THE 2020 FBC RES.
 SEC. G2420.5.
  
 12. WOULD YOU PLEASE SHOW COMPLIANCE FOR ELECTRICAL
 BONDING PER 2020 FGC 310/FBC RES G2411.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-10 Cont ID  
Sent By cthroop Date 2023-01-10 Time 15:59 Rev Time 0.00
Received By cthroop Date 2022-12-21 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-23 Cont ID  
Sent By cthroop Date 2022-11-23 Time 16:32 Rev Time 0.00
Received By cthroop Date 2022-10-27 Time 15:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-05 Cont ID  
Sent By cthroop Date 2022-10-05 Time 12:27 Rev Time 0.00
Received By cthroop Date 2022-08-30 Time 15:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-27 Cont ID  
Sent By cthroop Date 2022-04-27 Time 10:42 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 05:50 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By cthroop Date 2022-04-27 Time 09:52 Rev Time 0.00
Received By cthroop Date 2022-04-27 Time 09:52 Sent To  
Notes
2022-04-27 09:53:25PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2022-12-22 Cont ID  
Sent By medwards Date 2022-12-22 Time 14:45 Rev Time 0.00
Received By medwards Date 2022-12-22 Time 14:45 Sent To  
Notes
2022-12-22 14:46:41PLEASE ADDRESS THE COMMENT FROM THE PREVIOUS REVIEW
 CYCLE BELOW:
  
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS PROJECT OR PROVIDE A COMPLETED LIKE FOR LIKE
 CHANGE OUT FORM FOR THE AHU. FEC R403.7.1
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-11-04 Cont ID  
Sent By medwards Date 2022-11-04 Time 10:03 Rev Time 0.00
Received By medwards Date 2022-11-04 Time 10:03 Sent To  
Notes
2022-11-04 10:03:502ND REVIEW FMC
 PERMIT: 22030579
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-8: NOTE 1 APPEARS TO BE MISSING FROM THE
 KEYNOTES. PROVIDE A PLAN THAT INCLUDES THIS NOTE. FBC
 107.3.5
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS PROJECT. FEC R403.7.1
  
 3) PROVIDE THE NEW BATH EXHAUST FAN CFM???S AND SHOW
 THE BATH EXHAUST FAN ON THE DRAWING ALONG WITH THE
 TERMINATION LOCATION. FRC R303.3
  
 4) SHOW THE RETURN AIR PATH FROM ALL ROOMS WITH DOORS
 BACK TO THE AHU. FRC M1602.3
  
 5) IT APPEARS THE NEW AHU IS LOCATED IN THE MIDDLE OF
 THE FLOOR IN THE GARAGE, IS THIS STILL TO BE A CAR
 GARAGE? WILL THE AHU BE PROTECTED?
  
 6) THERE AE DUCTS AND DIFFUSERS THAT APPEAR TO BE
 INSTALLED IN WALLS, PLEASE SHOW THESE IN THE ROOMS THAT
 THEY ARE MEANT TO BE INSTALLED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-09-02 Cont ID  
Sent By medwards Date 2022-09-02 Time 11:21 Rev Time 0.00
Received By medwards Date 2022-09-02 Time 11:21 Sent To  
Notes
2022-09-02 12:04:46THE SCOPE OF WORK FOR THE MECHANICAL DESIGN IS STATED
 ON SHEET A-8. NOTE 1 STATES THAT THE MECHANICAL WORK
 INVOLVES THE ADDITION OR 2 MINI SPLIT UNITS TO AUGMENT
 EXISTING. IS THIS THE ENTIRE SCOPE OF WORK? THE DRAWING
 INDICATES DUCTWORK, IS THIS EXISTING DUCT WORK OR NEW
 DUCTWORK? CLEARLY IDENTIFY ON THIS DRAWING THE LOCATION
 OF THE INTERIOR UNIT FOR THE MINI SPLIT SYSTEM. CLEARLY
 LOCATION THE CONDENSING UNIT FOR THE NEW MINI SPLIT
 SYSTEMS. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-28 Cont ID  
Sent By medwards Date 2022-03-28 Time 15:45 Rev Time 0.00
Received By medwards Date 2022-03-28 Time 15:45 Sent To  
Notes
2022-03-28 15:49:26PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS PROJECT. FEC R403.7
  
