Plan Review Details - Permit 22030438
Plan Review Stops For Permit 22030438
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-14 Cont ID  
Sent By pvalenti Date 2022-04-14 Time 13:01 Rev Time 0.00
Received By pvalenti Date 2022-04-14 Time 13:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-28 Cont ID  
Sent By pvalenti Date 2022-03-28 Time 14:00 Rev Time 0.00
Received By pvalenti Date 2022-03-28 Time 13:45 Sent To  
Notes
2022-03-28 14:07:05PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 PLEASE PROVIDE THE TEST REPORTS FOR THE FOLLOWING
 FLOORING/UNDERLAYMENT TESTS. NOTE THAT TEST REPORTS ARE
 REQUIRED - MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE
 DUE TO DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND
 TEST REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY
 THE MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-15 Cont ID  
Sent By cwalker Date 2022-04-15 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-11 Cont ID  
Sent By cwalker Date 2022-03-11 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-03-11 12:43:59FIRE COMMENTS:
 PROVIDE INFORMATION ON THE VINYL FLOORING TO BE
 INSTALLED TO INCLUDE THE CRITICAL RADIANT FLUX OF THE
 FLOORING FOR THE TESTED AND LISTED FIRE PERFORMANCE.
 NFPA 101 10.2.7
 FIRE PLAN REVIEW BY CHARLES ?RANDY? WALKER
 [email protected]
 561-804-4762
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-18 Cont ID  
Sent By aoliver Date 2022-04-18 Time 08:06 Rev Time 0.00
Received By aoliver Date 2022-04-14 Time 13:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-28 Cont ID  
Sent By pvalenti Date 2022-03-28 Time 14:09 Rev Time 0.00
Received By pvalenti Date 2022-03-10 Time 08:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-03-28 Cont ID  
Sent By pvalenti Date 2022-03-28 Time 14:09 Rev Time 0.00
Received By pvalenti Date 2022-03-28 Time 13:45 Sent To  
Notes
***NONE***