Plan Review Details - Permit 22030526
Plan Review Stops For Permit 22030526
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-06-21 Cont ID  
Sent By rmcphers Date 2022-06-21 Time 15:46 Rev Time 0.00
Received By rmcphers Date 2022-06-21 Time 15:46 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-04-28 Cont ID  
Sent By rmcphers Date 2022-04-28 Time 15:13 Rev Time 0.00
Received By rmcphers Date 2022-04-28 Time 15:13 Sent To  
Notes
2022-04-28 15:14:05PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 14:46 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 14:46 Sent To  
Notes
2022-04-14 14:46:41PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-06-21 Cont ID  
Sent By rmcphers Date 2022-06-21 Time 15:47 Rev Time 0.00
Received By rmcphers Date 2022-06-21 Time 15:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-28 Cont ID  
Sent By rmcphers Date 2022-04-28 Time 15:14 Rev Time 0.00
Received By rmcphers Date 2022-04-28 Time 15:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 14:49 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 14:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By jleahy Date 2022-05-18 Time 11:40 Rev Time 0.00
Received By jleahy Date 2022-05-17 Time 09:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-13 Cont ID  
Sent By jleahy Date 2022-04-13 Time 16:50 Rev Time 0.00
Received By jleahy Date 2022-04-13 Time 16:44 Sent To  
Notes
2022-04-13 16:51:03FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL WORK SHOWN ON PLANS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-27 Cont ID  
Sent By pleduc Date 2022-04-27 Time   Rev Time 0.00
Received By pleduc Date 2022-04-27 Time 14:28 Sent To  
Notes
2022-04-27 14:29:39FIRE PROVISO:
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS REQUIRE
 MODIFICATIONS AS A RESULT OF THE PROPOSED WORK.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-25 Cont ID  
Sent By pleduc Date 2022-03-25 Time   Rev Time 0.00
Received By pleduc Date 2022-03-25 Time 10:35 Sent To  
Notes
2022-03-25 11:47:04FIRE PROVISO:
  
 THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS REQUIRE
 MODIFICATIONS AS A RESULT OF THE PROPOSED WORK.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-21 Cont ID  
Sent By rmcphers Date 2022-06-21 Time 15:47 Rev Time 0.00
Received By rmcphers Date 2022-06-13 Time 13:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-18 Cont ID  
Sent By jleahy Date 2022-05-18 Time 11:40 Rev Time 0.00
Received By jleahy Date 2022-04-26 Time 06:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 15:02 Rev Time 0.00
Received By rmcphers Date 2022-03-24 Time 10:59 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 15:00 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 15:00 Sent To  
Notes
2022-04-14 15:01:15NO CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-04 Cont ID  
Sent By medwards Date 2022-05-04 Time 13:37 Rev Time 0.00
Received By medwards Date 2022-05-04 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-08 Cont ID  
Sent By medwards Date 2022-04-08 Time 12:24 Rev Time 0.00
Received By medwards Date 2022-04-08 Time 12:24 Sent To  
Notes
2022-04-08 12:24:311ST REVIEW FMC
 PERMIT: 22030526
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1.1 INDICATES THAT THE EXHAUST AIR DEVICES
 AND DUCTWORK TO BE REMOVED. SHEET M-2.1 IS SHOWING THIS
 AS EXISTING. PLEASE SHOW THE NEW DUCTWORK AND DEVICES.
 FBC 107.2.1
  
 2) SHEET M-2.1 PLEASE ADD DUCT AND GRILLE SIZES TO THE
 DRAWING ALONG WITH THE CFM?S AT EACH. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-28 Cont ID  
Sent By jesmith Date 2022-04-28 Time 12:40 Rev Time 0.00
Received By jesmith Date 2022-04-28 Time 11:28 Sent To  
Notes
2022-04-28 12:40:0522030526 295 LAKEVIEW AVE
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 REQUIRED DRINKING FOUNTAIN IS EXISTING AND LOCATION
 COMPLIES WITH FPC 403.5. SEE PLAN SHEET A2.01
  
  
 PROVISO: SEE PLAN SHEET A2.07
 TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET TO THE
 CENTERLINE OF THE DISPENSER. FAC 604.8
  