 PLEASE SHOW THE DUCT SIZES FOR TH DUCTWORK BEING MOVED.
 FBC 107.2.1
  
 PLEASE SHOW THE NEW MECHANICAL UNITS ON THE MECHANICAL
 DRAWING, THIS SHOULD INCLUDE THE CONCENSING UNITS AND
 CONDENSATE DRAINAGE LOCATION. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status N Date 2022-10-06 Cont ID  
Sent By cthroop Date 2022-10-06 Time 15:05 Rev Time 0.00
Received By cthroop Date 2022-10-06 Time 14:25 Sent To  
Notes
2022-10-06 15:07:163RD NFIP REVIEW:
 ADJUSTED VALUE, BASED ON THE REDUCED SOW, REMOVES THE
 SUBSTANTIAL IMPROVEMENT (S/I) REQUIREMENT UNDER FEMA'S
 50% RULE. CT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-10-05 Cont ID  
Sent By cthroop Date 2022-10-05 Time 12:24 Rev Time 0.00
Received By cthroop Date 2022-10-05 Time 09:33 Sent To  
Notes
2022-10-05 12:26:10NFIP REVIEW
  
 2ND REQUEST
  
 SUBSTANTIAL IMPROVEMENT PER FEMA P-758, 50% RULE.
 NOTICE: PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE VALUE OF WORK ($350,000.00) EXCEEDS
 50% OF THE IMPROVEMENT VALUE ($295,328.00) AS STATED ON
 THE PROPERTY APPRAISERS WEB-SITE. WORK IS CONSIDERED A
 SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758.
  
  
 NOTICE:
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH A BASE
 FLOOD ELEVATION OF 6.0 FEET NAVD. BASED ON THE VALUE OF
 THIS SUBMITTAL, THE WORK ON THE PROPERTY IS CONSIDERED
 A SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758.
  
 2020 FBC EXISTING BUILDING
 1201.3FLOOD HAZARD AREAS.
 IN FLOOD HAZARD AREAS, IF ALL PROPOSED WORK, INCLUDING
 REPAIRS, WORK REQUIRED BECAUSE OF A CHANGE OF
 OCCUPANCY, AND ALTERATIONS, CONSTITUTES SUBSTANTIAL
 IMPROVEMENT, THEN THE BUILDING SHALL COMPLY WITH
 SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING, OR
 SECTION R322 OF THE FLORIDA BUILDING CODE, RESIDENTIAL,
 AS APPLICABLE.
  
 CITY ORDINANCE NO. 4658-16
  
 CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16
 AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT
 AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE
 MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD
 HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM
 BEACH, FL.
  
 ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON
 NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM
 BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A
 TWO-FOOT FREEBOARD ABOVE THE (BFE).
 FINISHED FLOOR ELEVATIONS SHALL BE PLACED ON FOUNDATION
 PLAN AND/OR FLOOR PLAN.
  
 1. PROVIDE AN ELEVATION CERTIFICATE WITH AN ACCURATELY
 COMPLETED BOUNDY LINE SURVEY. (2ND REQUEST)
  
 NOTICE: 3 EC S ARE REQUIRED
  
 1. A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 2.A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE
 IS REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 3.A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By cthroop Date 2022-04-27 Time 09:54 Rev Time 0.00
Received By cthroop Date 2022-04-27 Time 08:57 Sent To  
Notes
2022-04-27 10:13:10SUBSTANTIAL IMPROVEMENT PER FEMA P-758, 50% RULE.
  
 NOTICE:
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH A BASE
 FLOOD ELEVATION OF 6.0 FEET NAVD. BASED ON THE VALUE OF
 THIS SUBMITTAL, THE WORK ON THE PROPERTY IS CONSIDERED
 A SUBSTANTIAL IMPROVEMENT (S/I) PER FEMA P-758.
  
