Plan Review Details - Permit 22030298
Plan Review Stops For Permit 22030298
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-05-04 Cont ID  
Sent By medwards Date 2022-05-04 Time 17:20 Rev Time 0.00
Received By medwards Date 2022-04-27 Time 07:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-25 Cont ID  
Sent By medwards Date 2022-04-25 Time 16:10 Rev Time 0.00
Received By medwards Date 2022-04-14 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-05 Cont ID  
Sent By medwards Date 2022-04-05 Time 16:39 Rev Time 0.00
Received By medwards Date 2022-03-30 Time 08:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-17 Cont ID  
Sent By vbroglia Date 2022-03-17 Time 11:56 Rev Time 0.00
Received By vbroglia Date 2022-03-09 Time 07:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-05-04 Cont ID  
Sent By medwards Date 2022-05-04 Time 17:19 Rev Time 0.00
Received By medwards Date 2022-05-04 Time 17:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-04-25 Cont ID  
Sent By medwards Date 2022-04-25 Time 16:09 Rev Time 0.00
Received By medwards Date 2022-04-25 Time 16:09 Sent To  
Notes
2022-04-25 16:10:073RD REVIEW FMC
 PERMIT: 22030298
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE CONSISTENT DOCUMENTS. THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS ARE FOR A 2-TON DUCTLESS
 SYSTEM ? CHURCH FOOD STORAGE. THE ENERGY CALCULATIONS
 ALSO SHOW 1 2-TON DUCTLESS HEAT PUMP. THE MECHANICAL
 DRAWINGS ARE BLURRY AND YOU CANNOT READ THE WRITING.
 PLEASE PROVIDE CLEAR DRAWINGS. THE MECHANICAL DRAWINGS
 ALSO SHOW A TOTAL OF 2 A/C UNITS, THIS DOES NOT MATCH
 THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE
 SHOW THAT THESE A/C UNITS PROVIDE THE REQUIRED HEAT FOR
 THIS SPACE. THE MECHANICAL DRAWING IS TITLED CHURCH A/C
 SYSTEM PLEASE LABEL THIS DRAWING TO CLEARLY IDENTIFY
 WHERE THE SYSTEMS SILL BE LOCATED. PLEASE SHOW HOW THE
 REQUIRED OUTDOOR AIR WILL BE BROUGHT INTO THIS
 BUILDING. PLEASE PICK A DESIGN AND MAKE EVERYTHING
 SUBMITTED AS ONE SYSTEM. THERE ARE TOTALLY DIFFERENT
 DRAWINGS IN THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS THAN THE MECHANICAL DRAWING SUBMITTED. I
 CANNOT DO A REVIEW ON THIS PROJECT UNTIL THE DOCUMENTS
 ARE SUBMITTED CORRECTLY FOR ONE DESIGN. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-04-05 Cont ID  
Sent By medwards Date 2022-04-05 Time 16:38 Rev Time 0.00
Received By medwards Date 2022-04-05 Time 16:38 Sent To  
Notes
2022-04-05 16:38:582ND REVIEW FBC-2020 MECHANICAL
 PERMIT-22030298
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT CLEAR DETAILED DRAWINGS THAT SHOW
 EXACTLY WHAT IS BEING INSTALLED. I CANNOT READ THE
 DRAWINGS AND IT IS NOT CLEAR AS TO WHAT IS BEING
 COMPLETED FOR THIS PROJECT. IS THERE TO BE 2 BUILDINGS
 OR IS THE DRAWINGS TRYING TO SHOW N,S,E,W, ELEVATIONS?
  
 2) PLEASE PROVIDE THE PERMIT NUMBER FOR THE NEW
 BUILDING.
  
 3) WHAT IS THE USE OF THIS NEW BUILDING?
  
 4) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS
 NEW BUILDING.
  
 5) PLEASE PROVIDE A SITE PLAN THAT CLEARLY IDENTIFIES
 THE BUILDING THAT THIS MECHANICAL SYSTEM WILL BE
 INSTALLED IN. THERE ARE SEVERAL BUILDINGS ON THIS
 PARCEL. FBC 107.2.1
  
 6) PLEASE PROVIDE THE ENERGY CALCULATIONS SHOWING THE
 TYPE OF WALLS, DOORS, WINDOWS, INSULATION. THE ENERGY
 CALCULATION SUBMITTED IS NOT A STANDARD ENERGY
 CALCULATION. FEC C402.
  
 7) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS BASED ON THE MINIMUM REQUIREMENTS OF
 MANUAL N OR BY AN APPROVED EQUIVALENT COMPUTATIONAL
 PROCEDURE USING THE DESIGN PERIMETERS SPECIFIED IN
 CHAPTER 3 OF THE FEC OR YOU MAY CHOOSE TO MEET THE
 EXCEPTION AND HAVE A LICENSED ENGINEER DESIGN THE
 SYSTEM. FEC C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-14 Cont ID  
Sent By medwards Date 2022-03-14 Time 16:06 Rev Time 0.00
Received By medwards Date 2022-03-14 Time 16:06 Sent To  
Notes
2022-03-14 16:06:421ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22030298
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A SCOPE OF WORK FOR THIS PROJECT. IS THIS
 FOR A NEW CONSTRUCTION BUILDING? IF SO, PLEASE PROVIDE
 THE ENERGY CALCULATIONS AND THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS. THERE IS NOT ENOUGH INFORMATION
 SUBMITTED TO DO A COMPLETE REVIEW. FBC 107.2.1
  
 2) THE DESIGNERS OF THE DRAWINGS MUST PRINT AND SIGN
 EACH DRAWING. WPB AMEND 107.2.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-05-04 Cont ID  
Sent By medwards Date 2022-05-04 Time 17:20 Rev Time 0.00
Received By medwards Date 2022-05-04 Time 17:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-03-14 Cont ID  
Sent By medwards Date 2022-03-14 Time 16:07 Rev Time 0.00
Received By medwards Date 2022-03-14 Time 16:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-04-21 Cont ID  
Sent By vbroglia Date 2022-04-21 Time 14:14 Rev Time 0.00
Received By vbroglia Date 2022-04-21 Time 14:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-04-05 Cont ID  
Sent By vbroglia Date 2022-04-05 Time 13:05 Rev Time 0.00
Received By vbroglia Date 2022-04-05 Time 13:05 Sent To  
Notes
2022-04-05 13:06:294/5/2022 FAILED
  
 PLEASE REVIEW PREVIOUS COMMENTS AND ADDRESS
  
 VALENTINA BROGLIA

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-17 Cont ID  
Sent By vbroglia Date 2022-03-17 Time 11:53 Rev Time 0.00
Received By vbroglia Date 2022-03-17 Time 11:53 Sent To  
Notes
2022-03-17 11:56:173/17/2022 FAILED
  
 PLEASE PROVIDE A SITE PLAN OR SURVEY SHOWING THE
 LOCATION OF THE MECHANICAL EQUIPMENT AND THE DISTANCE
 FROM THE PROPERTY LINE
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  