Plan Review Details - Permit 22030383
Plan Review Stops For Permit 22030383
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-05-21 Cont ID  
Sent By cpuell Date 2022-05-21 Time 11:23 Rev Time 0.00
Received By cpuell Date 2022-05-21 Time 11:23 Sent To  
Notes
2022-05-21 11:23:47ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-10-18 Cont ID  
Sent By rmcphers Date 2022-10-18 Time 14:43 Rev Time 0.00
Received By rmcphers Date 2022-10-18 Time 14:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-09-27 Cont ID  
Sent By rmcphers Date 2022-09-27 Time 08:27 Rev Time 0.00
Received By rmcphers Date 2022-09-27 Time 08:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-09-06 Cont ID  
Sent By rmcphers Date 2022-09-06 Time 11:03 Rev Time 0.00
Received By rmcphers Date 2022-09-06 Time 11:03 Sent To  
Notes
2022-09-06 11:10:26NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PRODUCT APPROVAL PROVIDED FOR THE ROOF NEEDS TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD. FBC WPB 107.3.4
  
 2) SOME DRAWINGS SHOW A TILE ROOF AT FRONT ENTRY - SOME
 DRAWINGS SHOW A FLAT ROOF AT FRONT ENTRY - PLEASE
 CLARIFY - ALL DRAWINGS SHOULD MATCH.
  
 3) AC CALCULATIONS PROVIDED SHOW R30 INSULATION IN THE
 CEILING - PLEASE SHOW THE TYPE OF INSULATION ON THE
 DRAWINGS.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-03 Cont ID  
Sent By rmcphers Date 2022-08-03 Time 09:23 Rev Time 0.00
Received By rmcphers Date 2022-08-03 Time 09:23 Sent To  
Notes
2022-08-03 09:36:07NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PRODUCT APPROVAL PROVIDED FOR THE ROOF (18-0119.11)
 IS FOR A CONCRETE ROOF DECK - DRAWINGS SHOW ROOF DECK
 TO BE PLYWOOD.
  
 2) DRAWING A-1.0 - (OTHER DRAWINGS HAVE BEEN REVISED) -
 EMERGENCY ESCAPE WINDOW "A" IS TOO SMALL TO MEET THE
 EMERGENCY EGRESS DIMENSIONS ( THE NET CLEAR HEIGHT
 OPENING SHALL BE NOT LESS THAN 24 INCHES) - FBC
 R310.2.1
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-11 Cont ID  
Sent By rmcphers Date 2022-07-11 Time 11:57 Rev Time 0.00
Received By rmcphers Date 2022-07-11 Time 10:17 Sent To  
Notes
2022-07-11 11:56:57NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, MULL
 BARS AND ROOFING SYSTEMS. ALL PRODUCT APPROVALS NEED TO
 BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD OR LISTED ON THE DRAWINGS BY THE
 PERMIT NUMBER FBC WPB 107.3.4
  
 2) EMERGENCY ESCAPE WINDOW "A" IS TOO SMALL TO MEET THE
 EMERGENCY EGRESS DIMENSIONS ( THE NET CLEAR HEIGHT
 OPENING SHALL BE NOT LESS THAN 24 INCHES) - FBC
 R310.2.1
  
 3) FBC R320.1.1 ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES,
 TRIPLEXES, CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT
 LEAST ONE BATHROOM, LOCATED WITH MAXIMUM POSSIBLE
 PRIVACY, WHERE BATHROOMS ARE PROVIDED ON HABITABLE
 GRADE LEVELS, WITH A DOOR THAT HAS A 29-INCH (737 MM)
 CLEAR OPENING.
  
 4) PLEASE SHOW ROOF SCUPPER TO BE LEVEL WITH THE ROOF
 DECK FBC R903.4 ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF
 DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE
 ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL
 BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR
 PARAPET.
  
 5) SCUPPERS SHOWN MEET THE REQUIREMENTS FOR THE
 REQUIRED - OVER FLOW SCUPPERS FBC R903.4.1 OVERFLOW
 DRAINS AND SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES
  
 6) SITE PLAN NEEDS TO SHOW THE SITE STORM WATER
 DRAINAGE - FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 7) PLEASE SHOW THE REQUIRED SMOKE ALARM LOCATIONS FBC
 R314.3
  
 8) PLEASE PROVIDE A SURVEY.
  