 2020 FBC EXISTING BUILDING
 1201.3FLOOD HAZARD AREAS.
 IN FLOOD HAZARD AREAS, IF ALL PROPOSED WORK, INCLUDING
 REPAIRS, WORK REQUIRED BECAUSE OF A CHANGE OF
 OCCUPANCY, AND ALTERATIONS, CONSTITUTES SUBSTANTIAL
 IMPROVEMENT, THEN THE BUILDING SHALL COMPLY WITH
 SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING, OR
 SECTION R322 OF THE FLORIDA BUILDING CODE, RESIDENTIAL,
 AS APPLICABLE.
  
 CITY ORDINANCE NO. 4658-16
  
 CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16
 AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT
 AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE
 MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD
 HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM
 BEACH, FL.
  
 ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON
 NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM
 BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A
 TWO-FOOT FREEBOARD ABOVE THE (BFE).
 FINISHED FLOOR ELEVATIONS SHALL BE PLACED ON FOUNDATION
 PLAN AND/OR FLOOR PLAN.
  
 1. PROVIDE AN ELEVATION CERTIFICATE WITH AN ACCURATELY
 COMPLETED BOUNDY LINE SURVEY.
  
  
 NOTICE: 3 EC S ARE REQUIRED
  
 1. A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 2.A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE
 IS REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 3.A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-12-27 Cont ID  
Sent By rwbrown Date 2022-12-27 Time 07:14 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-10-29 Cont ID  
Sent By rwbrown Date 2022-10-29 Time 08:59 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-10-29 08:59:313RD PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - YOUR DIAGRAM FOR THE
 DWV IS NOT IN ISOMETRIC FORM. PLEASE RECONFIGURE THE
 DRAWING TO BE IN A TYPICAL ISOMETRIC CONFIGURATION. THE
 ISOMETRIC SHOULD INCLUDE PIPE SIZES WHERE NEEDED. THE
 ISOMETRIC SHOULD INDICATE DIRECTIONAL FLOW.
  
 2. 2020 FRC P3108.1 - THE CONFIGURATION OF THE FIXTURE
 DRAIN CONNECTIONS DO NOT COMPLY WITH THE CODE.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-09-01 Cont ID  
Sent By rwbrown Date 2022-09-01 Time 07:53 Rev Time 0.00
Received By rwbrown Date 2022-09-01 Time 07:53 Sent To  
Notes
2022-09-01 09:31:372ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - YOUR DIAGRAM FOR THE
 DWV IS NOT IN ISOMETRIC FORM. PLEASE RECONFIGURE THE
 DRAWING TO BE IN A TYPICAL ISOMETRIC CONFIGURATION. THE
 ISOMETRIC SHOULD INCLUDE PIPE SIZES WHERE NEEDED. THE
 ISOMETRIC SHOULD INDICATE DIRECTIONAL FLOW.
  
 2. 2020 FRC P3108.1 - THE CONFIGURATION OF THE FIXTURE
 DRAIN CONNECTIONS DO NOT COMPLY WITH THE CODE. TWO
 TRAPS ON THE HIGH SIDE OF THE VENTED FIXTURE CONNECTION
 IS NOT ALLOWED.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-15 Cont ID  
Sent By lcrespo Date 2022-03-15 Time 15:12 Rev Time 0.00
Received By lcrespo Date 2022-03-15 Time 11:40 Sent To  
Notes
2022-03-15 15:13:1803/15/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. ON SHEET A-8;
  
 A. THE SANITARY ISOMETRIC DIAGRAM IS HARD TO READ AS IT
 DOES NOT MATCH THE FLOOR PLAN. WOULD YOU PLEASE CORRECT
 TO MATCH PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (12) RESIDENTIAL PLUMBING?
  
 B. IT DOES NOT SHOW THE WASHING MACHINE ON THE FLAT
 PLANS, BUT YOU HAVE IT SHOWN ON ISOMETRIC, AND THERE IS
 A SHOWER THAT IS NOT VENTED CORRECTLY. WOULD YOU PLEASE
 SHOW AND LABEL PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENT?
  
