Plan Review Details - Permit 22030391
Plan Review Stops For Permit 22030391
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By jwitmer Date 2022-05-25 Time 15:09 Rev Time 0.00
Received By jwitmer Date 2022-05-25 Time 14:25 Sent To  
Notes
2022-05-25 15:09:29WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22030391
 ADD: 400 N FLAGLER DR UNIT 1706
 CONT: ADVANCED COMMUNICATIONS TECHNOLOGY
 TEL: 561-771-6677
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 25TH/2022
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE VALUE OF WORK
 AT $30,000.00 FOR BOTH THE CGC & THE EC THE VALUE OF
 WORK FOR THE SCOPE OF WORK SHOWN IS LOW. 109.3 BUILDING
 PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE FOUNDATION PLAN C-4 SECTION A SHOWS THE GROUND
 ELEVATION AT 5.80 AMSL, BASE FLOOD AT 7.00 AMSL,
 FREEBOARD OF ONE FOOT AND THE TOP OF THE CONCRETE PAD
 AT 8.13 AMSL. PLEASE BE AWARE THAT THE CITY OF WEST
 PALM BEACH REQUIRES A TWO-FOOT FREEBOARD NOT ONE FOOT.
  
 FLOOD ZONE CERTIFICATES/ SURVEYORS- DEPT. OF
 AGRICULTURE
 1612.5 FLOOD HAZARD DOCUMENTATION. WEST PALM BEACH MUNI
 CODE. ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD
 PREVENTION & CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF PERMIT
 APPLICATION AFTER SEPT. 12/2016,
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 3) WITH THE GROUND ELEVATION OF 5.80 AMSL AND THE
 REQUIRED 2-FOOT FREEBOARD OR THE TOP OF THE CONCRETE
 PAD REQUIRED TO BE ABOVE 9.0 FEET NGVD88. PLEASE
 PROVIDE ALL ELEVATIONS IN NGVD SINCE ALL COASTAL FLOOD
 MAPS WERE ADOPTED BY THE CITY WEST PALM BEACH TO NGVD88
 ON OCT. 11/2017.
  
 4) HOW WILL THE GENERATOR BE HELD TO THE ELEVATION
 ABOVE 9.0 NCVD88 IF THE GROUND ELEVATION IS 5.80 AMSL.
 WILL THE ELEVATED HEIGHT OF THE GENERATOR REQUIRE
 ADDITIONAL FOUNDATION STRENGTH AND ANCHORING OF THE
 GENERATOR TO RESIST THE WIND FORCES OF THE MOMENT OF
 OVERTURNING? EVERY STRUCTURE SHALL BE DESIGNED TO
 RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 15:01 Rev Time 0.00
Received By mpeterso Date 2022-06-07 Time 15:01 Sent To  
Notes
2022-06-07 16:15:41ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL OVERCURRENT PROTECTION IN MAIN
 DISCONNECT AS REQUIRED PER NEC 240.15
 2) PLEASE DETAIL SUPPORT FOR CONDUCTORS IN VERTICAL
 RACEWAYS AS REQUIRED PER NEC 300.19(A)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-18 Cont ID  
Sent By pleduc Date 2022-05-18 Time   Rev Time 0.00
Received By pleduc Date 2022-05-18 Time 12:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-21 Cont ID  
Sent By lmarchan Date 2022-06-21 Time 12:40 Rev Time 0.00
Received By lmarchan Date 2022-05-17 Time 06:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 16:20 Rev Time 0.00
Received By mpeterso Date 2022-06-07 Time 16:19 Sent To  
Notes
2022-06-07 16:20:29ALL PLANS PASSED SIGNATURE REVIEW. MP

Review Stop Z ZONING
Rev No 1 Status F Date 2022-06-21 Cont ID  
Sent By avann Date 2022-06-21 Time 10:17 Rev Time 0.00
Received By kdefranc Date 2022-06-21 Time 10:16 Sent To  
Notes
2022-06-21 10:17:036/21/22 ? FAILED
  
 REVIEW COMMENT TO BE ADDRESSED:
 THIS PROJECT REQUIRES A WIRELESS COMMUNICATION FACILITY
 APPLICATION APPROVAL PRIOR TO BUILDING PERMIT
 APPLICATION SUBMITTAL.
  
  
 KEVIE DEFRANC
 PLANNER ? PLANNING DIVISION
 [email protected]
 561-822-1449
  