 9) WINDOW, DOOR AND ROOFING SYSTEM PRODUCT APPROVALS
 MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE
 DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-08-04 Cont ID  
Sent By mpeterso Date 2022-08-04 Time 14:12 Rev Time 0.00
Received By mpeterso Date 2022-08-04 Time 14:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-09 Cont ID  
Sent By mpeterso Date 2022-06-09 Time 11:17 Rev Time 0.00
Received By mpeterso Date 2022-06-09 Time 11:14 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2022-10-18 Cont ID  
Sent By amhamilt Date 2022-10-18 Time 15:36 Rev Time 0.00
Received By amhamilt Date 2022-10-18 Time 15:36 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status F Date 2022-10-04 Cont ID  
Sent By amhamilt Date 2022-10-04 Time 14:41 Rev Time 0.00
Received By amhamilt Date 2022-10-04 Time 14:41 Sent To  
Notes
2022-10-04 14:43:43THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 SITE PLAN STILL SHOWS TILE ROOF OVER PORCH, PLEASE
 REVISE TO FLAT ROOF AS SHOWN IN OTHER PLANS AND
 APPROVED HPB PLANS. PLEASE ALSO ENSURE THAT ALL OTHER
 PLANS MATCH AS WELL.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2022-09-16 Cont ID  
Sent By amhamilt Date 2022-09-16 Time 15:04 Rev Time 0.00
Received By amhamilt Date 2022-09-16 Time 15:04 Sent To  
Notes
2022-09-16 15:09:11THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PLEASE ENSURE THAT ALL SHEETS ARE FOR THE CORRECT
 PROJECT BETWEEN 4010 AND 4008 GREENWOOD AND SHEETS ARE
 LABELED FOR THE CORRECT PROJECT AND MATCH THE PROJECT
 APPROVED BY HPB. MOST SHEETS APPEAR CORRECT FOR THIS
 PROJECT, HOWEVER, SECTIONS AND ROOF PLAN ARE STILL
 MISLABELED.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2022-08-16 Cont ID  
Sent By amhamilt Date 2022-08-16 Time 11:18 Rev Time 0.00
Received By amhamilt Date 2022-08-16 Time 11:18 Sent To  
Notes
2022-08-16 11:19:29SHEET A-3.0 (ELEVATIONS) IS FOR 4008 GREENWOOD, NOT
 4010 GREENWOOD. 4010 GREENWOOD AS SUBMITTED FOR HPB
 APPROVAL HAD WINDOWS WITH NO GRIDS. PLEASE REVISE SHEET
 TO SHOW CORRECT ELEVATIONS.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-06-03 Cont ID  
Sent By amhamilt Date 2022-06-03 Time 16:30 Rev Time 0.00
Received By amhamilt Date 2022-06-03 Time 16:30 Sent To  
Notes
2022-06-03 16:31:51THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PER HPB APPROVAL CONDITIONS, PLEASE INDICATE THAT
 WINDOWS WILL HAVE CLEAR GLASS, AND ANY LOW E COATING
 WILL ONLY BE APPLIED ON SIDES AND REAR.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-10-19 Cont ID  
Sent By aoliver Date 2022-10-19 Time 08:39 Rev Time 0.00
Received By aoliver Date 2022-10-11 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-05 Cont ID  
Sent By lmarchan Date 2022-10-05 Time 15:15 Rev Time 0.00
Received By lmarchan Date 2022-09-19 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-18 Cont ID  
Sent By shill Date 2022-09-18 Time 19:38 Rev Time 0.00
Received By shill Date 2022-08-29 Time 16:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-17 Cont ID  
Sent By aoliver Date 2022-08-17 Time 06:30 Rev Time 0.00
Received By aoliver Date 2022-07-26 Time 07:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-11 Cont ID  
Sent By rmcphers Date 2022-07-11 Time 12:31 Rev Time 0.00
Received By rmcphers Date 2022-05-20 Time 05:35 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-11-01 Cont ID  
Sent By aoliver Date 2022-11-01 Time 16:29 Rev Time 0.00
Received By aoliver Date 2022-10-25 Time 13:42 Sent To  
Notes
2022-11-01 16:29:05RECEIPT MU-2022-048584-0000 - $11,913.65 PAID
2022-10-25 13:42:4310/25/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-07-11 Cont ID  
Sent By rmcphers Date 2022-07-11 Time 11:57 Rev Time 0.00
Received By rmcphers Date 2022-07-11 Time 11:57 Sent To  
Notes
2022-07-11 11:57:46PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-07-27 Cont ID  
Sent By medwards Date 2022-07-27 Time 10:23 Rev Time 0.00
Received By medwards Date 2022-07-27 Time 10:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-27 Cont ID  
Sent By medwards Date 2022-05-27 Time 09:25 Rev Time 0.00
Received By medwards Date 2022-05-27 Time 09:25 Sent To  
Notes
2022-05-27 09:30:17PROVIDE THE ENERGY CALCULATIONS FOR THIS HOUSE. FEC
 R101.5.1.1
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS HOUSE. FEC 403.7.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-05-26 Cont ID  
Sent By rwbrown Date 2022-05-26 Time 14:46 Rev Time 0.00
Received By rwbrown Date 2022-05-26 Time 14:39 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2022-09-27 Cont ID  
Sent By rmcphers Date 2022-09-27 Time 08:27 Rev Time 0.00
Received By rmcphers Date 2022-09-27 Time 08:27 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2022-09-06 Cont ID  
Sent By rmcphers Date 2022-09-06 Time 11:10 Rev Time 0.00
Received By rmcphers Date 2022-09-06 Time 11:10 Sent To  
Notes
2022-09-06 11:10:50SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-08-03 Cont ID  
Sent By rmcphers Date 2022-08-03 Time 09:53 Rev Time 0.00
Received By rmcphers Date 2022-08-03 Time 09:53 Sent To  
Notes
2022-08-03 09:54:00SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-07-11 Cont ID  
Sent By rmcphers Date 2022-07-11 Time 12:29 Rev Time 0.00
Received By rmcphers Date 2022-07-11 Time 12:29 Sent To  
Notes
2022-07-11 12:31:06SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-10-18 Cont ID  
Sent By rmcphers Date 2022-10-18 Time 14:43 Rev Time 0.00
Received By rmcphers Date 2022-10-18 Time 14:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-09-27 Cont ID  
Sent By rmcphers Date 2022-09-27 Time 09:34 Rev Time 0.00
Received By rmcphers Date 2022-09-27 Time 09:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-06 Cont ID  
Sent By rmcphers Date 2022-09-06 Time 11:17 Rev Time 0.00
Received By rmcphers Date 2022-09-06 Time 11:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-03 Cont ID  
Sent By rmcphers Date 2022-08-03 Time 09:54 Rev Time 0.00
Received By rmcphers Date 2022-08-03 Time 09:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-09 Cont ID  
Sent By mpeterso Date 2022-06-09 Time 11:21 Rev Time 0.00
Received By mpeterso Date 2022-06-09 Time 11:21 Sent To  
Notes
2022-06-09 11:22:29ALL PLANS PASSED SIGNATURE REVIEW
2022-05-27 09:31:34DIGITAL SIGNATURE FOR MECHANICAL DRAWINGS APPROVED ME

Review Stop Z ZONING
Rev No 3 Status P Date 2022-10-18 Cont ID  
Sent By amhamilt Date 2022-10-18 Time 15:32 Rev Time 0.00
Received By amhamilt Date 2022-10-18 Time 15:32 Sent To  
Notes
2022-10-18 15:33:51PERMIT HAS PASSED, HOWEVER, ALL DRIVEWAYS, MECHANICAL,
 FENCING, AND LANDSCAPING TO BE APPROVED UNDER SEPARATE
 PERMIT IF APPLICABLE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-16 Cont ID  
Sent By amhamilt Date 2022-08-16 Time 11:19 Rev Time 0.00
Received By amhamilt Date 2022-08-16 Time 11:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-06-03 Cont ID  
Sent By asangele Date 2022-06-03 Time 16:28 Rev Time 0.00
Received By amhamilt Date 2022-06-03 Time 16:28 Sent To  
Notes
2022-06-03 16:29:20THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 A SEPERATE LANDSCAPE PERMIT IS REQUIRED AND MUST BE
 SUBMITTED FOR ZONING APPROVAL TO MOVE FORWARD.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  