 CLARIFICATION: SEE PLAN SHEET A2.07
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE. FAC
 609.4
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-05 Cont ID  
Sent By jesmith Date 2022-04-05 Time 14:10 Rev Time 0.00
Received By jesmith Date 2022-03-31 Time 16:11 Sent To  
Notes
2022-04-05 14:05:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22030526 295 LAKEVIEW AVE
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. REGARDING A2.01/SCOPE OF DEMOLITION NOTE 13, PER WPB
 FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC CHAPTERS
 2, 3 AND 6 PROVIDE DETAILS OR NOTES FOR REFINISHED
 TOILET ROOMS INDICATING THE FOLLOWING:
 ***A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL
 OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
 ***B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER
 CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR
 WALL.PER FBC ACC 604.3.1 AND 604.8.1.1.
 ***C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 ***D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ***E) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ***F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 ***G) INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS
 PER FBC ACC 604.8.
 ***H) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS SHALL
 NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER FBC
 ACC 604.4.
 ***I) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ***J) URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG
 TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP
 MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL RIM
 TO THE BACK OF THE FIXTURE PER FBC ACC 605.2
 ***K) LAVATORIES SHALL BE INSTALLED WITH THE FRONT OF
 THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC
 606.3, ADDITIONALLY TOE AND KNEE CLEARANCE SHALL BE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 ***L) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ***M) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 ***N) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
  
 2. IS THERE A CHANGE OF OCCUPANCY? PER WPB FBC 107.2.1,
 PROVIDE OCCUPANCY AND LOAD.
  
 3. PER WPB FBC 107.2.1, PROVIDE PLUMBING FIXTURE
 SCHEDULE (INCLUSIVE OF ALL NEW AND EXISTING FIXTURES)
 SHOWING COMPLIANCE WITH OCCUPANCY TYPE ACCORDING TO FBC
 PL 403.1 AND TABLE 403. PLEASE NOTE, A SERVICE SINK IS
 PROBABLY A REQUIREMENT. IF THERE IS AN EXISTING SERVICE
 SINK, PLEASE INDICATE ON THE PLANS. IF NOT, PROVIDE AS
 WOULD BE REQUIRED BY FBC PL TABLE 403.1.
  
 4. RE: PFL-1.1/PLUMBING DEMOLITION KEY NOTE 4, PER WPB
 FBC 107.2.1, PROVIDE THE FOLLOWING:
 ***A) PLAN SHEET NUMBER SHOWING THE NEW LOCATION OF THE
 HOSE BIBB
 ***B) PLAN VIEW ROUTING AND RISER DIAGRAM OF EXTENDED
 PIPING; PROVIDE SIZE AND MATERIAL TYPE.
 ***C) PROVIDE A VACUUM BREAKER PER FBC PL 608.1/TABLE
 608.1.
 ***D) PROVIDE A SHUTOFF VALVE PER FBC PL 606.2(2).
 ***E) PROVIDE A HANGER DETAIL WITH A NOTE STATING,
 "HORIZONTAL PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH
 FBC PL TABLE 308.5."
  
 5. PER WPB FBC 107.2.1, PROVIDE TYPICAL DETAIL FOR
 CAPPING OF ABANDONED PLUMBING PIPING (SANITARY DRAINS,
 VENTS AND WATER)
  
 6. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS FOR THE PLUMBING WORK THAT IS TO BE REMOVED
 AND CAPPED BELOW THE FLOOR AS NOTED ON PFL-1.1 AND
 A2.01. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 7. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-04-28 Cont ID  
Sent By rmcphers Date 2022-04-28 Time 15:18 Rev Time 0.00
Received By rmcphers Date 2022-04-28 Time 15:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 15:00 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 15:00 Sent To  
Notes
2022-04-08 12:25:58DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME
2022-04-05 12:43:44SIGNATURES FOR PLUMBING DRAWINGS ARE VALID. JS
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2022-03-31 Cont ID  
Sent By ckimmerl Date 2022-03-31 Time 15:47 Rev Time 0.00
Received By ckimmerl Date 2022-03-31 Time 15:47 Sent To  
Notes
***NONE***