Plan Review Details - Permit 22030306
Plan Review Stops For Permit 22030306
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-22 Cont ID  
Sent By cthroop Date 2022-04-22 Time 16:18 Rev Time 0.00
Received By cthroop Date 2022-04-18 Time 09:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-01 Cont ID  
Sent By cthroop Date 2022-04-01 Time 15:40 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 15:40 Sent To  
Notes
2022-04-01 16:37:59PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT:
  
 NOTICE: SITE WALLS REQUIRE A SEPERATE PERMIT. PROVISO
 ON PLAN PAGE S-1.
  
 NOTICE: LETTER SUBMITTED FOR REVIEW STATES STORAGE SHED
 IS STRUCTURALY INDEPENDENT OF MAIN DWELLING UNIT.
 BUILDING OFFICIAL REQUIRES A SEPERATE PERMMIT FOR ANY
 NEW STRUCTURES.
 PROVISO ON PLAN PAGE A-100.
  
 1. PROVIDE A NEW SITE PLAN AND BOUNDARY LINE SURVEY.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE
 AND INCLUDED BOUNDARY LINE SURVEY.
  
 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 3. PLAN PAGE S-1 HAS DETAILS REFERENCED TO PLAN PAGE
 S-2. PROVIDE PLAN PAGE S-2.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-01 Cont ID  
Sent By cthroop Date 2022-04-01 Time 15:27 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 15:42 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-04-22 Cont ID  
Sent By cthroop Date 2022-04-22 Time 16:08 Rev Time 0.00
Received By cthroop Date 2022-04-18 Time 09:40 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-04-01 Cont ID  
Sent By cthroop Date 2022-04-01 Time 14:34 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 15:42 Sent To  
Notes
2022-04-01 15:39:43PLAN REVIEW FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1.A GAS SUB-PERMIT UNDER MASTER 19070834.
 PERMITS - 105.1 REQUIRED.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
  
 2. SUBMIT APPLICABLE GAS TABLES.
  
 3. SUBMIT MANUFACTURERS SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR
 2020 FBC FUEL GAS RES. SEC. G2408.1.
  
 4. SUBMIT GAS REGULATOR SPECIFICATIONS. 2020 FBC FUEL
 GAS SEC.305.1 OR 2020 FBC FUEL GAS RES. SEC. G2408.1.
  
 5. REGULATORS SHALL HAVE A UNION INSTALLED WITHIN 1
 FOOT OF EITHER SIDE OF THE REGULATOR FBC FG 410.2
  
 6. SUBMIT A COPY OF A HOUSE PLAN SHOWING THE LOCATION
 OF ALL PROPOSED GAS APPLIANCES. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE PROPOSED
 GAS APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDINGS MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FGC
 SEC.304.9.3 OR 2017 FBC R G2407.9.3. COMBINED
 COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
2022-04-01 14:35:31GAS IS UNDER PERMIT 19070834. NO GAS REVISION. CT

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-04-04 Cont ID  
Sent By fmittner Date 2022-04-04 Time 09:44 Rev Time 0.00
Received By amhamilt Date 2022-04-01 Time 14:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-22 Cont ID  
Sent By cthroop Date 2022-04-22 Time 16:18 Rev Time 0.00
Received By cthroop Date 2022-04-14 Time 06:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-05 Cont ID  
Sent By aoliver Date 2022-04-05 Time 08:56 Rev Time 0.00
Received By aoliver Date 2022-03-08 Time 10:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-04-22 Cont ID  
Sent By cthroop Date 2022-04-22 Time 16:13 Rev Time 0.00
Received By cthroop Date 2022-04-18 Time 09:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-04-01 Cont ID  
Sent By cthroop Date 2022-04-01 Time 15:27 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 15:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-22 Cont ID  
Sent By cthroop Date 2022-04-22 Time 16:08 Rev Time 0.00
Received By cthroop Date 2022-04-18 Time 09:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-04-01 Cont ID  
Sent By cthroop Date 2022-04-01 Time 15:39 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 15:42 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-04-01 Cont ID  
Sent By cthroop Date 2022-04-01 Time 15:07 Rev Time 0.00
Received By cthroop Date 2022-04-01 Time 14:35 Sent To  
Notes
2022-04-01 15:08:31ROOFING PRODUCT APPROVALS UNDER MASTER 19070834. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-04-22 Cont ID  
Sent By cthroop Date 2022-04-22 Time 16:08 Rev Time 0.00
Received By cthroop Date 2022-04-18 Time 09:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-01 Cont ID  
Sent By cthroop Date 2022-04-01 Time 15:07 Rev Time 0.00
Received By cthroop Date 2022-03-14 Time 15:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-21 Cont ID  
Sent By amhamilt Date 2022-04-21 Time 14:01 Rev Time 0.00
Received By amhamilt Date 2022-04-21 Time 14:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-06 Cont ID  
Sent By fmittner Date 2022-04-04 Time 09:42 Rev Time 0.00
Received By amhamilt Date 2022-04-04 Time 09:42 Sent To  
Notes
2022-04-04 09:43:31THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 SURVEY WITH MARKED SETBACKS REQUIRED.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  