| Plan Review Stops For Permit 22030308 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2022-05-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-05-31 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-05-31 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2022-05-31 09:40:38 | SPOKE WITH ZONING, A SECONDARY RENTAL UNIT NOT ALLOWED, | | | NO ADDITONAL ADDRESS REQUIRED. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-03-09 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-03-09 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-03-09 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2022-03-09 13:03:20 | AN ADDRESS WILL NEED TO BE ASSIGNED TO THIS ADU, PLEASE | | | HAVE OWNER CONTACT [email protected] OR CALL 561-805-6659 | | | TO BE ASSIGNED AN ADDRESS ONCE ZONING HAS APPROVED THE | | | PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2022-10-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-08 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-08 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-07 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-03 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2022-09-07 16:50:40 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 4TH REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: PERMIT TYPE HAS BEEN CHANGED FROM BLD-RES TO | | | RES-ADD. | | | | | | NOTICE: VALUE HAS BEEN ADJUSTED TO $224,343.00 PER THE | | | ICC BUILDING VALUATION DATA. (INCREASE IN CONDITIONED | | | SPACE) | | | | | | NOTICE: WINDOWS AND EXTERIOR DOOR PRODUCT APPROVALS | | | SHALL BE DEFERRED PER NOTE ON PAGE A-2. | | | | | | NEW NOTICE 9-20-22: PROVIDE THE MANUFACTURERS | | | CERTIFICATION PER CHAPTER 553, PART 1 F.S. | | | | | | 1. | | | | | | 2. | | | | | | 3. REF. COVER PAGE FOR THE FOLLOWING: SCOPE OF WORK | | | (SOW) STATES "NEW PRE-FABRICATED DETACHED RESIDENTIAL | | | ADDITION". PLEASE CORRECT. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 4. REF. COVER PAGE FOR THE FOLLOWING: ADDRESS FOR THE | | | CITY OF WPB BUILDING DEPARTMENT IS INCORRECT. PLEASE | | | CORRECT. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 5. REF. PLAN PAGE A1.1 FOR THE FOLLOWING: PROVIDE A | | | STRUCTURAL CONNECTION DETAIL BETWEEN THE VIKING STEEL | | | BUILDING AND THE EXISTING STRUCURE. THE PROPOSED | | | U-CHANNEL IS NOT A STRUCTURAL CONNECTION. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 6. PROVIDE A 2ND FLOOR TRUSS PLAN. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 7. REF. PLAN PAGE A-5 FOR THE FOLLOWING: DETAIL A/4.5 | | | FOR THE BOX EAVE RAFTER/POST DETAIL IS MISSING. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 8. PROVIDE WINDOW IN-FILL DETAIL FOR EXISTING | | | STRUCTURE. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 9. REF. PLAN PAGE A-2 FOR THE FOLLOWING: 2-STORY | | | ADDITION IS MISSING FROM EAST ELEVATION. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 10. REF. PLAN PAGE A-5 FOR THE FOLLOWING: ROOF FRAMING | | | IS METAL. PLYWOOD SHEATHING NAILING SCHEDULE SPECIFIES | | | 8D RING SHANK NAILS. PLEASE CLARIFY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 11. PROVIDE AN EXTERIOR WALL SECTION DETAIL FOR THE NEW | | | 2-STORY ADDITION. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 12. PROVIDE THE EXTERIOR WALL AND CEILING INSULATION | | | TYPE AND R-VALUE. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-07-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-07-30 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-30 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2022-07-30 10:28:36 | NO BLDG. REVIEW HAS BEEN PERFORMED. ACCESSORY | | | STRUCTURES ARE NOT ALLOWED. SEE 3RD ZONING REVIEW | | | COMMENTS. CT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-06-30 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-06-30 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2022-06-30 16:12:16 | THIS WILL BE REVIEWED UPON APPROVAL OF ZONING TO ALLOW | | | THE STRUCTURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-30 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-30 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2022-04-30 12:18:37 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1.PROVIDE A SOILS REPORT. | | | R401.4 SOIL TESTS. | | | WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL | | | SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, | | | SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE | | | LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL | | | DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE | | | THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION. | | | THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN | | | APPROVED METHOD. | | | 1803.2 INVESTIGATIONS REQUIRED. | | | GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN | | | ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5. | | | WHERE REQUIRED BY THE BUILDING OFFICIAL OR WHERE | | | GEOTECHNICAL INVESTIGATIONS INVOLVE IN-SITU TESTING, | | | LABORATORY TESTING OR ENGINEERING CALCULATIONS, SUCH | | | INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED | | | DESIGN PROFESSIONAL. | | | ZONING MAP - SOILS | | | | | | BASED ON THE OFFICIAL ZONING MAP REFERRED TO IN SECTION | | | 53-2 OF CHAPTER 53 OF THE CITY CODE OF WEST PALM BEACH, | | | FLORIDA, 1962, ADOPTED JUNE 15, 1964, YOUR PROPERTY, | | | LOCATED AT 4121 WAVERLY DR., W.P.B., FL, IS LOCATED IN | | | AN AREA OF QUESTIONABLE SOILS AND DOES REQUIRE | | | INVESTIGATION BY A GEOTECHNICAL ENGINEER WITH ITS | | | SUBSEQUENT SOILS REPORT AND DENSITY TESTING. | | | THIS ONLY RELIEVES YOU FROM THE STATUTORY REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE. THERE MAY BE OTHER | | | ENTITIES, SUCH AS YOUR DESIGN PROFESSIONAL OR YOUR | | | LENDING INSTITUTION THAT MAY REQUIRE THE ABOVE | | | MENTIONED INVESTIGATION. | | | | | | 2. PROVIDE THE FINISH FLOOR ELEVATION ? NON-FLOOD ZONE | | | R403.1.7.3 FOUNDATION ELEVATION. | | | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION | | | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER | | | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED | | | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 | | | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO | | | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN | | | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF | | | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT | | | ALL LOCATIONS ON THE SITE. | | | | | | 3.PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH | | | FBC R401.3 DRAINAGE. | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | | | | 4. PROVIDE THE MEAN ROOF HEIGHT: STATE MRH ON ELEVATION | | | PLAN PAGE. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 5.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT | | | APPROVAL OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 | | | FBC, FOR THE PROPOSED WINDOWS AND DOORS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 6 PROVIDE A ROOF FRAMIMG PLAN: | | | PROVIDE THE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE | | | R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES | | | R301.2.1.1WIND DESIGN REQUIRED. | | | | | | 7.PROVIDE A ROOF SHEATHING FASTENER SCHEDULE PER | | | CALCULATED DESIGN PRESSURES. | | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | | | NOTICE: REF. PLAN PAGE CVR FOR THE FOLLOWING COMMENTS: | | | | | | 8. SOW STATES THIS IS A PRE-FABRICATED RES. ADDITION. | | | THIS IS A STAND ALONE ACCESSORY DWELLING UNIT. PLEASE | | | CORRECT. | | | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2022-10-11 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-10-11 |
Time |
22:32 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-10-11 |
Time |
22:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-09-02 |
Time |
20:29 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-09-02 |
Time |
19:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-06-06 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-06-06 |
Time |
22:13 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-06-06 |
Time |
20:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-03-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-03-28 |
Time |
22:52 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-03-28 |
Time |
21:56 |
Sent To |
|
|
| Notes |
| 2022-03-28 22:52:53 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. LOCATION OF NEW PANEL NOT SHOWN IN NEW ADU. PLEASE | | | SHOW LOCATION FBC 107.2.1 | | | | | | 2. DISCONNECT REQUIRED PER NEC 225.32 ON ADU NEAREST | | | THE POINT OF THE ENTRANCE OF FEEDER CONDUCTORS | | | | | | 3. GROUNDING ELECTRODE SYSTEM REQUIRED FOR NEW ADU PER | | | NEC 250.32 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-10-24 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-10-24 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-10-07 |
Time |
16:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-09-08 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-09-08 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-08-31 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-07-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-07-30 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-09 |
Time |
09:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-06-30 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-05-23 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-04-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-30 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-08 |
Time |
06:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-10-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-10-24 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-10-17 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2022-10-24 16:40:06 | RECEIPT MU-2022-048043 - $546.52 PAID | | 2022-10-17 11:05:40 | 10/17/22 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-04-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-30 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-30 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2022-04-30 11:58:06 | IMPACT FEE QUESTIONNAIRE | | | | | | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2022-10-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-11 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-11 |
Time |
07:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-01 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-01 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2022-09-01 16:30:14 | PROVIDE THE ENERGY CALCULATIONS AND MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS FOR THE NEW HALL THAT | | | ATTACHES THE STRUCTURES TOGETHER. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-05-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-25 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-25 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-17 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-17 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2022-03-17 11:36:43 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22030308 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC R402 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC R403.7 | | | | | | 3) THE DRYER TERMINATION CANNOT HAVE AN SCREENS, PLEASE | | | REMOVE. FBC RES M1502.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-10-10 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-10 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-10-10 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-01 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-09-01 |
