Plan Review Details - Permit 22030340
Plan Review Stops For Permit 22030340
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-05-31 Cont ID  
Sent By aoliver Date 2022-05-31 Time 07:53 Rev Time 0.00
Received By aoliver Date 2022-05-31 Time 07:44 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2022-05-21 Time   Rev Time 0.00
Received By   Date 2022-05-21 Time   Sent To  
Notes
2022-05-21 20:08:47AN ASBESTOS SURVEY WAS UPLOADED. THIS IS NOT NEEDED.
 PLEASE PROVIDE THE FOLLOWING, UPLOAD TO PROJECTDOX AND
 COMPLETE THE TASK:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 10:57 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 10:57 Sent To  
Notes
2022-04-21 10:58:33PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 10:56 Rev Time 0.00
Received By rmcphers Date 2022-04-20 Time 17:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-20 Cont ID  
Sent By mpeterso Date 2022-05-20 Time 11:12 Rev Time 0.00
Received By mpeterso Date 2022-05-20 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-05 Cont ID  
Sent By mpeterso Date 2022-04-05 Time 16:53 Rev Time 0.00
Received By mpeterso Date 2022-04-05 Time 16:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-03 Cont ID  
Sent By pleduc Date 2022-05-03 Time   Rev Time 0.00
Received By pleduc Date 2022-05-03 Time 10:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-04-04 Cont ID  
Sent By pleduc Date 2022-04-04 Time   Rev Time 0.00
Received By pleduc Date 2022-04-04 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-31 Cont ID  
Sent By jleahy Date 2022-05-31 Time 12:25 Rev Time 0.00
Received By jleahy Date 2022-05-26 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-21 Cont ID  
Sent By shill Date 2022-05-21 Time 20:08 Rev Time 0.00
Received By shill Date 2022-05-02 Time 13:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 11:00 Rev Time 0.00
Received By rmcphers Date 2022-04-04 Time 05:58 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 10:56 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 10:56 Sent To  
Notes
2022-04-21 10:56:40NO CHANGE OF OCCUPANCY - NO ADDED SQUARE FOOTAGE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-05-27 Cont ID  
Sent By medwards Date 2022-05-27 Time 07:15 Rev Time 0.00
Received By medwards Date 2022-05-27 Time 07:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-05-06 Cont ID  
Sent By medwards Date 2022-05-06 Time 14:41 Rev Time 0.00
Received By medwards Date 2022-05-06 Time 14:40 Sent To  
Notes
2022-05-06 14:43:10PLEASE REVISIT THE OUTDOOR AIR CALCULATIONS FOR EACH
 CONFERENCE ROOM. REMEMBER WE MUST USE TABLE 403.3.1.1
 TO GET THE OCCUPANT COUNT AND NOT THE ARCHITECT'S
 EGRESS OCCUPANT COUNT. FMC 403.3.1.1 3RD SENTENCE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-06 Cont ID  
Sent By medwards Date 2022-04-06 Time 14:26 Rev Time 0.00
Received By medwards Date 2022-04-06 Time 14:25 Sent To  
Notes
2022-04-06 14:26:091ST REVIEW FMC
 PERMIT: 22030340
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION SHOULD REFLECT THE FLOOR
 NUMBERS OF THIS PROJECT.
  
 2) PLEASE PROVIDE THE RATING OF THE ELEVATOR LOBBY
 WALLS AND PROVIDE RATED DAMPERS FOR ALL DUCTWORK
 PENETRATING THESE WALLS, ALSO PLEASE SHOW HOW THE
 RETURN FROM THE 8TH FLOOR ELEVATOR LOBBY WILL FLOW BACK
 OUT OF THE ELEVATOR LOBBY. FMC 607.
  
 3) ALL OF THE DUCTWORK AT THE RATED SHAFTS; EXISTING
 SMOKE EXHAUST, EXISTING OA/SMOKE PRESSURIZATION AND THE
 EXISTING EXHAUST RISER, ON BOTH FLOORS SHOULD HAVE
 FIRE/SMOKE DAMPERS AT THE SHAFT PENETRATION. FMC 607
  
 4) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE AND NOT BY THE WSHP. EACH USE OF SPACE
 SHOULD BE CALCULATED USING FMC 403.3.1.1 3RD SENTENCE
 AND TABLE 403.3.1.1. PLEASE PROVIDE THE OCCUPANCY
 CLASSIFICATION THAT MOST CLOSELY REPRESENTS EACH USE OF
 SPACE FROM TABLE 403.3.1.1. EXAMPLE: A CONFERENCE ROOM
 IS CALCULATED DIFFERENTLY THAN AN OFFICE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-03 Cont ID  
Sent By rwbrown Date 2022-05-03 Time 10:23 Rev Time 0.00
Received By rwbrown Date 2022-05-03 Time 10:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-04-05 Cont ID  
Sent By rwbrown Date 2022-04-05 Time 13:31 Rev Time 0.00
Received By rwbrown Date 2022-04-05 Time 07:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-05-31 Cont ID  
Sent By jleahy Date 2022-05-31 Time 12:25 Rev Time 0.00
Received By jleahy Date 2022-05-31 Time 12:25 Sent To  
Notes
2022-05-27 07:16:39DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-20 Cont ID  
Sent By mpeterso Date 2022-05-20 Time 11:15 Rev Time 0.00
Received By mpeterso Date 2022-05-20 Time 11:15 Sent To  
Notes
2022-05-06 14:44:05DIGITAL SIGNATURES FOR MECHANICAL DOCUMENTS APPROVED.
 ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-21 Cont ID  
Sent By rmcphers Date 2022-04-21 Time 10:58 Rev Time 0.00
Received By rmcphers Date 2022-04-21 Time 10:58 Sent To  
Notes
2022-04-21 10:55:52SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ALL OF THE ELECTRICAL, PLUMBING, MECHANICAL AND FIRE
 PLANS DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER
 -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
2022-04-06 14:27:14MECHANICAL PAGES SIGNATURES ARE COPIES OF THE ORIGINAL
 DIGITAL SIGNATURES. FAILED ME
2022-04-05 07:51:14PLUMBING PAGES NOT SIGNED - RWB

Review Stop Z ZONING
Rev No 1 Status N Date 2022-04-08 Cont ID  
Sent By ckimmerl Date 2022-04-08 Time 11:08 Rev Time 0.00
Received By ckimmerl Date 2022-04-08 Time 11:08 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved