Plan Review Details - Permit 22030515
Plan Review Stops For Permit 22030515
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-06-13 Cont ID  
Sent By lmarchan Date 2022-06-13 Time 13:51 Rev Time 0.00
Received By lmarchan Date 2022-06-13 Time 13:51 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 09:15 Rev Time 0.00
Received By rmcphers Date 2022-05-03 Time 09:15 Sent To  
Notes
2022-05-03 09:15:46PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 12:40 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 09:15 Sent To  
Notes
2022-04-14 12:41:13PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 09:15 Rev Time 0.00
Received By rmcphers Date 2022-05-03 Time 09:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 09:15 Sent To  
Notes
2022-04-14 13:00:45REMODEL HOTEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE HOURLY FIRE RATING FOR THE NEW DOORS
 BETWEEN UNITS PER FBC 708.6
  
 2) ACCESSIBLE RESTROOMS = REAR GRAB BAR LOCATION
 DIMENSIONS SHOULD BE SHOWN FROM THE CENTERLINE OF THE
 TOILET PER FBC A 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 3) ACCESSIBLE RESTROOMS = SHOWER GRAB BAR DIMENSIONS
 SHOULD BE SHOWN FROM THE FLOOR TO THE TOP OF THE
 GRIPPING SURFACE FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 4) FOR THE FLOORING (EXCEPT - CARPET) - THE FOLLOWING
 ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY
 THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING TO
 PROJECTDOX ( [email protected] )
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-13 Cont ID  
Sent By jleahy Date 2022-04-13 Time 16:43 Rev Time 0.00
Received By jleahy Date 2022-04-13 Time 16:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-02 Cont ID  
Sent By pleduc Date 2022-05-02 Time   Rev Time 0.00
Received By pleduc Date 2022-04-27 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-17 Cont ID  
Sent By pleduc Date 2022-03-17 Time   Rev Time 0.00
Received By pleduc Date 2022-03-17 Time 15:35 Sent To  
Notes
2022-03-17 16:07:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET AO .01 - THERE ARE INDICATIONS OF NO FIRE
 ALARM OR FIRE SPRINKLER REVISIONS AS PART OF THIS WORK.
  
 HOWEVER, UNDER THE SCOPE OF WORK FOR EACH FLOOR THERE
 ARE INDICATIONS OF WORK THAT MAY AFFECT FIRE ALARM &
 FIRE SPRINKLER EQUIPMENT.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT ON THE PLAN
 SHEET.
  
  
 1A) PER THE ABOVE FIRE ALARM COMMENT, HOW WILL THE FIRE
 ALARM BE MAINTAINED WHILE WORK IS BEING DONE ON EACH
 FLOOR.
  
 PLEASE INCLUDE SPECIFIC DETAILS INCLUDING HOW FALSE
 ALARMS WILL BE CONTROLLED.
  
  
 1B) PER THE ABOVE FIRE SPRINKLER COMMENT, HOW WILL THE
 FIRE SPRINKLER HEADS BE MAINTAINED WHILE WORK IS BEING
 DONE ON EACH FLOOR.
  
 PLEASE INCLUDE SPECIFIC DETAILS.
  
  
 1C) THE REASON FOR COMMENTS 1A & 1B IS THAT THE FIRE
 ALARM & FIRE SPRKLER CONTRACTOR WILL NEED TO BE
 INVLOVED HOW HOW THES SYSTEMS AND EQUIPMENT WILL REMAIN
 FUNCTIONAL AND IS DAMAGE REAPIRED UNDER SEPARATE PEMRIS
 AND SHOP DRAWINGS.
  
  
 2) A SHEET - UNDER THE SCOPE OF WORK THERE ARE
 INDICATIONS OF CLOSING OFF A FLOOR FOR GUESTS TO
 COMPLETE THE WORK UNTIL MOVING TO ANOTHER FLOOR.
  
 THERE ARE NO INDICATIONS HOW THIS WILL TAKE PLACE.
  
 HOW WILL THE FLOOR AREA, INCLUDING STAIR AND ELEVATOR,
 BE ISOLATED SO THAT GUESTS CAN NOT ENTER THE
 CONSTRUCTION AREA AND STILL ALLOW ACCESS/EGRESS TO
 WORKERS?
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 09:16 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 06:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 13:07 Rev Time 0.00
Received By rmcphers Date 2022-03-15 Time 07:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 13:01 Sent To  
Notes
2022-04-14 13:02:26NO CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-04-12 Cont ID  
Sent By medwards Date 2022-04-12 Time 08:02 Rev Time 0.00
Received By medwards Date 2022-04-12 Time 08:02 Sent To  
Notes
2022-04-12 08:02:44ACCORDING TO THE SCOPE OF WORK, NO MECHANICAL WORK WILL
 BE INCLUDED IN THIS RENOVATION. ME

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-04-06 Cont ID  
Sent By rwbrown Date 2022-04-06 Time 14:42 Rev Time 0.00
Received By rwbrown Date 2022-04-06 Time 14:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 09:16 Rev Time 0.00
Received By rmcphers Date 2022-05-03 Time 09:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 13:07 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 13:07 Sent To  
Notes
2022-04-06 14:33:20PLUMBING PAGES SIGNED - RWB
  

Review Stop Z ZONING
Rev No 1 Status N Date 2022-03-21 Cont ID  
Sent By ckimmerl Date 2022-03-21 Time 09:20 Rev Time 0.00
Received By ckimmerl Date 2022-03-21 Time 09:20 Sent To  
Notes
***NONE***