 C. THE ORIENTATION OF THE LAVS AND OTHER FIXTURES IS
 CHALLENGING TO MATCH. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. THE WASHING MACHINE AND LAUNDRY ARE NOT VENTED
 CORRECTLY. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. THE RESTROOM WITH THE THREE LAVS LOOKS LIKE THE
 WATER CLOSET HAS A DRY VENT ON A WET VENT PER THE FBC
 2020 R P3108.2.1 HORIZONTAL WET VENT.
  
 F. WOULD YOU PLEASE LABEL ALL BATHROOMS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 G. WOULD YOU PLEASE PROVIDE A SCOPE OF WORK ON WHAT THE
 PLUMBING WORK CONSISTS OF PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 H. PIPES SIZES ARE MISSING ON THE ISOMETRIC. WOULD YOU
 PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 I. ON SHEET A-3, IT DOES NOT MATCH THE FLOOR PLAN A-8
 IN THE LAUNDRY ROOM. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-04-27 Cont ID  
Sent By cthroop Date 2022-04-27 Time 09:51 Rev Time 0.00
Received By cthroop Date 2022-04-26 Time 15:45 Sent To  
Notes
2022-04-27 09:52:28PROVISO ON PLAN PAGE A6: A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-12-30 Cont ID  
Sent By mpeterso Date 2022-12-30 Time 08:49 Rev Time 0.00
Received By mpeterso Date 2022-12-30 Time 08:46 Sent To  
Notes
2022-12-30 08:50:3512/30/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS
 PASSED AND ROUTED TO STORAGE.MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-11-03 Cont ID  
Sent By mpeterso Date 2022-11-03 Time 12:30 Rev Time 0.00
Received By mpeterso Date 2022-11-03 Time 12:29 Sent To  
Notes
2022-11-03 12:31:0211/3/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS
 PASSED AND ROUTED TO STORAGE.MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-10-05 Cont ID  
Sent By cthroop Date 2022-10-05 Time 12:20 Rev Time 0.00
Received By cthroop Date 2022-10-05 Time 09:33 Sent To  
Notes
2022-10-05 12:23:20SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 CFM
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 2ND REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
  
  
 2. UPLOAD DOCUMENTS WITH VALID DIGITAL SIGNATURES.
 INCLUDE SURVEY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By cthroop Date 2022-04-27 Time 09:53 Rev Time 0.00
Received By cthroop Date 2022-04-26 Time 15:46 Sent To  
Notes
2022-04-27 09:54:13SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 CFM
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
  
 SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE.
  

Review Stop Z ZONING
Rev No 3 Status N Date 2022-11-17 Cont ID  
Sent By vbroglia Date 2022-11-17 Time 16:34 Rev Time 0.00
Received By vbroglia Date 2022-11-17 Time 16:34 Sent To  
Notes
2022-11-17 16:35:07ADDITION REMOVED FROM SCOPE OF WORK.

Review Stop Z ZONING
Rev No 2 Status F Date 2022-09-08 Cont ID  
Sent By vbroglia Date 2022-09-08 Time 10:41 Rev Time 0.00
Received By vbroglia Date 2022-09-08 Time 10:41 Sent To  
Notes
2022-09-08 10:50:419/8/2022 FAILED
  
 THE SIDE SETBACKS DO NOT MEET THE REQUIRMENT PER THE
 ZONING LAND REGUALTIONS CODE SECTION 94-72 (A)(2):
  
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
 FRONT: 25 FEET;
 CORNER: 12.5 FEET;
 REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER IS
 LESS;
 SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
 MAXIMUM BUILDING HEIGHT: 30 FEET.
  
  
 PLEASE SHOW THE LENGTH OF THE STRCTURE ON THE EXISITING
 FLOOR PLAN SHEET 002 A-2
  
 IT IS UNCLEAR IF PROJECT INCLUDES EXTENSIONS OF THE
 STRUCTURE, PLEASE EMAIL ME WITH A RESPONSE OR PROVIDE A
 WRITTEN RESPONSE UPLOADED WITH THE PERMIT
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-03-30 Cont ID  
Sent By vbroglia Date 2022-03-30 Time 11:49 Rev Time 0.00
Received By vbroglia Date 2022-03-18 Time 11:49 Sent To  
Notes
2022-03-18 11:51:19 
  
  
  


Account Summary | Usage Policy | Privacy Policy