Time |
07:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-05-24 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-05-24 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-05-24 |
Time |
11:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-03-09 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-03-09 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-03-09 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2022-03-09 15:16:50 | 03/09/22 1 ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW, | | | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED | | | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. ON SHEET P-1; | | | | | | A. THE UPSTAIRS BATHS AND THE DOWNSTAIRS FULL BATH ARE | | | VENTED INCORRECTLY; NOT MORE THAN ONE WET-VENTED | | | FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE | | | DRY-VENTED FIXTURE DRAIN CONNECTION. CURRENTLY, THE | | | SHOWER AND WATER CLOSET ARE UPSTREAM OF THE LAVATORY | | | CONNECTION PER THE 2020 FBC R3108.1 HORIZONTAL WET VENT | | | PERMITTED. | | | | | | B. ON THE WASHER IT IS NOT VENTED CORRECTLY, A VENT | | | SHALL BE PROVIDED WITH A SYSTEM OF VENT PIPING THAT | | | WILL PERMIT THE ADMISSION OR EMISSION OF AIR SO THAT | | | THE SEAL OF ANY FIXTURE TRAP PER THE 2020 FBC SEC. R | | | 901.2. | | | | | | C. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS | | | WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION | | | ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW | | | ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF | | | HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE | | | BACKFLOW DEVICE WILL BE NEEDED FOR THE WATER METER PER | | | THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND | | | THEIR CONNECTION CONTROL PROGRAM. | | | | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON | | | REQUEST. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-04-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-30 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-30 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2022-04-30 11:56:53 | PROVISO ON PLAN PAGE A-2: A SEPERATE ROOFING PERMIT IS | | | REQUIRED. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2022-10-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-08 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-08 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-09-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-03 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-03 |
Time |
11:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-07-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-07-30 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-30 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-06-30 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-06-30 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-03-08 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-08 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-08 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2022-03-08 09:29:25 | SIGNATURE REVIEW | | | | | | ORIGINAL SIGNED AND SEALED DRAWINGS FROM SANDRA E. | | | PUERTA - OK | | | SURVEY SIGNED BY EFRAIN LOPEZ IS NOT AN ORIGINAL RAISED | | | SEAL. | | | | | | CORRECTIONS NEEDED - | | | | | | 1) SURVEY SIGNED BY EFRAIN LOPEZ DOES NOT SHOW AS | | | DIGITALLY SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | | DIVISION AT THE CITY HALL. | | | | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2022-10-21 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-10-21 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-10-21 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2022-10-21 11:34:03 | 10/21/2022 | | | | | | PASSED WITH PROVISO- DETACHED STRUCTURE NOT PERMITTED | | | TO BE RENTED OUT TO PUBLIC, PERSONAL USE ONLY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2022-09-08 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-09-08 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-09-08 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-07-28 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-07-28 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2022-07-28 11:41:30 | SEE PREVIOUS COMMENTS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2022-06-30 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2022-06-30 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2022-06-30 15:37:36 | 6/30/22- FAILED- FOR THE RESIDENTIAL NEIGHBORHOOD OF | | | ECHO LAKES AND WESTFIELD, ALL ROOFED ACCESSORY | | | BUILDINGS ARE PROHIBITED (SEC. 94-304 B.1). | | | | | | ANGELLA VANN | | | 5618221441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-05-27 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-05-27 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-05-27 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2022-05-31 08:57:30 | PLEASE NOTE UNIT IS NOT ALLOWED TO BE RENTED OUT PER | | | THE ZONING DISTRICT SF7 | | | | | | VALENTINA BROGLIA | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-03-17 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-03-17 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-03-17 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2022-03-17 11:32:35 | 3/17/2022 FAILED | | | | | | PLEASE PROVIDE THE HEIGTH ON THE ELEVATION PLANS | | | STARTING FROM GRADE TO THE MEAN OF THE ROOF, SECT | | | 94-304 (B)(4) ACCESSORY STRUCTURES SHALL NOT EXCEED 25 | | | FEET | | | | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|
|