Plan Review Details - Permit 22030512
Plan Review Stops For Permit 22030512
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 08:50 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 16:45 Sent To  
Notes
2022-04-18 08:50:24SHELL BUILD OUT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-16 Cont ID  
Sent By rmcphers Date 2022-05-16 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2022-05-16 Time 12:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 09:14 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 16:46 Sent To  
Notes
2022-04-18 09:13:59BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE WALL FINISH FOR THE WALLS
 SURROUNDING THE MOP SINK - FBC 1210.2.2 WALLS AND
 PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 2) PLEASE SHOW THE DIMENSIONS FOR THE KITCHEN - FBC
 1208.1 KITCHENS SHALL HAVE A CLEAR PASSAGEWAY OF NOT
 LESS THAN 3 FEET (914 MM) BETWEEN COUNTER FRONTS AND
 APPLIANCES OR COUNTER FRONTS AND WALLS.
  
 3) PLEASE SHOW THE ACCESSIBLE BAR SEATING COUNTER TOP
 HEIGHT - FBC A 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4) DRAWING 1.4A - SECTION 2-1.4A DOES NOT SHOW THE
 ACCESSIBLE BAR SEATING - PER THE FLOOR PLAN 1.0A
  
 5) DRAWING 1.6A DETAIL 10 - THE CASHIER COUNTER HEIGHT
 NEEDS TO COMPLY WITH FBC 904.4 SALES AND SERVICE
 COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 6) ACCESSIBLE RESTROOM - PLEASE SHOW THE DIMENSIONS FOR
 THE GRAB BARS, MIRROR. ETC FBC ACCESSIBILITY CHAPTER 6
  
 7) ACCESSIBLE RESTROOM - DOOR CANNOT SWING INTO THE
 FIXTURE CLEAR FLOOR SPACE (PLEASE SHOW THE CLEAR FLOOR
 SPACE IF USING THE EXCEPTION) - FBC A 603.2.3 DOOR
 SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 EXCEPTIONS: (2) WHERE THE TOILET ROOM OR BATHING ROOM
 IS FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING
 WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC
 OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING
 INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR
 ANY FIXTURE.
  
 8) ACCESSIBLE RESTROOM - PLEASE SHOW THE DOOR
 MANEUVERING CLEARANCE (18" BESIDE THE LATCH SIDE) TO
 EXIT THE RESTROOM - FBC A 404.2.4
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-09 Cont ID  
Sent By fgiaquin Date 2022-04-09 Time 22:49 Rev Time 0.00
Received By fgiaquin Date 2022-04-09 Time 21:04 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-04-09 Cont ID  
Sent By fgiaquin Date 2022-04-09 Time 22:49 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-10 Cont ID  
Sent By pleduc Date 2022-05-10 Time   Rev Time 0.00
Received By pleduc Date 2022-05-10 Time 11:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-21 Cont ID  
Sent By   Date 2022-03-21 Time   Rev Time 0.00
Received By bdolan Date 2022-03-21 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-18 Cont ID  
Sent By medwards Date 2022-05-18 Time 12:53 Rev Time 0.00
Received By medwards Date 2022-05-09 Time 14:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-20 Cont ID  
Sent By lmarchan Date 2022-04-20 Time 16:58 Rev Time 0.00
Received By lmarchan Date 2022-03-18 Time 07:45 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 09:14 Rev Time 0.00
Received By rmcphers Date 2022-04-18 Time 09:14 Sent To  
Notes
2022-04-18 09:15:57SHELL BUILD OUT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By medwards Date 2022-05-18 Time 12:52 Rev Time 0.00
Received By medwards Date 2022-05-18 Time 12:52 Sent To  
Notes
2022-05-18 12:53:30ASEPARATE PERMIT AND MECHANICAL REVIEW WILL BE REQUIRED
 FOR THE WALK IN COOLERS AS THEY WERE NOT REVIEWED UNDER
 THIS PERMIT. ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-04 Cont ID  
Sent By medwards Date 2022-04-04 Time 14:35 Rev Time 0.00
Received By medwards Date 2022-04-04 Time 14:08 Sent To  
Notes
2022-04-04 14:35:331ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22030512
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE ON THE MECHANICAL DRAWINGS STATING
 THAT THE REFRIGERATION WILL REQUIRE A SEPARATE PERMIT
 AND REVIEW AS THE WALK-INS WILL NOT BE REVIEWED UNDER
 THIS PERMIT.
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FEC C403.2.1
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS
 ACCORDING TO FMC 403.3.1.1 3RD SENTENCE WE MUST USE
 TABLE 403.3.1.1 AND NOT THE ARCHITECT?S EGRESS
 OCCUPANCY COUNT. PLEASE DO NOT FORGET THE EXHAUST FOR
 THIS KITCHEN. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 4) PLEASE SHOW THE LOCATION OF THE CONDENSING UNIT AND
 THE ANCHORAGE OF THIS UNIT. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-13 Cont ID  
Sent By ccole Date 2022-05-13 Time 13:48 Rev Time 0.00
Received By ccole Date 2022-05-13 Time 09:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-01 Cont ID  
Sent By lcrespo Date 2022-04-01 Time 14:11 Rev Time 0.00
Received By lcrespo Date 2022-04-01 Time 08:42 Sent To  
Notes
2022-04-01 14:09:5104/01/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET C-1, UNDER GENERAL NOTES, IT MENTIONS THE
 6TH EDITION, AND THE RECENT ADDITION IS THE 2020 FBC
 7TH EDITION. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET 1.0A;
  
 A. WOULD YOU PLEASE GIVE DIMENSIONS FOR FIXTURE
 CLEARANCES FOR WATER CLOSET LAV AND TURNING RADIUS PER
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
  
 B. ADA DETAIL OF HEIGHTS AND DIMENSIONS NOT SHOWN;
 PLEASE PROVIDE DETAILED DRAWINGS PER THE 2020 FBC
 ACCESSIBILITY CODE.
  
 3. ON SHEET 1.3A, THE SERVICE SINK (MOP SINK)
 SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE
 IN ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2
 AND 2020 FBC SEC. P 310.3. THE PAINT IS NOT AN APPROVED
 FINISH. PLEASE MAKE A NOTE ON THIS SHEET.
  
 4. ON SHEET 3.2P;
  
 A. IT SHOWS A TWO HAND SINK GOING INTO THE GREASE
 INTERCEPTOR. IT SHALL NOT GO INTO GREASE INTERCEPTORS
 AS THEY DO NOT PRODUCE WASTE REQUIRING TREATMENT OR
 SEPARATION AND SHALL BE DISCHARGED INTO ANY INTERCEPTOR
 PER THE 2020 FBC SEC. 1003.2 APPROVAL.
  
 B. IN THE ISOMETRIC, IT SHOWS THE ICE LINE AND WATER
 GOING INTO SANITARY, AND ON 3.0P, IT SHOWS IT GOING IN
 INTO GREASE, AND IT IS LABELED AS A WATER CLOSET. IT
 NEEDS TO SHOW GOING INTO THE SANITARY. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10.
  
 5. DUE TO A CHANGE IN PROCESS, THE BACKFLOW PERMIT AND
 GREASE INTERCEPTOR PERMITS MUST BE SUBMITTED BEFORE
 ISSUING THE PRIMARY PERMIT (AS APPLICABLE). YOU CAN
 SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF YOU
 DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL, AND I WILL CHANGE THE REVIEW
 STATUS TO PASS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-16 Cont ID  
Sent By rmcphers Date 2022-05-16 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2022-05-16 Time 12:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-18 Cont ID  
Sent By rmcphers Date 2022-04-18 Time 09:30 Rev Time 0.00
Received By rmcphers Date 2022-04-18 Time 09:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-04-20 Cont ID  
Sent By jroach Date 2022-04-20 Time 16:00 Rev Time 0.00
Received By jroach Date 2022-04-20 Time 15:47 Sent To  
Notes
2022-04-20 16:00:33THIS REVIEW IS LIMITED TO THE INTERIOR BUILD-OUT ONLY.
  
 THE CASA MARA COMMERCIAL PLANNED DEVELOPMENT SHALL BE
 SUBJECT TO ALL DEVELOPMENT ORDER CONDITIONS, AS
 OUTLINED IN RESOLUTION NO. 108-21, APPROVED ON JUNE 1,
 2021, AND AS MAY BE AMENDED.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved